HomeMy WebLinkAboutPAPERWORK FROM SALAS OBRIEN3501 Quadrangle Blvd., Suite 100 SALASO'B RI E N' expect a difference February 02, 2022 SHOP DRAWING REVIEW COMMENTS Reference: Trane WPB SLC Rack Road Jail Chiller #3 Salas O'Brien Florida #2104404 Subject: SUBMITTAL ID: 01 Trane Equipment Submittal Reviewed By: Joseph Detig, P.E. Mahaley Vann Orlando, Florida 32817 407.380.0400 1 www.salasobrien.com SCANNED Y Engineer's review is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication processes, for techniques of assembly, and for performance of work in a safe manner. OVERALL DISPOSITION: NO EXCEPTIONS TAKEN FILE COPY ST. LUCIE COUNTY BUILDING DIVISION REVIEWED FOR OMPLIANCE REVIEWED BY DATE PLANS AND PERMIT MUSTBE KEPT ON JOB OR NO INSPEnGN WILL BE MADE END OF DOCUMENT Prepared For: St Lucie County Submittal Date: December 29, 2021 Job Name: SLC - Rock Road Jail Chiller Repl 2021 Trane U.S. Inc. is pleased to provide the following submittal for your review and approval. Product Summary Qty Product 1 Centrifugal Water Chiller (CH-3) Chris Cowling Trane U.S. Inc. 6965 Vista Parkway North, Suite 11 West Palm Beach, FL 33411 Office Phone: (561) 683-1521 Please Note: The attached information describes the equipment we propose furnish for this project, and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customer's responsibility to obtain such verification. Contractors & Engineer to review submittal for accuracy before order is placed. ELECTRONIC SHOP DRAWING REVIEW By: Salas O'Brien Florida, Inc. NO EXCEPTIONS TAKEN ,Nrmy m< m.eao� nl� e.vi­MS am mMrWlm ee1en-1w .r,emt„,marten,.1m10 wN.aee ia, a<um ma =w.r..a—V A ,tir .-M �m...ab,.�mr,�a .Id ..nHn� .n w+.mk...e sine ...hnekanng+GOApae<r.m¢ eee,a m.renKnnq,. Ky: Kyle J. ea,uer, FM a:mvmu © 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl - 11-23-21.docx Table of Contents ProductSummary ...........................................................................................................................................................1 Centrifugal Water Chiller (Item Al) ...............................................................................................................................3 TagData....................................................................................................................................................................... 3 ProductData.................................................................................................................................................................3 ProductReport ..............................................................................................................................................................4 MechanicalSpecifications............................................................................................................................................6 DimensionalDrawings................................................................................................................................................13 Weight, Clearance & Rigging.....................................................................................................................................19 Accessory...................................................................................................................................................................21 FieldWiring.................................................................................................................................................................23 Field Installed Options - Part/Order Number Summary ............................................................................................25 CentrifugalWater Chiller............................................................................................................................................25 © 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl - 11-23-21.docx SLC - Rock Road Jail Chiller Repl 2021 Tag Data - Centrifugal Water Chiller (Qtv"l) November 23, 2021 Item Ta s Qt Description I Model Number Al I CH-3 1 1 1 Centrifugal Chiller CTV I CVHE045 Product Data - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Standard ship cycle CVHE, CVHF & CVHG Centrifugal liquid chiller with 3 stage compressor Compressor size: 450 nominal tons Adaptiview controls Compressor motor voltage: 460 volt 3 phase Compressor motor power: 234 kW Motor frame size: 440E Compressor impeller cutback: 230 Orifice size: 400 nominal tons Evaporator: Evaporator shell size: 050 short Evaporator bundle size: 580 nominal tons Evaporator tubes: 0.75 inch (19.1 mm) dia. internally enhanced copper Evaporator tube wall:.025 inch (0.6 mm) thick Evaporator fluid type: Water Evaporator waterbox type: Non -marine Evaporator waterbox construction: Standard Evaporator water box passes: Two pass Evaporator waterbox pressure: 150 psig (1034 kPa) Evaporator waterbox connection: Victaulic Evap waterbox arrangement: in RH end - out RH end Thermal dispersion flow switch (IFM) - Field Installed (Fld) Condenser: Condenser shell size: 050 short Condenser bundle size: 500 nominal tons Condenser tube: 0.75 inch (19.1 mm) internally enhanced copper Condenser tube wall:.028 inch (0.7 mm) thick (thicker tube option) Condenser shell construction: Standard Condenser fluid type: Water Condenser waterbox type: non -marine Condenser waterbox construction: Standard Condenser water box passes: Two pass Condenser waterbox pressure: 150 psig (1034 kPa) Condenser waterbox connection: Victaulic Condenser waterbox arrangement: in RH end - out RH end Thermal dispersion flow switch (IFM) - Field Installed (Fid) Misc/Electrical: Agency listing: U.L. listed unit (United States requirement) Factory performance test: Standard air run and vibration test Selection tolerance: AHRI Standard tolerance Brass logo with customer specified engraving No unit insulation package — insulation in the field by others AHRI Certified, Complies with ASHRAE 90.1 - 2016 Generic BAS / BACnet interface Trane-supplied R514 Refrigerant, Shipped loose for field installation at start-up Low Voltage Wye -Delta Starters Starter type: Unit Mounted Wye -Delta Starter maximum RLA: 346 Amps Starter power connection: Circuit Breaker High -Interrupt Starter power connection maximum RLA: 296 Amps Starter option: Surge protector/lightning arrestor Factory Start-up 10 year Parts, Labor & Refrigerant warranty Qty 1, Refrigerant Sensor for existing Sherlock Refrigerant Monitor (Fld) — See end of submittal for data sheet Equipment Submittal Page 3 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Product Report - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 r-T._... _. ..07 " Applidofion ty-o ;Standard cooling��'����� Troeor Controls BACne� f''~��] _'— Compmf�or�460__� Impollar1230 t Oy:f00._._�...........��.�_. S rifice 4 Certified in accordance with the AHRI Water -Cooled Water - Chilling and Heat Pump Water -Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found In the AHRI Directory at www.ahridirectory.org. Equipment Submittal Page 4 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Product Report - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Corapliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4) due to the R-514A refrigerant GWP being less than 2. Note: Trans recognizes and respects the U.S. Green Building Council® mandate that a default 2 % Refrigerant Leakage Rate (Lr) be used by all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there Is no IndustZ standard. yrane has exhaustively documented a leak rate of less than 0.5%for CenTmVac- chillers (models CVHE, CVHF, CVHG. CVHS, CVHM, DHF, CDHG, CVHH and CDHH) and utilizes an average design refrigerant charge of less than 2 lb./ton. The U.S. Green Building Council's LEER® green building program is the preeminentprogram for the design, construction, maintenance and operations of high-performance green buildings. It provides Independent, third -party verification pal a building project meets the highest green building and performance measures. Trans Select Assist 55235 Version Number. Data Generation Date: 10/4/2021 Equipment Submittal Page 5 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Mechanical Specifications - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 Compressor -Motor Direct drive multiple -stage compressor, multi -stage capacity control guide vanes. Shrouded aluminum alloy impellers dynamically balanced. Motor -compressor assembly balanced to .15 in./sec (.0038m/sec) maximum vibration measured on motor and bearing housings. Refrigerant cooled, hermetically sealed, two -pole, squirrel cage induction motor. Two pressure lubricated bearings support the rotating assembly. A direct drive submerged oil pump motor, 3/4 hp (.560 kW) 115V/50/60/1 provides filtered and temperature controlled oil to compressor bearings. Evaporator -Condenser Shells are carbon steel plate. Evaporator includes rupture disk per BSR/ASHRAE 15 Safety Code. Carbon steel tube sheets are drilled, reamed and grooved to accommodate tubes. Tubes are individually replaceable externally finned seamless copper. Tubes are mechanically expanded into tube sheets. Eliminators are installed over entire length of the evaporator tube bundle. A multiple orifice control system maintains proper refrigerant flow. Condenser baffle prevents direct impingement of compressor discharge gas upon the tubes. Refrigerant side of the assembled unit is tested at both pressure(30.00 psi leak test) and vacuum. Water side is hydrostatically tested at one and one-half times design working pressure, but not less than 225.00 psi. Trane reserves the right to implement chiller technology enhancements that will reduce the chiller's refrigerant charge, with no impact on chiller performance. Changes may be reflected in the chiller's nameplate refrigerant charge and the quantity of refrigerant charge shipped to the jobsite, depending upon the final date of equipment manufacture. Water Boxes Drains and vents - Water boxes typically have 3/4-inch NPTI vents and drain connections provided. Evaporators have 2 vents and 2 drains, condensers have 1 vent and 1 drain. If grooved connections are offered, the design is based on Style 77. Non -marine water boxes have water connections that extend out from the end. Economizer A flash economizer with no moving parts provides power saving capability. Purge System The EarthWise(TM) purge includes a 1/4 hp 115V/60/1, 100V/50/1 air cooled condensing unit, purge tank, drier elements, and a 1/20 hp (.037 kW) 115V/60/1, 110V/50/1 pump -out compressor. The purge is designed with an activated carbon filtration system that includes an autoregeneration feature which results in automatic high -efficiency removal of noncondensibles from the chiller without manual carbon maintenance. The purge meets Green Seal GS- 31 with a leak rate less than 1.0% of the charge per year and also meets ASHRAE 147 with a leak rate of less than one unit mass of refrigerant per unit of air. AdaptiView Control Panel: The Tracer(tm) AdaptiView is a microprocessor -based chiller control system that provides complete stand alone system control and monitoring for the water cooled CenTraVac (TM). It is a factory mounted package including a full complement of controls to safely and efficiently operate the CenTraVac chiller, including oil management, purge operation, interface to the starter, and comprehensive motor protection including three phase solid state motor overload. Inlet and outlet water (fluid) temperature sensors are located in the evaporator and condenser waterbox connections as standard. The display is a touch sensitive 12 1/8" diagonal color liquid crystal display (LCD) that uses color graphics and animation to ensure ease of use. The touch sensitive interface allows the operator to view the chiller graphically and receive a status indication via subsystem animations. The operator can navigate easily between the primary chiller subsystems including: compressor, evaporator, condenser, and motor. For each subsystem, you can view status and detailed operating parameters. In addition, alarms, reports, trending, and settings can all be accessed quickly from the main screen. The display is mounted on a flexible "arm" that allows extensive height and viewing angle variations. The panel supports an extensive list of languages including the default English. The data can be set to be viewed in inch pounds IP or metric units SI. For remote starters - Class 1 control panel voltage (30-115 V) are clearly labeled in the control panel. Class 2 input voltage (30V max) is also labeled in the control panel. Equipment Submittal Page 6 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Operating Data including: 0 *operating hours *number of starts *chilled water setpoint *evaporator and condenser water flow status *evaporator entering and leaving water temperatures *evaporator saturated refrigerant temperatures *evaporator approach temperature *evaporator refrigerant pressure *condenser entering and leaving water temperatures *condenser saturated refrigerant temperatures *condenser approach temperature *condenser refrigerant pressure *oil differential pressure *oil tank temperature *purge mode *purge average daily pump -out time *% RLA per phase for motor *RLA per phase *volts per phase *power factor *kw *kwh *frequency The AdaptiView also contains the following dedicated reports: Evaporator, Condenser, Compressor, Motor, Purge, and ASHRAE. Each report is comprised of a detailed listing of operational data relative to that chiller subsystem. Control functions including: *leaving chilled water temperature *percent demand limit *chiller water reset (based on return water temperature *front panel control type *setpoint source *differential to start *differential to stop Status data including: *waiting to start *running *run limit *run inhibit (adaptive) *auto *free cooling (option) *preparing to shutdown *shutting down (post lube) *stopped Safeties including: Automatic safety shutdown for: *Low chilled water temperature, *low evaporator refrigerant temperature *high condenser refrigerant pressure *evaporator and condenser flow status *low evaporator/condenser differential refrigerant pressure *low oil pressure *oil pressure overdue *high or low oil temperature *high bearing oil temperature (requires enhanced protection option) *high motor current Equipment Submittal Page 7 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 *high motor temperature *starter function faults *critical temperature and pressure sensor faults The devices are of a latching trip out type requiring manual reset. Non -latching safety trip outs for operating conditions external to the chiller automatically permits unit to resume normal operation when condition is corrected. Advanced motor protection monitors 3-phase current to provide latching trip out protection from adverse effects of phase loss, phase unbalance, phase reversal, loss of phase reversal protection, and electrical distribution faults (momentary power loss) by instantaneous trip out of motor. Surge protection - Detects surge and limits chiller loading through inlet vane modulation. Head relief through lowering cooling tower water temperature can be requested. If not corrected within 7 minutes, chiller is shut down. Enhanced Adaptive Control(TM) - Built in intelligence to keep the chiller on line (safely making maximum tons) while simultaneously preventing chiller damage/failure. During any chiller limiting mode of operation, the control panel enunciates the condition via a relay output. Trending: The controller provides 10 standard graphs for trending multiple parameters, The operator can add an additional 6 custom graphs if desired. On anyone custom graph, the operator can choose to trend up to 10 unique parameters from a more comprehensive list. Two Y axes are available for any graph to facilitate readability. Diagnostics: AdaptiView includes comprehensive diagnostic monitoring. All active diagnostics are available, and up to 20 historic diagnostics are communicated to the operator via the 12 1/8" LCD display with graphic navigation system. Each diagnostic is time and date stamped. Service Tool: A PC -based service tool called Tracer TU, connected to the chiller via USB port, is available for additional cost and displays the last 100 diagnostics, indicating the time, date of occurrence, and system parameters at the time of the diagnostic. The service tool provides advanced troubleshooting and access to sophisticated configuration settings not needed during operation of the chiller. Security: The AdaptiView can be set to prevent unauthorized access to the chiller settings. The operator can choose to secure the operating settings with a password. Data and reports can still be accessed once the settings are locked out. The memory for the AdaptiView is non-volatile type, so if power is lost, operating settings are retained. A life time battery is standard, which is used only to support the clock function for the chiller. Chilled and Condenser water pump relays: Chilled water and condenser water pump relays are provided and it is recommended that they be used for pump control. BACnet(MSTP) Direct Points List: The following points are available directly from the chiller. Recognize that some of these points require chiller options or configurations. Inputs Including Chiller Auto/Stop Chiller Mode (e.g. cool) External Base Loading Enable/Disable (requires Extended Operation option) External Base Loading Setpoint (requires Extended Operation option) Chilled Water Setpoint Current Limit Setpoint Heating Setpoint (requires Extended Operation option) Wall Mounted Refrigerant Specific Monitor (requires Extended Operation option) Clear Diagnostics Outputs Including Evaporator Pump relay Equipment Submittal Page 8 of 25 SLC • Rock Road Jail Chiller Rapt 2021 November 23, 2021 Condenser Pump relay Chilled Water Flow Status Condenser Water Flow Status Evaporator Water Flow Rate (requires Flow Compensation option) Condenser Water Flow Rate (requires Flow Compensation option) Chiller capacity (requires Flow Compensation option) Leaving Chilled Water Temperature Entering Chilled Water Temperature Entering Condenser Water Temperature Leaving Condenser Water Temperature Second Condenser Entering Water Temperature (requires HR or Aux condenser bundle) Second Condenser Leaving Water Temperature (requires HR or Aux condenser bundle) Active Chilled/Hot Water Setpoint Active Current Limit Setpoint Active Base Loading Setpoint (requires Extended Operation option) Head Relief Request relay Compressor Running relay Chiller On/Off Limit Warning relay Maximum Capacity relay Alarms Description'! Manual Reset Alarm relay Auto Reset Alarm relay Purge Alarm relay Alarm Reset Condenser Refrigerant Pressure Condenser Refrigerant Temperature Evaporator Refrigerant Pressure Evaporator Refrigerant Temperature Compressor Discharge Refrigerant Temperature (requires Enhanced Protection option) Differential refrigerant pressure (not for head pressure control) Operating Status (Alarm, Run Enabled, Local Control, Limited) Chiller Modes (i.e. Off, Starting, Running, Shutting Down) Base Loading Active (requires Extended Operation option) Hot Gas Bypass Active (requires Hot Gas Bypass option) Operating Mode (e.g. Cool) Current Per Line Voltage Per Phase Unit Power Consumption (kW) Motor winding temperature Motor power factor (uncorrected) Oil Temperature Oil Pressure Differential High Side Oil Pressure Low Side Oil Pressure Compressor Starts Compressor Run Time Inlet guide vane position Inboard bearing oil temperature (requires Enhanced Protection option) Outboard bearing oil temperature (requires Enhanced Protection option) Purge Status2 Purge pumpout Average (24 hour) Purge pump -out Purge regeneration Purge carbon tank temperature Purge liquid temperature Purge suction temperature Purge time to next purge run Purge pump -out chiller on-7 days Purge pump -out chiller off-7 days Purge pump -out life Equipment Submittal Page 9 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Purge regeneration life Refrigerant Monitor AFD output frequency AFD transistor temperature Hardwire BAS Interface provides: Chilled Water Setpoint input - Provides for setpoint adjustment of control point from multiple sources Current Limit Setpoint input - provides for setpoint adjustment of control point from multiple sources Percent RLA Output - provides % RLA output Condenser Pressure Output - A hardwire output signal of condenser pressure, or differential pressure between the evaporator and condenser is provided. Operating Status: The following hardwire binary outputs are available: Compressor running relay Alarm relay - manual reset Alarm relay - auto reset Limit warning relay Purge alarm relay Head relief request relay Maximum capacity relay Evaporator Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM Installation manual (PART-SVN223'-EN) notes shipped with your rupture guard /contact local Trane sales office Condenser Proof of Flow - Thermal Dispersion A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field installation in the ship with components box. Follow the installation instructions in the chiller installation manual. Reference specific IFM Installation manual (PART-SVN223'-EN) notes shipped with your rupture guard /contact local Trans sales office Paint All CenTraVac(TM) painted surfaces are coated with a primer and an air-dry beige primer -finisher prior to shipment. Isolation All units ship with neoprene isolator pads as standard, except when spring isolators are chosen. Enough pads are provided to cover the area under the chiller supports. Shipment All units are of hermetic design, leak tested, charged to 5.00 psi and shipped as a single factory assembled package. Full oil charge shipped in oil sump. Refrigerant shipped to jobsite from refrigerant manufacturer. The entire chiller is shrink wrapped for protection. Unit Mounted Starter Wye Delta -Reduced Voltage, NEMA 1A (vented) enclosure with a gasket. Starter factory mounted and completely prewired to compressor motor and control panel. Factory run testing assures proper circuitry and operational reliability. The Wye Delta starter is a reduced voltage starter and therefore draws - 33% of locked rotor amps (LRA), and the motor acceleration time is 5-12 seconds typically. The starter is designed and tested in accordance with UL 1995 Features include: 115 volt control power transformer to power chiller unit controller, purge and oil system. Therefore, with line power, no other power is needed for auxiliary equipment on the chiller. Equipment Submittal Page 10 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Environmental specification: Operation from sea level to 6000 ft (1829 m). Operating ambient temperature range 32.0 F to 104.0 F. Non -operating ambient temperature range -40.0 F to 158.0 F. Relative humidity, non -condensing 5% to 95% through the ambient temperature range. Voltage utilization ±10 % Top of starter includes access area for a wiring entrance area. Bottom entry for line power is not available. Terminal block connection is standard. Circuit breakers may be included as an option. See the following submittal pages for disconnect ratings and lug information on these optional disconnects if offered. Starter installer responsibilities The following are considered functions normally required of the equipment installer for unit mounted starters. Remove access area panel for line side wiring. The upper right quadrant of the starter provides recommended access to starter/disconnect lugs. The starter can accommodate top line power entry only. Provide and install field wiring to line side lugs of starter. Required Installer Responsibilities The following are considered functions normally required of the equipment installer./n Install unit on a foundation with flat support surfaces level within 1/16" and of sufficient length to support concentrated loading. (Spring isolators should be considered whenever chiller installation is planned for an upper story location.) Place isolation pads or optional spring type isolators provided by the chiller manufacturer under the unit. When spring isolators are chosen, no pads are provided. Install unit per applicable Trane Installation Manual. Complete all water and electrical connections. Where specified, provide and install valves in water piping upstream and downstream of the evaporator and condenser water boxes as means of isolating shells for maintenance and to balance and trim system. Furnish and install a flow switch or equivalent device in both the chilled water and condenser water piping properly interlocked to insure that unit can operate only when water flow is established. Furnish and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections of both evaporator and condenser. Furnish and install drain valves to each water box. Install vent cocks on each water box. Furnish and install strainers upstream of chiller evaporator and condenser bundles to protect tubes from potential damage caused by debris in the circulating water. Note: Failure to install strainers in all water piping entering the chiller could result in tube plugging conditions that could damage unit components. If the circulating pumps are immediately upstream of the chiller bundles, then the strainer can be installed immediately ahead of the pumps. If the circulating pumps are downstream of the chiller bundles, then the strainers should be installed immediately ahead of the chiller bundles. Furnish sufficient refrigerant 25.0 lb per machine and dry nitrogen 50.0 lb per machine for pressure testing under manufacturer's supervision. Start-up unit under supervision of a qualified Trane field engineer Where specified, insulate evaporator and any other portions of machine required to prevent sweating under normal operating conditions. Water connection piping must not transfer forces to the chiller. Because of cumulative tolerances in manufacture and field installation, prepiping of water connections closer than 36" is not recommended. Any problems associated with prepiping of water connections closer than 36" to the chiller are the responsibility of the installing contractor. Equipment Submittal Page 11 of 25 SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Furnish and install vent lines for rupture disk and purge venting to atmosphere per ASHRAE 15 and unit installation manual. If RuptureGuard-Relief Valve option is ordered, remove factory rupture disk and install RuptureGuard-Relief Valve per the IOM manual. In some chiller configurations the RuptureGuard may not bolt directly to the chiller flange. Locally sourced and approved piping may be required between the chiller and the RuptureGuard. Field Disassembly With chillers that may require field disassembly (for example due to clearance concerns during unit installation) reference the Disassembly and Reassembly manual and your Trane Sales representative prior to the order being placed. Caution: if certain components are removed in the field, for example the economizer, the necessary components (gaskets, seals, etc.) are not provided as standard. Leak -Tight Warranty The CenTraVac chiller features a 5-year limited Leak -Tight Warranty which is valid for the lesser of 60 months from initial start-up or 66 months from date of shipment. The limited Leak -Tight Warranty covers models CVHE/F/L, CVHS, CVHM and CDHF chillers installed in the United States or Canada. The Company's obligations and liabilities under this warranty are limited to furnishing replacement refrigerant; no other parts or labor are covered under this limited warranty. No liability whatever shall attach to the Company until appropriate actions have been taken (acceptable to Company) to eliminate the source of the leak, and then said liability shall be limited to furnishing the replacement refrigerant. If the chiller is placed under a comprehensive Trane service and maintenance agreement (Trane Select Agreement or better) prior to the expiration of the standard Leak -Tight Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption. If a 10-Year Parts, Labor and Refrigerant Warranty was purchased for the chiller and the chiller is placed under a Trane Select Agreement (or better) prior to the expiration of the 10-Year Parts, Labor and Refrigerant Warranty, the protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without interruption Equipment Submittal Page 12 of 25 a LEFT SIDE VIEW CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAYBE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE -P1/T". COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. TOP VIEW FRONT VIEW RIGHT SIDE VIEW SHELLTYPE CONN DA CONNTYPE FLOWDIRECTION EVAPORATOR 8" VICTAULIC IN REAR OUT FRONT COOLING COND 8" VICTAULIC IN BOTTOM OUT TOP to A a CVHE Compressor sae: 450 Erap shall sae: 050S Cord shell size. 050S Without additional condenser Ads (ooci screw 16 nom mamee (See accesserydrowin9 for details) CUSTOMER NOTES: GRMHIC6 ON SUBMITTAL ME SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE H-1/2". COOLING COND CONNS ME STRAIGHT OUT THE END OF THE WATER BOX WATER BOX DRAIN AND VENT LOCATIONS ME SHOWN ON THE WATER BOX END PLATES, TOP VIEW SHELLTYPE CONN DIA EVAPORATOR COOLING COND after CONNTYPE FLOWDIRECTION VICTAULIC IN REM OUT FRONT VICTAULIC IN BOTTOM OUT TOP CD w 0 3 a CVHE Compressor slzei 450 Evap shell sae050S Cond shell size. 050S Without additional condenser CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY. UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES, FRONT VIEW SHELLTYPE CONN DA EVAPORATOR COOLING COND CONNTYPE FLOWDIRECTION VICTAULIO IN REAR OUT FRONT VIOTAULIC IN BOTTOM OUT TOP a m 10 m m O N U CVHE Compressor size; 450 Evap shell saw 0SOS ConC shell size. 0505 Wi addi0onal condenser LEFT SIDE VIEW CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE -FI/Z. COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX, WATER BOX ORAN PNO VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES. SHELLTYPE CONN DA CONNTYPE FLOWDIRECTION EVAPORATOR B" VICTAULIC IN REAR OUT FRONT COOLING COND 8" VICTAULIC IN BOTTOM OUT TOP Z O G 3 3 Q m N W N O N 3 if CVHE Compressor sizo: 450 Evap shell sue'0505 Cone shell size, 050S Without additicnal condenser 98 CUSTOMER NOTES: GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS. UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLMITY, UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE 41Q'. COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX. WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.. RIGHT SIDE VIEW SHELLTYPE CONN DA EVAPORATOR S, COOLING COND S" CONNTYPE FLOWDIRECTION VICTAULIO IN REAR OUT FRONT VICTAULIC IN BOTTOM OUT TOP to n 3 m hi LEFT SIDE VIEW SHIPPINGWEIGHT " 17,244.01E OPERATING WEIGHT 19,217.01E COMPRESSOR SIZE 450 EVAPORATOR SIZE 050S EVAPORATORWATERPASS 2 EVAPORATORWATERBO%ARANGEMENT RERE CONDENSER SIZE 050S CONDENSERWATERPASS 2 CONDENSERVA ERSO%ARRANGEMENT I RERE ALL PUBLISHED WEIGHTSACCURATE TO •/-10 % "SHIPPING WEIGHT INCLUDES REFRIGERANT. IF ORDERED WITHOUT, CONSULT PRODUCT SUPPORT FOR DRY SHP WEIGHT. TOP VIEW SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Weight, Clearance & Rigging - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 WEIGHTS AND CENTER OF GRAVITY LEFT LEFT RIGHT REAR RIGHT FRONT SPRING ISOLATOR SELECTION LOCATION ISOLATORLOAD' VENDOR PM TRANEP/N ISOLATOR COLOR LEFT FRONT 4,583.0 RE LEFTREAR 3,570B It, RIGHT FRONT 6.1150lb RIGHT REAR 4.08.01b LEFTMIDDLE N!A RIGHTMIDDLE NIA COMPONENT WEIGHT' COMPRESSOR WEIGHT 5,418.0I1, MOTOR WEIGHT 1,832.01b STARTER WEIGHT MiTO Ib SUCTION ELBOW WEIGHT 26001b ECONOMIZER WEIGHT 635B1b EVAPORATORWEIGHT 4,025.0m EVAPORATOR WATERBOXES WEIGHT 83001b CON DENSER WEIGHT 2d5d.016 CON OENSER WATERBOXES WEIGHT 399.0I1, HEAT RECOVERY CONDENSER MEG HT NIA FAT RECOVERY CONDENSER WATERBOXES WEIGHT N/A FAUXILIARY CONDENSER WEIGHT N/A AUXILIARY CONDENSER WATERBOXES WEIGHT N/A M I SCELLANEO US WEIGHT 1,013.ON WEIGHTS SHIPPING OPERATING 17,244.0lb 19,217.00 UNIT CENTER OF GRAVITY CG Z(DIMENSION FROM RIGHTTO LEFT) 56000 in CG X(DIMENSION FROM FRONT TO REAR) 28A001n CG Y(HEIGHT DIMENSION FROM FLOOR) 45.000 in RIGHT FRONT ISOLATOR MOUNTING HOLE BOTTOM OF THIS HOLE IS 0,0,0 POINT FOR CENTER OF GRAVITY DIMENSIONS Y ZX� NAMEPLATE PRODUCT DESCRIPTION: MDIIX CVHE VOLT 480 PTON 300.00 bns ;TON 450 EVTM TECU COTM TECU CPRW 234 CPIM 230 COBS 500 EVSZ 050S EVBS 580 ORSZ 400 CDSZ 050S 'AlLPUBLISHEDWEIGHTSACCURATETO-/.10 % Equipment Submittal Page 19 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Weight, Clearance & Rigging - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 1. HEAVY OBJECTSI DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS SHOWN. EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT THE UNIT MUST BE CAPABLE OF SUPPORTING TH E ENTIRE WEIGHT OF THE UNIT LIFTING CABLES (CHAINS OR SLINGS) MAY NOT BE OF THE SAME LENGTH. ADJUST AS NECESSARY FOR EVEN UNIT LIFT. OTHER LIFTING ARRANGEM ENTS MAY CAUSE EQUIPMENT OR PROPERTY -ONLY DAMAGE. FAILURE TO PROPERLY LIFT UNIT MAY RESULT IN DEATH OR SERIOUS INJURY SEE DETAILS BELOW 2. IMPROPER UNIT LIFTI TEST LIFT UNIT APPROXIMATELY 24 INCHESTO VERIFY PROPER CENTER OF GRAVITY LIFT POINT. TO AVOID DROPPING OF UNIT, REPOSITION LIFTING POINT IF UNIT IS NOT LEVEL. FAILURE TO PROPERLY LIFT UNIT COULD RESULT IN DEATH OR SERIOUS INJURY OR POSSIBLE EQUIPMENT OR PROPERTY -ONLY DAMAGE. 3.ATTACH SAFETY CHAIN OR CABLE AS SHOWN WTTHOUTTENSION, NOT AS ALIFTING CHAIN OR CABLE, BUTTO PREVENTTHE UNIT FROM ROLLING. C DO NOT FORKLIFTTHE UNITTO MOVE OR LIFT. 5. LIFTING HOLES PROVIDED ON CHILLER TOATTACH CABLES (CHAINSOR SLINGS). 6. 36' (900 MM) RECOMMENDED CLEARANCEA90VE HIGHEST POINT OF COMPRESSOR. Q FOLLOWNEG SECTION 110 AND OTHER APPLICABLE LOCALCODES FOR CLEARANCES IN FRONT OF ELECTRICAL ENCLOSURES. 8. SPECIFIC SHIPPING AND OPERATING WEIGHTS OF THE SUBM"ED CHILLER ARE PROVIDED IF THE CENTRIFUGAL CHUER SELECTION WAS ENTERED IN TOPSS. DETAILED LOAD POINT AND SPRING ISOLATOR APPLICATION WEIGHTS ME AVAUABLE FROM'CENTRAVAC ISOLATOR SELECTION REPORT' AVAILABLE FROM THE REPORT GENERATOR OFTHETRANETOPSS CHILLER SELECTION PROGRAM. CONTACT YOUR LOCALTRANE SALES ENGINEER IF THIS DATA IS REQUIRED. 5' TYP (127mm) 4 X.88(22mm) 2SIT TYP(67mm) DIAHOLES FOR 13116" TYP(3dom) ANCHORING UNIT EVAPORATOR 2'TYP TUSESHEET (51mm) HOLE DETAIL TYP r - SAFETY CHAINS OR CABLES 16fi MINIMUM=4B77mm (SEE NOTE 8 ABOVE) XI MAMUMSHIPPWG 17,244G Ib MAXIMUM OPERATING 1 19,21TO Ib 34 114- DIMENSIONN MCLUDESTUBESHEETS 44112, 135, 320 12' 141" Equipment Submittal Page 20 of 25 .SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Accessory - Centrifugal Water Chiller Item: Al Qty: 1 Tag(s): CH-3 ADAPTIVIEW CONTROL PANEL TOP VIEW O O O O 63'4 O O ------------- 1 va'DIAHOLE 20. 11,p� TYPICALHOME / DANDLE POSITION 1 2X 1 5116- 1 NOTE: DISPLAY CAN MOVE TO AN INFINITE NUMBER OF POSITIONS. REF -BOTTOM FRONT OF PANEL DOOR I ✓'� LOKEST POSRION AVAILABLE Equipment Submittal Page 21 of 25 SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021 Accessory -Centrifugal Water Chiller 4 Item: Al Qty: 1 Tag(s): CH-3 UNIT MOUNTED WYE-DELTA STARTER tL BREAKER SHORT CIRCUIT CURRENT LINE CONNECTION LUGS I PANEL WTERNALWFIE SIZE AICAMPS RATINGS(RMSSYMETRICALAMPS) ME -DELTA STARTERS CONNECTION LENGTH 4DP 65 000 65,000 (2) 2i0- 50 OR (1)21U500 GBIC 25 POWER FACTOR CORRECTION CAPACITORS, WHEN SELECTED. ARE NOT CBIC= CIRCUIT BREAKER HIGH INTERRUPT CAPACITY INCLUDED IN THE UL SHORT CIRCUIT RATING OF THE STARTER. THE NON -FUSED DISCONNECT OR CIRCUIT BREAKER IS DESIGNED FOR USE ASA SERVICE DISCONNECT ONLY DOOR SWINGS TO THE LEFT FORAMAX OF 145 DEGREES & 38114" ELECTRICAL ENTRANCE r' 4 14' TOP TOP VIEW ALLOW MIN. FRONT WORKING SPACE CLEARANCE PER NEC ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS_ FRONT ELEVATION MAX DOOR SWING 145' & 36114"1972mm1 Equipment Submittal Page 22 of 25 ' ' SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021 Field Wiring - Centrifugal Water Chiller. Item: Al Qty: 1 Tag(s): CH-3 CAUTION USE CO W ER CON W CTORS Olan ATTENTION N'UTILISER DUE DES CBNDUCTEURS EN CUIVREI LES IMMES EE LWTC ME SUNS PAS S01NES POUR SZ.VBIR OLUIRCS i Rii SC CBNOLCIEIRS LVII PIN'mLHDdWfL¢ VHIUI CDIM1ICTLYR PRIECAUCOQN IUTILICE UNICAMENTE CONDUCTORES BE CDBRD LNO ESISH GSEA W PWA PCGEP'M WRLA BS TIME DE CO.MaTOIES. N M LO , IC WELE WAMD✓R I. x E.. DEVICE PREFIX CODE 1 •RWNUNITCONTROLPMIELDEVICE 2 = REMOTE MOU14TEDDEVEE 1 cUNITMOUNTEDDEVICE 5 v CUSTOMER PROVIDED DEVICE CUSTOMER SUPPLIED LINE VOLTAGE (SEE UNIT HAMEPLATE) GNO Lt L2 0 I I I I I I I I I I I I I I I I I I I I I I b b b d G Li L2 L3 201 OR tit DISCONNECT OR 2X3 TERMINAL BLOCK TRANE SUPPLIED UNIT MOUNTED LOW VOLTAGE WYE-DELTA STARTER PANEL WIRE NO OR DEVICE FIELD WIRING CIRCUIT SELECTION INFORMATION SUPPLYAND MOTORLEAD3 1M1 COMPRESSOR MOTOR LEADS SEE 11AlAEP1ATE: A11111AlUM1I CIRCUIT AMPACSS`/ 1A' 4 A AT I ISVAC, 8 AWG MAX WIRE SIZE 2A'ANO GRUNEL 1(100VA AT 1i5VAC, BAWG MAX WIRE SIZE(SVITHOUT OPTIONAL CPTR) 3B AND IB CIRCUIT PROTECTED AT 21A, IIWAD IN. 10 AWG MAX WIRE SIZE (WITH OPTIONAL CPTR) QA'AND 1DA' PUMP MOTOR, IN YE H P, 117 FIp 1E AWG MAX WIRE SIZE. OIRCU IT PROTECTED AT 15A. 110-120VAC IN WO, TWISTED, SHIELDED AMR, 30VDC, MAX LENGTH 1500 FT(AS72m) BELDEN TYPE 8780 RECOMMENDED MIT ', SST, 3B' AND 113' CIRCUIT P ROTECTED AT MA, IIWAC I PH. IO AWG MAX WIRE SZE 5 553 TNRU 58 bVDC.,U A RSTIVE LOAD, 14AWG MAX WIRE SIZE ALLREAWININGWDTERIANAIS PESI CONTATRAIG. 28BAIIJOUCTNE.In HP.D2-6VATSI-IMVAC 14AWGI.WWIRESZE NOTES: 'TWPEDCONTROLCONDUCTGRS 1 GASHED LILIES INDICATE RELDWIMNG SY OTHERS WIRE NUMBERS BHOVN ARE RECOMMENDED BY TRMIE. Z DO NOT ROUTE LOW VOLTAGE(XV) WITH CONTROL VOLTAGE(110-120V)AND 00 NOT POWER UNIT UNTIL CHECK-0UT MIOSTART-UP PROCEDURESHAVE BEEN COMPLETED, Equipment Submittal Page 23 of 25 ' ' SLC -Rock Road Jail Chiller Repl 2021 November 23, 2021 Field Wiring - Centrifugal Water Chiller . Item: Al Qty: 1 Tag(s): CH-3 ©TG EY%FORATM4 MJ] CClEE1EER 1. AM YJATER FLM CFIECIICN WNIROLLEIBUBTntt£O BY TR V E CVSTCuwSMPIIEO W BWIOMY R ANDCO(P.El5ER ATERPFOCF cf CF Fltl w W GEVKE9 ARE49AIO55 U. S95 PRUARY VFTERPR"OFROW DEACE: W ERXEIiSECRW RC W%)ER FA. OF ROW LEIICE$R V`ET O` FACTORY ME 54V EEMEEN U1-5 AID t Y$$d AtDPIBTALL55NA4BXONiy AlI W R W NE T BETYEEN t%K ANJ IYS]J AFD P6TALL 55 M LS SXO W N TRAIEIEW WIEIDS W P@YL SN1 EVAPCPANRANO2COID AB 51b`MJ TO ALLOWTXE 1454OOME00LLET0 CClRf9l PRMER SEOtIFJiRC. CAUTION I ATTE(sTMN NLTWSER WE DES CONUCTEMS w CVN [I Mi[W�2K]1Y�NI�E SiEflAtt.Wfrti � Tli oim,v[Ov LVECry[ �rmltl[�f PRECAUa6N IUTILICE MICN£RTE CMDXYOKS DE CDBK1 C.SI W ID WCL PI, KISIOUP MD /l CNPS OJBTCYERTOOIRECT EIXW 40 .O ER GE ZSTUSPUV 4gNT 593 IX]ERILL AV105IOP r�.x (Iffi10V-IUJfFR fiY$616EP. I M4 wwLeJw srPP � � _ _ IAwOVE MIPERTrv]611gq I N) x-1Dvoc `-- M%V RUCW PPE59CR WCPVI - NEIRdLPA9) 2. vO COIICffMRJIaEAP£FRILERV?P4IESSVFE LVFEREIIMI�PTES W EOUIPUT __ CCTDEl64RHJOP�aSViE CMRIAL D10VDCCR L2OM IXIFPINL CIPII.FNTWR$EIPgtR EXTER LR E D 11C.S CWLLEYATERSE)PCIM amaw AA �n — \ EVAPCMTORWATER AV% NLIPPIIEMOIX ` �ouPoly 59A $11 CON£tEER OA fWPPREPLOG FAIN UNT CUNTROL PANEL SM5 OR siANsou1. 1.1 NTE Llt.w EA. 7ER0,11NAL MNN�TICINS CWLLERALIPI.IPOIGTOH (4TERrN,E1 CPxNri4 Up — ET..- FN LIw FpC1OW CMPPAh CCrrtR0.lEL LT610L1EIi WdT/QE➢ �AD 9ICOR,dI/ACBB6 LA — Po\VER ONO X rl RR ,A„] usn.e o— ----1 i I `N1 I IASJid C- -F--O-o-O---� EYAPMTORWATER '741 PW PIENY OPTICIYL " Ns]zo o_ I ___Y x2 I —b N9J:1 +ASJxI O 1 O.YBEIEEIt WA]ER I pLLIP TEIAY fEOURED -'" NOR-9 O --1 b NAJa3 lSM� �� A= AIARtl PITM_'ALCR oPrDINL (CEFAIED uena o_ ___- I —b N9JaA Bu —b N15JPt Na J2-1 O —� ���CCYYY AIARYPPJGTOR —b NiSI]-3 UPR-9 O— OPIb1YL (E£fALLT) ----i S�XjI —b N1112d N9Jx-1 OFMrVLLL IOEf4ATj --O NtSh 1.12l12 O— _ —� 5Xfi —b lAt<IF2 UalF 10 O —� —�} MNERRUJNIIO PIPJGTM OP,gr16L � IEETAVLTI —y N16JT) NaJ29 O —� 5M !� I➢JIT _b N16J25 4iBJ2d o—_ UODER ___� MVt- __y N GTM MTKKILL ICEF D —b 1411p I I I I I I I uen-e o— I I I I I I -- I 91N aLL1ERHFAO N9nd 1�' RFREOVEY, 0------�-- PI GT (WAIT)) N9 YlJ OP,IOIUL O_ _ `R,1 p1 I OT4uWUrJ —r-1 —1 PP}GTM T OPTONAL WAMD p I%fs a PI:aA � IXK o IK$1J M z r I I LM�] E. ] LJ J 4 Eldl W poi a N1] / EU _ a-� A B o TO OE IIITALI W MSTMCR )want �3Fu I LCRY S NM r y2y1B Bw -J Ir-- LJ �I1„ - 9 Q .. TOEEPiSTAI]ED A I\L 4 i -i BY 0. STMER EIX =1 I I W9131 Q�V Equipment Submittal Page 24 of 25 SLC -Rock Road Jail Chiller Repl 2021 November 23, 2021 Field Installed Options - Part/Order Number Sommary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Centrifugal Water Chiller Item Tag(s)I Qty I Description I Model Number Al I CH-3 11 1 Centrifugal Chiller CTV I CVHE045 Field Installed Option Description Part/Ordering Number Thermal dispersion flow switch (I FM) - Field Installed Thermal dispersion flow switch (IFM) - Field Installed Equipment Submittal Page 25 of 25 1i) GEJEOW�ml%'.%-IITER-IIATIOIAL, IBC. SHERLOCK' INFRA -RED REFRIGERANT GAS SENSOR SPECIFICATIONS ENCLOSURE RATING NEMA 3R Aluminum, Black Powder Coat GENERAL SHERLOCK NON -DISPERSIVE IR REFRIGERANT GAS SENSOR was designed to monitor for the presence of refrigerant gases within an enclosed space. The sensor is mounted within the space to be monitored and connect- ed by cable to a SHERLOCK, Z(/rg4ac6 or EMS System. Each sensor is calibrated to a specific refrigerant gas. The IR comes in two different styles depending upon the monitoring environments: machine room and cold room for refrigerated applications in NEMA 3R Aluminum (Pictured). Water -tight ABS fiberglass housing for Wash down protection (NEMA 3R) and Stainless Steel enclo- sure also available for special applications. The IR Sensor is a reliable method of monitoring for refrigerant gas leaks in environments that have air quality problems. The IR sensor will eliminate many false alarms in environments that contain gasoline, diesel, and propane exhaust and fumes from solvents, paints, cleansers, and others (Please call Genesis Customer Support for more information). APPLICATIONS Typical applications include: Wineries HVAC Chiller Equipment Rooms Bakeries Refrigeration Mechanical Rooms Refrigerated Rooms Food Processing Plants DIMENSIONS 12.86 x 4.8 x 2.44 Inches (mm) (327 x 122 x 62) OPERATING ENVIRONMENT TEMPERATURE Machine Room Model 32°-120°F (0°- 50°C) Freezer Room Model-40°-120°F (-40°- 50°C) HUMIDITY 0 - 90% RH Non -Condensing POWER INPUT Sherlock / 2Ig44d 12VDC, 0.4 A Stand -Alone 12V DC - 32V DC Switching OUTPUTS (Standard) Current Driven Sherlock/Wizard 4 to 20 mA (Standalone Sensor) (Please contact Genesis for custom voltage outputs for the stand-alone sensor) RANGE (Parts Per Million, PPM) Sherlock/lIep"d 0 - 1500* (Control Dependent) Stand -Alone 0 - 1032* *Minimum effective range due to noise is 10 - 15ppm. SENSITIVITY fl ppm at 77°F (25°C), 45% RH RESOLUTION 1 ppm RESPONSE TIME Under 30 Seconds CALIBRATION Every 6 Months WARM-UP TIME Readings will stabilize in 3 hours (Up to 18 Hours in Cold Room Applications) LIFE EXPECTANCY Average of 5 to 7 years in normal environments AVAILABLE GAS SENSORS (Part Numbers) Machinery Room/Walk-In Cooler Application RI - 60-0057 R12 - 60-0104 R22 - 60-0053 R23 - 60-0232 R123 - 60-0137 R125 - 60-0466 R134a - 60-0054 R401a - 60-0465 R402a - 60-0231 R404a - 60-0052 R407a - 60-0223 R407c - 60-0214 R407f - 60-0514 R408a - 60-0184 R409a - 60-0066 R410a - 60-0165 R422d - 60-0546 R424a - 60-0469 R438a - 60-0246 R448a - 60-0544 R500 - 60-0067 R502 - 60-0059 R507 - 60-0061 R513a - 60-0542 R514a - 60-0550 R1233zd - 60-0548 R1234yf- 60-0551 Ammonia/NH3 - 60-0095 Extended Temperature/Freezer Application RI 1 - 60-0058 R22 - 60-0047 R402a - 60-0142 R404a - 60-0051 R407a - 60-0526 R407c - 60-0473 R407f - 60-0528 R408a - 60-0065 R438a - 60-0464 R448a - 60-0545 R500 - 60-0068 R502 - 60-0060 R507 - 60-0062 Ammonia/NH3 - 60-0096 Please contact Genesis if your sensor type is not listed. MULTIPLE 60 NUMBERS ON SHEET, NEMA 3R 09-12-19 DTMENSTONS O O C� 1 0 12.861 < L > 0 O O 4.8 �I 2.413 O WARNING!!!! The infrared sensor is not to be applied Into all refrigerated storage applications where other toxic �- _ gases are used in the same room. Some installations are not suitable for Infrared technology. Misapplication may result in damage to sensor. Contact the factory for a specific list of approved applications. 1316110110161 206 DIA. IIOLES O O O 1236 —J3JG Sensor Placement -- The Sherlock IR Sensor must be placed in locations where a refrigerant leak is likely to occur and where leaked refrigerant gas is likely to concentrate so as to pro- vide warning of a poten- tially hazardous condition. Mounting locations are dependent upon the appli- cation and the refrigerant gas to be monitored. For Halocarbon refriger- ants such as R11, R22, R123, R134a, R404a, etc... Place the sensor 18 to 24 inches off the floor. For Ammonia, place the sensor 18 to 24 inches from the ceiling. HVAC/Refrigeralion Machinery Room — Prior to placement of the IR Sensor, the room air currents need to be determined. The maxi- mum air flow rate past the sensor should not exceed 3 feet per second. Mounting - The sensor must be mounted with the wire termi- nal blocks oriented to the lower right and the sampling chamber in a vertical position. Failure to mount the sensor in this fash- ion may result in inaccurate readings and can allow moisture to enter the housing and destroy the sensor. SHERLOCK / WIZARD STAND ALONE (PLC, BAS) INFRARED SENSOR R R 4GND I Al V+ — V+ 4GND V+ G 3 V+ 1 pLC .. 3 V+ SNRA IN B G 20UT- I G z+2 8�60 2OUT- GND 1 OUT+ 7 OUT+ 1 SIG COMM- 1 —_ COMM- V+ COMM+ I COMM+ SNR B IN GND SENSOR POWERED BY 12V DC TO 32V DC POWER SUPPLY. SIGNAL IR SENSOR I IS 4-20MA. PLC INPUT SET TO 4-20MA INPUT. MAXIMUM I CURRENT LOOP RESISTANCE - 250 OWN. INFRARED SENSOR IN 1 I V+ AI 4 GND IN 1 1 PL ^ 3 V+ 2 G 2+1 6260 1 1 OUT+ 1 SIG HORN/ I COMM- STROBE 1 _ COMM+ STROBE SENSOR POWERED BY PLC PRODUCING 12V DC TO 32V DC, 400MA. 1 I SIGNAL IS 4-20MA. PLC INPUT SET To 4-20MA INPUT. MAXIMCM I CURRENT LOOP RESISTANCE - 250 OWN. GENESIS INTERNATIONAL, INC. 0 1040 FOX CHASE INDUSTRIAL DRIVE PHONE: (636) 282.0011 ARNOLD, MISSOURI 63010 FAX: (636) 282.2722 WEBSITE: EMAIL: ;tAt WWW.GENESIS-INTERNATIONAL.COM MAIL@GENESIS-INTERNATIONAL.COM DOC #44-0493-00