expect a difference
February 02, 2022
SHOP DRAWING REVIEW COMMENTS
Reference: Trane WPB SLC Rack Road Jail Chiller #3
Salas O'Brien Florida #2104404
Subject: SUBMITTAL ID: 01
Trane Equipment Submittal
Reviewed By: Joseph Detig, P.E.
Mahaley Vann
Orlando, Florida 32817
407.380.0400 1 www.salasobrien.com
SCANNED
Y
Engineer's review is for general conformance with the design concept and contract documents. Markings or comments
shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor
departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract
Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication
processes, for techniques of assembly, and for performance of work in a safe manner.
OVERALL DISPOSITION: NO EXCEPTIONS TAKEN
FILE COPY
ST. LUCIE COUNTY BUILDING DIVISION
REVIEWED FOR OMPLIANCE
REVIEWED BY
DATE
PLANS AND PERMIT MUSTBE KEPT ON JOB
OR NO INSPEnGN WILL BE MADE
END OF DOCUMENT
Prepared For:
St Lucie County
Submittal
Date: December 29, 2021
Job Name:
SLC - Rock Road Jail Chiller Repl 2021
Trane U.S. Inc. is pleased to provide the following submittal for your review and approval.
Product Summary
Qty Product
1 Centrifugal Water Chiller (CH-3)
Chris Cowling
Trane U.S. Inc.
6965 Vista Parkway North, Suite 11
West Palm Beach, FL 33411
Office Phone: (561) 683-1521
Please Note:
The attached information describes the equipment we propose
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid for a period of 6
months from the date of submittal generation. If six months or
more has elapsed between submittal generation and equipment
release, the product performance and submittal data will need to
be verified. It is the customer's responsibility to obtain such
verification.
Contractors & Engineer to review submittal for accuracy before order is placed.
ELECTRONIC SHOP DRAWING REVIEW
By: Salas O'Brien Florida, Inc.
NO EXCEPTIONS TAKEN
,Nrmy m< m.eao� nl� e.viMS am mMrWlm ee1en-1w
.r,emt„,marten,.1m10
wN.aee ia, a<um ma =w.r..a—V A ,tir .-M
�m...ab,.�mr,�a .Id ..nHn� .n w+.mk...e
sine ...hnekanng+GOApae<r.m¢ eee,a m.renKnnq,.
Ky: Kyle J. ea,uer, FM a:mvmu
© 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl - 11-23-21.docx
Table of Contents
ProductSummary ...........................................................................................................................................................1
Centrifugal Water Chiller (Item Al) ...............................................................................................................................3
TagData.......................................................................................................................................................................
3
ProductData.................................................................................................................................................................3
ProductReport ..............................................................................................................................................................4
MechanicalSpecifications............................................................................................................................................6
DimensionalDrawings................................................................................................................................................13
Weight, Clearance & Rigging.....................................................................................................................................19
Accessory...................................................................................................................................................................21
FieldWiring.................................................................................................................................................................23
Field Installed Options - Part/Order Number Summary ............................................................................................25
CentrifugalWater Chiller............................................................................................................................................25
© 2021 Trane Technologies All rights reserved Submittal - CVHE Chiller - SLC Rock Road Jail Chiller Repl - 11-23-21.docx
SLC - Rock Road Jail Chiller Repl 2021
Tag Data - Centrifugal Water Chiller (Qtv"l)
November 23, 2021
Item
Ta s
Qt
Description
I Model Number
Al
I CH-3
1 1
1 Centrifugal Chiller CTV
I CVHE045
Product Data - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
Standard ship cycle CVHE, CVHF & CVHG
Centrifugal liquid chiller with 3 stage compressor
Compressor size: 450 nominal tons
Adaptiview controls
Compressor motor voltage: 460 volt 3 phase
Compressor motor power: 234 kW
Motor frame size: 440E
Compressor impeller cutback: 230
Orifice size: 400 nominal tons
Evaporator:
Evaporator shell size: 050 short
Evaporator bundle size: 580 nominal tons
Evaporator tubes: 0.75 inch (19.1 mm) dia. internally enhanced copper
Evaporator tube wall:.025 inch (0.6 mm) thick
Evaporator fluid type: Water
Evaporator waterbox type: Non -marine
Evaporator waterbox construction: Standard
Evaporator water box passes: Two pass
Evaporator waterbox pressure: 150 psig (1034 kPa)
Evaporator waterbox connection: Victaulic
Evap waterbox arrangement: in RH end - out RH end
Thermal dispersion flow switch (IFM) - Field Installed (Fld)
Condenser:
Condenser shell size: 050 short
Condenser bundle size: 500 nominal tons
Condenser tube: 0.75 inch (19.1 mm) internally enhanced copper
Condenser tube wall:.028 inch (0.7 mm) thick (thicker tube option)
Condenser shell construction: Standard
Condenser fluid type: Water
Condenser waterbox type: non -marine
Condenser waterbox construction: Standard
Condenser water box passes: Two pass
Condenser waterbox pressure: 150 psig (1034 kPa)
Condenser waterbox connection: Victaulic
Condenser waterbox arrangement: in RH end - out RH end
Thermal dispersion flow switch (IFM) - Field Installed (Fid)
Misc/Electrical:
Agency listing: U.L. listed unit (United States requirement)
Factory performance test: Standard air run and vibration test
Selection tolerance: AHRI Standard tolerance
Brass logo with customer specified engraving
No unit insulation package — insulation in the field by others
AHRI Certified, Complies with ASHRAE 90.1 - 2016
Generic BAS / BACnet interface
Trane-supplied R514 Refrigerant, Shipped loose for field installation at start-up
Low Voltage Wye -Delta Starters
Starter type: Unit Mounted Wye -Delta
Starter maximum RLA: 346 Amps
Starter power connection: Circuit Breaker High -Interrupt
Starter power connection maximum RLA: 296 Amps
Starter option: Surge protector/lightning arrestor
Factory Start-up
10 year Parts, Labor & Refrigerant warranty
Qty 1, Refrigerant Sensor for existing Sherlock Refrigerant Monitor (Fld) — See end of submittal for data sheet
Equipment Submittal Page 3 of 25
SLC - Rock Road Jail Chiller Repl 2021
November 23, 2021
Product Report - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
r-T._... _. ..07
" Applidofion ty-o ;Standard cooling��'�����
Troeor Controls BACne� f''~��] _'—
Compmf�or�460__�
Impollar1230
t
Oy:f00._._�...........��.�_. S
rifice 4
Certified in accordance with the AHRI Water -Cooled Water -
Chilling and Heat Pump Water -Heating Packages
Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified
units may be found In the AHRI Directory at
www.ahridirectory.org.
Equipment Submittal Page 4 of 25
SLC - Rock Road Jail Chiller Repl 2021
November 23, 2021
Product Report - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
Corapliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4) due to the R-514A refrigerant
GWP being less than 2.
Note: Trans recognizes and respects the U.S. Green Building Council® mandate that a default 2 % Refrigerant Leakage Rate (Lr) be used by all
manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there Is no IndustZ standard. yrane has
exhaustively documented a leak rate of less than 0.5%for CenTmVac- chillers (models CVHE, CVHF, CVHG. CVHS, CVHM, DHF, CDHG, CVHH
and CDHH) and utilizes an average design refrigerant charge of less than 2 lb./ton.
The U.S. Green Building Council's LEER® green building program is the preeminentprogram for the design, construction, maintenance and operations
of high-performance green buildings. It provides Independent, third -party verification pal a building project meets the highest green building and
performance measures.
Trans Select Assist 55235
Version Number.
Data Generation Date: 10/4/2021
Equipment Submittal Page 5 of 25
SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021
Mechanical Specifications - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
Compressor -Motor
Direct drive multiple -stage compressor, multi -stage capacity control guide vanes. Shrouded aluminum alloy impellers
dynamically balanced. Motor -compressor assembly balanced to .15 in./sec (.0038m/sec) maximum vibration
measured on motor and bearing housings. Refrigerant cooled, hermetically sealed, two -pole, squirrel cage induction
motor. Two pressure lubricated bearings support the rotating assembly. A direct drive submerged oil pump motor, 3/4
hp (.560 kW) 115V/50/60/1 provides filtered and temperature controlled oil to compressor bearings.
Evaporator -Condenser
Shells are carbon steel plate. Evaporator includes rupture disk per BSR/ASHRAE 15 Safety Code. Carbon steel tube
sheets are drilled, reamed and grooved to accommodate tubes. Tubes are individually replaceable externally finned
seamless copper. Tubes are mechanically expanded into tube sheets. Eliminators are installed over entire length of
the evaporator tube bundle. A multiple orifice control system maintains proper refrigerant flow. Condenser baffle
prevents direct impingement of compressor discharge gas upon the tubes. Refrigerant side of the assembled unit is
tested at both pressure(30.00 psi leak test) and vacuum. Water side is hydrostatically tested at one and one-half times
design working pressure, but not less than 225.00 psi.
Trane reserves the right to implement chiller technology enhancements that will reduce the chiller's refrigerant charge,
with no impact on chiller performance. Changes may be reflected in the chiller's nameplate refrigerant charge and the
quantity of refrigerant charge shipped to the jobsite, depending upon the final date of equipment manufacture.
Water Boxes
Drains and vents - Water boxes typically have 3/4-inch NPTI vents and drain connections provided. Evaporators have
2 vents and 2 drains, condensers have 1 vent and 1 drain. If grooved connections are offered, the design is based on
Style 77.
Non -marine water boxes have water connections that extend out from the end.
Economizer
A flash economizer with no moving parts provides power saving capability.
Purge System
The EarthWise(TM) purge includes a 1/4 hp 115V/60/1, 100V/50/1 air cooled condensing unit, purge tank, drier
elements, and a 1/20 hp (.037 kW) 115V/60/1, 110V/50/1 pump -out compressor. The purge is designed with an
activated carbon filtration system that includes an autoregeneration feature which results in automatic high -efficiency
removal of noncondensibles from the chiller without manual carbon maintenance. The purge meets Green Seal GS-
31 with a leak rate less than 1.0% of the charge per year and also meets ASHRAE 147 with a leak rate of less than
one unit mass of refrigerant per unit of air.
AdaptiView Control Panel:
The Tracer(tm) AdaptiView is a microprocessor -based chiller control system that provides complete stand alone
system control and monitoring for the water cooled CenTraVac (TM). It is a factory mounted package including a full
complement of controls to safely and efficiently operate the CenTraVac chiller, including oil management, purge
operation, interface to the starter, and comprehensive motor protection including three phase solid state motor
overload. Inlet and outlet water (fluid) temperature sensors are located in the evaporator and condenser waterbox
connections as standard.
The display is a touch sensitive 12 1/8" diagonal color liquid crystal display (LCD) that uses color graphics and
animation to ensure ease of use. The touch sensitive interface allows the operator to view the chiller graphically and
receive a status indication via subsystem animations. The operator can navigate easily between the primary chiller
subsystems including: compressor, evaporator, condenser, and motor. For each subsystem, you can view status and
detailed operating parameters. In addition, alarms, reports, trending, and settings can all be accessed quickly from
the main screen. The display is mounted on a flexible "arm" that allows extensive height and viewing angle variations.
The panel supports an extensive list of languages including the default English. The data can be set to be viewed in
inch pounds IP or metric units SI. For remote starters - Class 1 control panel voltage (30-115 V) are clearly labeled in
the control panel. Class 2 input voltage (30V max) is also labeled in the control panel.
Equipment Submittal Page 6 of 25
SLC - Rock Road Jail Chiller Repl 2021
November 23, 2021
Operating Data including: 0
*operating hours
*number of starts
*chilled water setpoint
*evaporator and condenser water flow status
*evaporator entering and leaving water temperatures
*evaporator saturated refrigerant temperatures
*evaporator approach temperature
*evaporator refrigerant pressure
*condenser entering and leaving water temperatures
*condenser saturated refrigerant temperatures
*condenser approach temperature
*condenser refrigerant pressure
*oil differential pressure
*oil tank temperature
*purge mode
*purge average daily pump -out time
*% RLA per phase for motor
*RLA per phase
*volts per phase
*power factor
*kw
*kwh
*frequency
The AdaptiView also contains the following dedicated reports:
Evaporator, Condenser, Compressor, Motor, Purge, and ASHRAE. Each report is comprised of a detailed listing of
operational data relative to that chiller subsystem.
Control functions including:
*leaving chilled water temperature
*percent demand limit
*chiller water reset (based on return water temperature
*front panel control type
*setpoint source
*differential to start
*differential to stop
Status data including:
*waiting to start
*running
*run limit
*run inhibit (adaptive)
*auto
*free cooling (option)
*preparing to shutdown
*shutting down (post lube)
*stopped
Safeties including:
Automatic safety shutdown for:
*Low chilled water temperature,
*low evaporator refrigerant temperature
*high condenser refrigerant pressure
*evaporator and condenser flow status
*low evaporator/condenser differential refrigerant pressure
*low oil pressure
*oil pressure overdue
*high or low oil temperature
*high bearing oil temperature (requires enhanced protection option)
*high motor current
Equipment Submittal Page 7 of 25
SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021
*high motor temperature
*starter function faults
*critical temperature and pressure sensor faults
The devices are of a latching trip out type requiring manual reset. Non -latching safety trip outs for operating conditions
external to the chiller automatically permits unit to resume normal operation when condition is corrected.
Advanced motor protection monitors 3-phase current to provide latching trip out protection from adverse effects of
phase loss, phase unbalance, phase reversal, loss of phase reversal protection, and electrical distribution faults
(momentary power loss) by instantaneous trip out of motor.
Surge protection - Detects surge and limits chiller loading through inlet vane modulation. Head relief through lowering
cooling tower water temperature can be requested. If not corrected within 7 minutes, chiller is shut down.
Enhanced Adaptive Control(TM) - Built in intelligence to keep the chiller on line (safely making maximum tons) while
simultaneously preventing chiller damage/failure. During any chiller limiting mode of operation, the control panel
enunciates the condition via a relay output.
Trending:
The controller provides 10 standard graphs for trending multiple parameters, The operator can add an additional 6
custom graphs if desired. On anyone custom graph, the operator can choose to trend up to 10 unique parameters
from a more comprehensive list. Two Y axes are available for any graph to facilitate readability.
Diagnostics:
AdaptiView includes comprehensive diagnostic monitoring. All active diagnostics are available, and up to 20 historic
diagnostics are communicated to the operator via the 12 1/8" LCD display with graphic navigation system. Each
diagnostic is time and date stamped.
Service Tool:
A PC -based service tool called Tracer TU, connected to the chiller via USB port, is available for additional cost and
displays the last 100 diagnostics, indicating the time, date of occurrence, and system parameters at the time of the
diagnostic. The service tool provides advanced troubleshooting and access to sophisticated configuration settings not
needed during operation of the chiller.
Security:
The AdaptiView can be set to prevent unauthorized access to the chiller settings. The operator can choose to secure
the operating settings with a password. Data and reports can still be accessed once the settings are locked out.
The memory for the AdaptiView is non-volatile type, so if power is lost, operating settings are retained. A life time
battery is standard, which is used only to support the clock function for the chiller.
Chilled and Condenser water pump relays:
Chilled water and condenser water pump relays are provided and it is recommended that they be used for pump
control.
BACnet(MSTP) Direct Points List:
The following points are available directly from the chiller. Recognize that some of these points require chiller options
or configurations.
Inputs Including
Chiller Auto/Stop
Chiller Mode (e.g. cool)
External Base Loading Enable/Disable (requires Extended Operation option)
External Base Loading Setpoint (requires Extended Operation option)
Chilled Water Setpoint
Current Limit Setpoint
Heating Setpoint (requires Extended Operation option)
Wall Mounted Refrigerant Specific Monitor (requires Extended Operation option)
Clear Diagnostics
Outputs Including
Evaporator Pump relay
Equipment Submittal Page 8 of 25
SLC • Rock Road Jail Chiller Rapt 2021
November 23, 2021
Condenser Pump relay
Chilled Water Flow Status
Condenser Water Flow Status
Evaporator Water Flow Rate (requires Flow Compensation option)
Condenser Water Flow Rate (requires Flow Compensation option)
Chiller capacity (requires Flow Compensation option)
Leaving Chilled Water Temperature
Entering Chilled Water Temperature
Entering Condenser Water Temperature
Leaving Condenser Water Temperature
Second Condenser Entering Water Temperature (requires HR or Aux condenser bundle)
Second Condenser Leaving Water Temperature (requires HR or Aux condenser bundle)
Active Chilled/Hot Water Setpoint
Active Current Limit Setpoint
Active Base Loading Setpoint (requires Extended Operation option)
Head Relief Request relay
Compressor Running relay
Chiller On/Off
Limit Warning relay
Maximum Capacity relay
Alarms Description'!
Manual Reset Alarm relay
Auto Reset Alarm relay
Purge Alarm relay
Alarm Reset
Condenser Refrigerant Pressure
Condenser Refrigerant Temperature
Evaporator Refrigerant Pressure
Evaporator Refrigerant Temperature
Compressor Discharge Refrigerant Temperature (requires Enhanced Protection option)
Differential refrigerant pressure (not for head pressure control)
Operating Status (Alarm, Run Enabled, Local Control, Limited)
Chiller Modes (i.e. Off, Starting, Running, Shutting Down)
Base Loading Active (requires Extended Operation option)
Hot Gas Bypass Active (requires Hot Gas Bypass option)
Operating Mode (e.g. Cool)
Current Per Line
Voltage Per Phase
Unit Power Consumption (kW)
Motor winding temperature
Motor power factor (uncorrected)
Oil Temperature
Oil Pressure Differential
High Side Oil Pressure
Low Side Oil Pressure
Compressor Starts
Compressor Run Time
Inlet guide vane position
Inboard bearing oil temperature (requires Enhanced Protection option)
Outboard bearing oil temperature (requires Enhanced Protection option)
Purge Status2
Purge pumpout Average (24 hour)
Purge pump -out
Purge regeneration
Purge carbon tank temperature
Purge liquid temperature
Purge suction temperature
Purge time to next purge run
Purge pump -out chiller on-7 days
Purge pump -out chiller off-7 days
Purge pump -out life
Equipment Submittal Page 9 of 25
SLC - Rock Road Jail Chiller Rep[ 2021 November 23, 2021
Purge regeneration life
Refrigerant Monitor
AFD output frequency
AFD transistor temperature
Hardwire BAS Interface provides:
Chilled Water Setpoint input - Provides for setpoint adjustment of control point from multiple sources
Current Limit Setpoint input - provides for setpoint adjustment of control point from multiple sources
Percent RLA Output - provides % RLA output
Condenser Pressure Output - A hardwire output signal of condenser pressure, or differential pressure between the
evaporator and condenser is provided.
Operating Status:
The following hardwire binary outputs are available:
Compressor running relay
Alarm relay - manual reset
Alarm relay - auto reset
Limit warning relay
Purge alarm relay
Head relief request relay
Maximum capacity relay
Evaporator Proof of Flow - Thermal Dispersion
A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal
dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field
installation in the ship with components box. Follow the installation instructions in the chiller installation manual.
Reference specific IFM Installation manual (PART-SVN223'-EN) notes shipped with your rupture guard /contact local
Trane sales office
Condenser Proof of Flow - Thermal Dispersion
A factory provided, field installed thermal dispersion type proof of flow switch (IFM) is provided. The thermal
dispersion controller is mounted in the chiller control panel, the piping probe and wiring is shipped lose for field
installation in the ship with components box. Follow the installation instructions in the chiller installation manual.
Reference specific IFM Installation manual (PART-SVN223'-EN) notes shipped with your rupture guard /contact local
Trans sales office
Paint
All CenTraVac(TM) painted surfaces are coated with a primer and an air-dry beige primer -finisher prior to shipment.
Isolation
All units ship with neoprene isolator pads as standard, except when spring isolators are chosen. Enough pads are
provided to cover the area under the chiller supports.
Shipment
All units are of hermetic design, leak tested, charged to 5.00 psi and shipped as a single factory assembled package.
Full oil charge shipped in oil sump. Refrigerant shipped to jobsite from refrigerant manufacturer. The entire chiller is
shrink wrapped for protection.
Unit Mounted Starter
Wye Delta -Reduced Voltage, NEMA 1A (vented) enclosure with a gasket. Starter factory mounted and completely
prewired to compressor motor and control panel. Factory run testing assures proper circuitry and operational
reliability. The Wye Delta starter is a reduced voltage starter and therefore draws - 33% of locked rotor amps (LRA),
and the motor acceleration time is 5-12 seconds typically.
The starter is designed and tested in accordance with UL 1995
Features include:
115 volt control power transformer to power chiller unit controller, purge and oil system. Therefore, with line power, no
other power is needed for auxiliary equipment on the chiller.
Equipment Submittal Page 10 of 25
SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021
Environmental specification: Operation from sea level to 6000 ft (1829 m). Operating ambient temperature range 32.0
F to 104.0 F. Non -operating ambient temperature range -40.0 F to 158.0 F. Relative humidity, non -condensing 5% to
95% through the ambient temperature range. Voltage utilization ±10 %
Top of starter includes access area for a wiring entrance area. Bottom entry for line power is not available.
Terminal block connection is standard. Circuit breakers may be included as an option. See the following submittal
pages for disconnect ratings and lug information on these optional disconnects if offered.
Starter installer responsibilities
The following are considered functions normally required of the equipment installer for unit mounted starters.
Remove access area panel for line side wiring. The upper right quadrant of the starter provides recommended access
to starter/disconnect lugs. The starter can accommodate top line power entry only.
Provide and install field wiring to line side lugs of starter.
Required Installer Responsibilities
The following are considered functions normally required of the equipment installer./n
Install unit on a foundation with flat support surfaces level within 1/16" and of sufficient length to support concentrated
loading. (Spring isolators should be considered whenever chiller installation is planned for an upper story location.)
Place isolation pads or optional spring type isolators provided by the chiller manufacturer under the unit. When spring
isolators are chosen, no pads are provided.
Install unit per applicable Trane Installation Manual.
Complete all water and electrical connections.
Where specified, provide and install valves in water piping upstream and downstream of the evaporator and
condenser water boxes as means of isolating shells for maintenance and to balance and trim system.
Furnish and install a flow switch or equivalent device in both the chilled water and condenser water piping properly
interlocked to insure that unit can operate only when water flow is established.
Furnish and install taps for thermometers and pressure gauges in water piping adjacent to inlet and outlet connections
of both evaporator and condenser.
Furnish and install drain valves to each water box.
Install vent cocks on each water box.
Furnish and install strainers upstream of chiller evaporator and condenser bundles to protect tubes from potential
damage caused by debris in the circulating water. Note: Failure to install strainers in all water piping entering the
chiller could result in tube plugging conditions that could damage unit components. If the circulating pumps are
immediately upstream of the chiller bundles, then the strainer can be installed immediately ahead of the pumps. If the
circulating pumps are downstream of the chiller bundles, then the strainers should be installed immediately ahead of
the chiller bundles.
Furnish sufficient refrigerant 25.0 lb per machine and dry nitrogen 50.0 lb per machine for pressure testing under
manufacturer's supervision.
Start-up unit under supervision of a qualified Trane field engineer
Where specified, insulate evaporator and any other portions of machine required to prevent sweating under normal
operating conditions.
Water connection piping must not transfer forces to the chiller. Because of cumulative tolerances in manufacture and
field installation, prepiping of water connections closer than 36" is not recommended. Any problems associated with
prepiping of water connections closer than 36" to the chiller are the responsibility of the installing contractor.
Equipment Submittal Page 11 of 25
SLC - Rock Road Jail Chiller Repl 2021 November 23, 2021
Furnish and install vent lines for rupture disk and purge venting to atmosphere per ASHRAE 15 and unit installation
manual. If RuptureGuard-Relief Valve option is ordered, remove factory rupture disk and install RuptureGuard-Relief
Valve per the IOM manual. In some chiller configurations the RuptureGuard may not bolt directly to the chiller flange.
Locally sourced and approved piping may be required between the chiller and the RuptureGuard.
Field Disassembly
With chillers that may require field disassembly (for example due to clearance concerns during unit installation)
reference the Disassembly and Reassembly manual and your Trane Sales representative prior to the order being
placed. Caution: if certain components are removed in the field, for example the economizer, the necessary
components (gaskets, seals, etc.) are not provided as standard.
Leak -Tight Warranty
The CenTraVac chiller features a 5-year limited Leak -Tight Warranty which is valid for the lesser of 60 months from
initial start-up or 66 months from date of shipment. The limited Leak -Tight Warranty covers models CVHE/F/L, CVHS,
CVHM and CDHF chillers installed in the United States or Canada. The Company's obligations and liabilities under
this warranty are limited to furnishing replacement refrigerant; no other parts or labor are covered under this limited
warranty. No liability whatever shall attach to the Company until appropriate actions have been taken (acceptable to
Company) to eliminate the source of the leak, and then said liability shall be limited to furnishing the replacement
refrigerant.
If the chiller is placed under a comprehensive Trane service and maintenance agreement (Trane Select Agreement or
better) prior to the expiration of the standard Leak -Tight Warranty, the protection against refrigerant loss shall
continue under the Trane Select Agreement for as long as an active Trane Select Agreement remains in effect without
interruption.
If a 10-Year Parts, Labor and Refrigerant Warranty was purchased for the chiller and the chiller is placed under a
Trane Select Agreement (or better) prior to the expiration of the 10-Year Parts, Labor and Refrigerant Warranty, the
protection against refrigerant loss shall continue under the Trane Select Agreement for as long as an active Trane
Select Agreement remains in effect without interruption
Equipment Submittal Page 12 of 25
a
LEFT SIDE VIEW
CUSTOMER NOTES:
GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.
UNIT STRUCTURE AND SUBCOMPONENTS MAYBE REMOVED FOR CLARITY.
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE -P1/T".
COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.
WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
SHELLTYPE CONN DA CONNTYPE FLOWDIRECTION
EVAPORATOR 8" VICTAULIC IN REAR OUT FRONT
COOLING COND 8" VICTAULIC IN BOTTOM OUT TOP
to
A
a
CVHE Compressor sae: 450
Erap shall sae: 050S
Cord shell size. 050S
Without additional condenser
Ads
(ooci screw 16 nom mamee
(See accesserydrowin9 for details)
CUSTOMER NOTES:
GRMHIC6 ON SUBMITTAL ME SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.
UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE H-1/2".
COOLING COND CONNS ME STRAIGHT OUT THE END OF THE WATER BOX
WATER BOX DRAIN AND VENT LOCATIONS ME SHOWN ON THE WATER BOX END PLATES,
TOP VIEW
SHELLTYPE CONN DIA
EVAPORATOR
COOLING COND
after
CONNTYPE FLOWDIRECTION
VICTAULIC IN REM OUT FRONT
VICTAULIC IN BOTTOM OUT TOP
CD
w
0
3
a
CVHE Compressor slzei 450
Evap shell sae050S
Cond shell size. 050S
Without additional condenser
CUSTOMER NOTES:
GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.
UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY.
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE
COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.
WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES,
FRONT VIEW
SHELLTYPE CONN DA
EVAPORATOR
COOLING COND
CONNTYPE FLOWDIRECTION
VICTAULIO IN REAR OUT FRONT
VIOTAULIC IN BOTTOM OUT TOP
a
m
10
m
m
O
N
U
CVHE Compressor size; 450
Evap shell saw 0SOS
ConC shell size. 0505
Wi addi0onal condenser
LEFT SIDE VIEW
CUSTOMER NOTES:
GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.
UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLARITY
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE -FI/Z.
COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX,
WATER BOX ORAN PNO VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES.
SHELLTYPE CONN DA CONNTYPE FLOWDIRECTION
EVAPORATOR B" VICTAULIC IN REAR OUT FRONT
COOLING COND 8" VICTAULIC IN BOTTOM OUT TOP
Z
O
G
3
3
Q
m
N
W
N
O
N
3
if
CVHE Compressor sizo: 450
Evap shell sue'0505
Cone shell size, 050S
Without additicnal condenser
98
CUSTOMER NOTES:
GRAPHICS ON SUBMITTAL ARE SIMPLIFIED TO SHOW MAJOR ENVELOPE COMPONENTS.
UNIT STRUCTURE AND SUBCOMPONENTS MAY BE REMOVED FOR CLMITY,
UNLESS OTHERWISE SPECIFIED DIMENSIONAL TOLERANCE 41Q'.
COOLING COND CONNS ARE STRAIGHT OUT THE END OF THE WATER BOX.
WATER BOX DRAIN AND VENT LOCATIONS ARE SHOWN ON THE WATER BOX END PLATES..
RIGHT SIDE VIEW
SHELLTYPE CONN DA
EVAPORATOR S,
COOLING COND S"
CONNTYPE FLOWDIRECTION
VICTAULIO IN REAR OUT FRONT
VICTAULIC IN BOTTOM OUT TOP
to
n
3
m
hi
LEFT SIDE VIEW
SHIPPINGWEIGHT "
17,244.01E
OPERATING WEIGHT
19,217.01E
COMPRESSOR SIZE
450
EVAPORATOR SIZE
050S
EVAPORATORWATERPASS
2
EVAPORATORWATERBO%ARANGEMENT
RERE
CONDENSER SIZE
050S
CONDENSERWATERPASS
2
CONDENSERVA ERSO%ARRANGEMENT
I RERE
ALL PUBLISHED WEIGHTSACCURATE TO •/-10 %
"SHIPPING WEIGHT INCLUDES REFRIGERANT. IF ORDERED WITHOUT, CONSULT PRODUCT SUPPORT FOR DRY SHP WEIGHT.
TOP VIEW
SLC - Rock Road Jail Chiller Repl 2021
November 23, 2021
Weight, Clearance & Rigging - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
WEIGHTS AND CENTER OF GRAVITY
LEFT
LEFT
RIGHT REAR
RIGHT FRONT
SPRING ISOLATOR SELECTION
LOCATION
ISOLATORLOAD' VENDOR PM TRANEP/N ISOLATOR COLOR
LEFT FRONT
4,583.0 RE
LEFTREAR
3,570B It,
RIGHT FRONT
6.1150lb
RIGHT REAR
4.08.01b
LEFTMIDDLE
N!A
RIGHTMIDDLE
NIA
COMPONENT
WEIGHT'
COMPRESSOR WEIGHT
5,418.0I1,
MOTOR WEIGHT
1,832.01b
STARTER WEIGHT
MiTO Ib
SUCTION ELBOW WEIGHT
26001b
ECONOMIZER WEIGHT
635B1b
EVAPORATORWEIGHT
4,025.0m
EVAPORATOR WATERBOXES WEIGHT
83001b
CON DENSER WEIGHT
2d5d.016
CON OENSER WATERBOXES WEIGHT
399.0I1,
HEAT RECOVERY CONDENSER MEG HT
NIA
FAT RECOVERY CONDENSER WATERBOXES WEIGHT
N/A
FAUXILIARY CONDENSER WEIGHT
N/A
AUXILIARY CONDENSER WATERBOXES WEIGHT
N/A
M I SCELLANEO US WEIGHT
1,013.ON
WEIGHTS
SHIPPING OPERATING
17,244.0lb 19,217.00
UNIT CENTER OF GRAVITY
CG Z(DIMENSION FROM RIGHTTO LEFT)
56000 in
CG X(DIMENSION FROM FRONT TO REAR)
28A001n
CG Y(HEIGHT DIMENSION FROM FLOOR)
45.000 in
RIGHT FRONT ISOLATOR MOUNTING HOLE
BOTTOM OF THIS HOLE IS 0,0,0 POINT
FOR CENTER OF GRAVITY DIMENSIONS
Y
ZX�
NAMEPLATE PRODUCT DESCRIPTION:
MDIIX
CVHE
VOLT 480
PTON
300.00 bns
;TON
450
EVTM
TECU
COTM TECU
CPRW
234
CPIM
230
COBS
500
EVSZ
050S
EVBS
580
ORSZ
400
CDSZ
050S
'AlLPUBLISHEDWEIGHTSACCURATETO-/.10 %
Equipment Submittal Page 19 of 25
SLC - Rock Road Jail Chiller Rep[ 2021
November 23, 2021
Weight, Clearance & Rigging - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
1. HEAVY OBJECTSI
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS SHOWN. EACH OF
THE CABLES (CHAINS OR SLINGS) USED TO LIFT THE UNIT MUST BE
CAPABLE OF SUPPORTING TH E ENTIRE WEIGHT OF THE UNIT LIFTING
CABLES (CHAINS OR SLINGS) MAY NOT BE OF THE SAME LENGTH. ADJUST
AS NECESSARY FOR EVEN UNIT LIFT. OTHER LIFTING ARRANGEM ENTS
MAY CAUSE EQUIPMENT OR PROPERTY -ONLY DAMAGE. FAILURE TO
PROPERLY LIFT UNIT MAY RESULT IN DEATH OR SERIOUS INJURY
SEE DETAILS BELOW
2. IMPROPER UNIT LIFTI
TEST LIFT UNIT APPROXIMATELY 24 INCHESTO VERIFY PROPER CENTER
OF GRAVITY LIFT POINT. TO AVOID DROPPING OF UNIT, REPOSITION LIFTING
POINT IF UNIT IS NOT LEVEL. FAILURE TO PROPERLY LIFT UNIT COULD
RESULT IN DEATH OR SERIOUS INJURY OR POSSIBLE EQUIPMENT OR
PROPERTY -ONLY DAMAGE.
3.ATTACH SAFETY CHAIN OR CABLE AS SHOWN WTTHOUTTENSION, NOT AS
ALIFTING CHAIN OR CABLE, BUTTO PREVENTTHE UNIT FROM ROLLING.
C DO NOT FORKLIFTTHE UNITTO MOVE OR LIFT.
5. LIFTING HOLES PROVIDED ON CHILLER TOATTACH CABLES (CHAINSOR SLINGS).
6. 36' (900 MM) RECOMMENDED CLEARANCEA90VE HIGHEST POINT OF COMPRESSOR.
Q FOLLOWNEG SECTION 110 AND OTHER APPLICABLE LOCALCODES
FOR CLEARANCES IN FRONT OF ELECTRICAL ENCLOSURES.
8. SPECIFIC SHIPPING AND OPERATING WEIGHTS OF THE SUBM"ED
CHILLER ARE PROVIDED IF THE CENTRIFUGAL CHUER SELECTION
WAS ENTERED IN TOPSS. DETAILED LOAD POINT AND SPRING
ISOLATOR APPLICATION WEIGHTS ME AVAUABLE FROM'CENTRAVAC
ISOLATOR SELECTION REPORT' AVAILABLE FROM THE REPORT GENERATOR
OFTHETRANETOPSS CHILLER SELECTION PROGRAM. CONTACT
YOUR LOCALTRANE SALES ENGINEER IF THIS DATA IS REQUIRED.
5' TYP (127mm)
4 X.88(22mm) 2SIT TYP(67mm)
DIAHOLES FOR 13116" TYP(3dom)
ANCHORING UNIT
EVAPORATOR
2'TYP TUSESHEET
(51mm)
HOLE DETAIL TYP
r
-
SAFETY CHAINS
OR CABLES
16fi MINIMUM=4B77mm
(SEE NOTE 8 ABOVE)
XI MAMUMSHIPPWG 17,244G Ib
MAXIMUM OPERATING 1 19,21TO Ib
34 114-
DIMENSIONN MCLUDESTUBESHEETS
44112, 135,
320 12'
141"
Equipment Submittal Page 20 of 25
.SLC - Rock Road Jail Chiller Rep[ 2021
November 23, 2021
Accessory - Centrifugal Water Chiller
Item: Al Qty: 1 Tag(s): CH-3
ADAPTIVIEW CONTROL PANEL TOP VIEW
O O
O O
63'4
O
O
-------------
1 va'DIAHOLE
20.
11,p�
TYPICALHOME
/
DANDLE
POSITION
1
2X 1 5116- 1
NOTE: DISPLAY CAN MOVE TO AN
INFINITE NUMBER OF POSITIONS.
REF -BOTTOM FRONT
OF PANEL DOOR
I
✓'� LOKEST POSRION
AVAILABLE
Equipment Submittal Page 21 of 25
SLC - Rock Road Jail Chiller Rep[ 2021
November 23, 2021
Accessory -Centrifugal Water Chiller 4
Item: Al Qty: 1 Tag(s): CH-3
UNIT MOUNTED WYE-DELTA STARTER
tL
BREAKER
SHORT CIRCUIT CURRENT
LINE CONNECTION LUGS
I PANEL
WTERNALWFIE
SIZE
AICAMPS
RATINGS(RMSSYMETRICALAMPS)
ME -DELTA STARTERS
CONNECTION
LENGTH
4DP
65 000
65,000
(2) 2i0- 50 OR (1)21U500
GBIC
25
POWER FACTOR CORRECTION CAPACITORS, WHEN SELECTED. ARE NOT CBIC= CIRCUIT BREAKER HIGH INTERRUPT CAPACITY
INCLUDED IN THE UL SHORT CIRCUIT RATING OF THE STARTER.
THE NON -FUSED DISCONNECT OR CIRCUIT BREAKER IS DESIGNED FOR USE ASA SERVICE DISCONNECT ONLY
DOOR SWINGS TO THE LEFT FORAMAX OF 145 DEGREES & 38114"
ELECTRICAL ENTRANCE r' 4 14' TOP
TOP
VIEW
ALLOW MIN. FRONT WORKING SPACE CLEARANCE PER NEC ARTICLE 110
REQUIREMENTS FOR ELECTRICAL
INSTALLATIONS_
FRONT
ELEVATION
MAX DOOR SWING
145' & 36114"1972mm1
Equipment Submittal Page 22 of 25
' ' SLC - Rock Road Jail Chiller Repl 2021
November 23, 2021
Field Wiring - Centrifugal Water Chiller.
Item: Al Qty: 1 Tag(s): CH-3
CAUTION
USE CO W ER CON W CTORS Olan
ATTENTION
N'UTILISER DUE DES CBNDUCTEURS
EN CUIVREI
LES IMMES EE LWTC ME SUNS
PAS S01NES POUR SZ.VBIR OLUIRCS
i Rii SC CBNOLCIEIRS
LVII PIN'mLHDdWfL¢ VHIUI CDIM1ICTLYR
PRIECAUCOQN
IUTILICE UNICAMENTE CONDUCTORES
BE CDBRD
LNO ESISH
GSEA W PWA PCGEP'M WRLA BS TIME
DE CO.MaTOIES.
N M LO , IC WELE WAMD✓R
I. x E..
DEVICE PREFIX CODE
1 •RWNUNITCONTROLPMIELDEVICE
2 = REMOTE MOU14TEDDEVEE
1 cUNITMOUNTEDDEVICE
5 v CUSTOMER PROVIDED DEVICE
CUSTOMER SUPPLIED
LINE VOLTAGE
(SEE UNIT HAMEPLATE)
GNO Lt L2 0
I I I
I I I I
I I I I
I I I I
I I I
I I I I
b b b d
G Li L2 L3
201 OR tit DISCONNECT
OR 2X3 TERMINAL BLOCK
TRANE SUPPLIED
UNIT MOUNTED
LOW VOLTAGE
WYE-DELTA
STARTER PANEL
WIRE NO OR DEVICE
FIELD WIRING CIRCUIT SELECTION INFORMATION
SUPPLYAND MOTORLEAD3
1M1 COMPRESSOR MOTOR LEADS
SEE 11AlAEP1ATE: A11111AlUM1I CIRCUIT AMPACSS`/
1A'
4 A AT I ISVAC, 8 AWG MAX WIRE SIZE
2A'ANO GRUNEL
1(100VA AT 1i5VAC, BAWG MAX WIRE SIZE(SVITHOUT OPTIONAL CPTR)
3B AND IB
CIRCUIT PROTECTED AT 21A, IIWAD IN. 10 AWG MAX WIRE SIZE (WITH OPTIONAL CPTR)
QA'AND 1DA'
PUMP MOTOR, IN YE H P, 117 FIp 1E AWG MAX WIRE SIZE. OIRCU IT PROTECTED AT 15A.
110-120VAC IN
WO,
TWISTED, SHIELDED AMR, 30VDC, MAX LENGTH 1500 FT(AS72m)
BELDEN TYPE 8780 RECOMMENDED
MIT ', SST, 3B' AND 113'
CIRCUIT P ROTECTED AT MA, IIWAC I PH. IO AWG MAX WIRE SZE
5
553 TNRU 58
bVDC.,U A RSTIVE LOAD, 14AWG MAX WIRE SIZE
ALLREAWININGWDTERIANAIS
PESI
CONTATRAIG. 28BAIIJOUCTNE.In HP.D2-6VATSI-IMVAC 14AWGI.WWIRESZE
NOTES: 'TWPEDCONTROLCONDUCTGRS
1 GASHED LILIES INDICATE RELDWIMNG SY OTHERS WIRE NUMBERS BHOVN ARE RECOMMENDED BY TRMIE.
Z DO NOT ROUTE LOW VOLTAGE(XV) WITH CONTROL VOLTAGE(110-120V)AND 00 NOT POWER UNIT UNTIL CHECK-0UT
MIOSTART-UP PROCEDURESHAVE BEEN COMPLETED,
Equipment Submittal Page 23 of 25
' ' SLC -Rock Road Jail Chiller Repl 2021
November 23, 2021
Field Wiring - Centrifugal Water Chiller .
Item: Al Qty: 1 Tag(s): CH-3
©TG EY%FORATM4 MJ]
CClEE1EER 1. AM YJATER FLM
CFIECIICN WNIROLLEIBUBTntt£O
BY TR V E CVSTCuwSMPIIEO
W
BWIOMY R ANDCO(P.El5ER
ATERPFOCF cf CF Fltl w W GEVKE9
ARE49AIO55 U. S95
PRUARY VFTERPR"OFROW DEACE:
W ERXEIiSECRW RC W%)ER FA.
OF ROW LEIICE$R V`ET O`
FACTORY ME 54V EEMEEN U1-5 AID
t Y$$d AtDPIBTALL55NA4BXONiy
AlI W R W NE T BETYEEN t%K ANJ
IYS]J AFD P6TALL 55 M LS SXO W N
TRAIEIEW WIEIDS W P@YL SN1
EVAPCPANRANO2COID AB
51b`MJ TO ALLOWTXE 1454OOME00LLET0
CClRf9l PRMER SEOtIFJiRC.
CAUTION I
ATTE(sTMN
NLTWSER WE DES CONUCTEMS
w CVN [I
Mi[W�2K]1Y�NI�E SiEflAtt.Wfrti
� Tli oim,v[Ov LVECry[ �rmltl[�f
PRECAUa6N
IUTILICE MICN£RTE CMDXYOKS
DE CDBK1
C.SI W ID WCL PI, KISIOUP
MD /l CNPS
OJBTCYERTOOIRECT
EIXW 40
.O ER
GE ZSTUSPUV 4gNT
593
IX]ERILL AV105IOP r�.x
(Iffi10V-IUJfFR fiY$616EP. I
M4
wwLeJw srPP � � _ _
IAwOVE MIPERTrv]611gq I N)
x-1Dvoc `--
M%V RUCW PPE59CR WCPVI -
NEIRdLPA9)
2. vO
COIICffMRJIaEAP£FRILERV?P4IESSVFE
LVFEREIIMI�PTES W EOUIPUT __
CCTDEl64RHJOP�aSViE CMRIAL
D10VDCCR L2OM IXIFPINL
CIPII.FNTWR$EIPgtR
EXTER LR E
D
11C.S CWLLEYATERSE)PCIM
amaw
AA �n
— \
EVAPCMTORWATER
AV%
NLIPPIIEMOIX
`
�ouPoly
59A $11
CON£tEER OA
fWPPREPLOG
FAIN UNT CUNTROL PANEL
SM5 OR siANsou1. 1.1 NTE Llt.w EA.
7ER0,11NAL
MNN�TICINS
CWLLERALIPI.IPOIGTOH
(4TERrN,E1
CPxNri4
Up
— ET..-
FN
LIw FpC1OW CMPPAh
CCrrtR0.lEL
LT610L1EIi WdT/QE➢
�AD 9ICOR,dI/ACBB6 LA
—
Po\VER
ONO X rl
RR
,A„]
usn.e o—
----1 i
I `N1 I
IASJid C-
-F--O-o-O---� EYAPMTORWATER '741
PW PIENY OPTICIYL "
Ns]zo o_
I
___Y x2 I
—b N9J:1
+ASJxI O
1 O.YBEIEEIt WA]ER
I pLLIP TEIAY fEOURED -'"
NOR-9 O
--1
b NAJa3
lSM� ��
A= AIARtl PITM_'ALCR
oPrDINL (CEFAIED
uena o_
___- I
—b N9JaA
Bu
—b N15JPt
Na J2-1 O
—�
���CCYYY AIARYPPJGTOR
—b NiSI]-3
UPR-9 O—
OPIb1YL (E£fALLT)
----i
S�XjI
—b N1112d
N9Jx-1
OFMrVLLL IOEf4ATj
--O NtSh
1.12l12 O—
_
—�
5Xfi
—b lAt<IF2
UalF 10 O
—� —�} MNERRUJNIIO
PIPJGTM
OP,gr16L � IEETAVLTI
—y N16JT)
NaJ29 O
—� 5M
!� I➢JIT
_b N16J25
4iBJ2d o—_
UODER
___� MVt- __y N GTM
MTKKILL ICEF D
—b 1411p
I
I I
I I
I I
uen-e o—
I I
I I
I I
--
I 91N aLL1ERHFAO
N9nd
1�' RFREOVEY,
0------�--
PI GT (WAIT))
N9 YlJ
OP,IOIUL
O_
_
`R,1
p1
I
OT4uWUrJ
—r-1 —1 PP}GTM
T
OPTONAL WAMD
p I%fs
a PI:aA
� IXK
o IK$1J
M
z
r
I I
LM�]
E.
] LJ
J 4 Eldl
W
poi
a N1]
/ EU
_
a-�
A B o
TO OE IIITALI
W MSTMCR
)want
�3Fu
I LCRY
S
NM
r
y2y1B
Bw
-J Ir--
LJ
�I1„
-
9
Q ..
TOEEPiSTAI]ED
A I\L
4
i
-i
BY 0. STMER
EIX
=1 I
I W9131
Q�V
Equipment Submittal Page 24 of 25
SLC -Rock Road Jail Chiller Repl 2021
November 23, 2021
Field Installed Options - Part/Order Number Sommary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or
order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a
bill of material for the job.
Product Family - Centrifugal Water Chiller
Item
Tag(s)I
Qty
I Description
I Model Number
Al
I CH-3
11
1 Centrifugal Chiller CTV
I CVHE045
Field Installed Option Description
Part/Ordering Number
Thermal dispersion flow switch (I FM) - Field Installed
Thermal dispersion flow switch (IFM) - Field Installed
Equipment Submittal Page 25 of 25
1i) GEJEOW�ml%'.%-IITER-IIATIOIAL, IBC.
SHERLOCK'
INFRA -RED REFRIGERANT GAS SENSOR
SPECIFICATIONS
ENCLOSURE RATING NEMA 3R Aluminum,
Black Powder Coat
GENERAL
SHERLOCK NON -DISPERSIVE IR REFRIGERANT
GAS SENSOR was designed to monitor for the presence
of refrigerant gases within an enclosed space. The sensor
is mounted within the space to be monitored and connect-
ed by cable to a SHERLOCK, Z(/rg4ac6 or EMS System.
Each sensor is calibrated to a specific refrigerant gas.
The IR comes in two different styles depending upon the
monitoring environments: machine room and cold room
for refrigerated applications in NEMA 3R Aluminum
(Pictured). Water -tight ABS fiberglass housing for Wash
down protection (NEMA 3R) and Stainless Steel enclo-
sure also available for special applications.
The IR Sensor is a reliable method of monitoring for
refrigerant gas leaks in environments that have air quality
problems. The IR sensor will eliminate many false alarms
in environments that contain gasoline, diesel, and propane
exhaust and fumes from solvents, paints, cleansers, and
others (Please call Genesis Customer Support for more
information).
APPLICATIONS
Typical applications include:
Wineries HVAC Chiller Equipment Rooms
Bakeries Refrigeration Mechanical Rooms
Refrigerated Rooms Food Processing Plants
DIMENSIONS 12.86 x 4.8 x 2.44
Inches (mm) (327 x 122 x 62)
OPERATING ENVIRONMENT
TEMPERATURE
Machine Room Model 32°-120°F (0°- 50°C)
Freezer Room Model-40°-120°F (-40°- 50°C)
HUMIDITY 0 - 90% RH Non -Condensing
POWER INPUT
Sherlock / 2Ig44d 12VDC, 0.4 A
Stand -Alone 12V DC - 32V DC Switching
OUTPUTS (Standard) Current Driven Sherlock/Wizard
4 to 20 mA (Standalone Sensor)
(Please contact Genesis for custom voltage outputs for the
stand-alone sensor)
RANGE (Parts Per Million, PPM)
Sherlock/lIep"d 0 - 1500* (Control Dependent)
Stand -Alone 0 - 1032*
*Minimum effective range due to noise is 10 - 15ppm.
SENSITIVITY fl ppm at 77°F (25°C), 45% RH
RESOLUTION 1 ppm
RESPONSE TIME Under 30 Seconds
CALIBRATION Every 6 Months
WARM-UP TIME Readings will stabilize in 3 hours
(Up to 18 Hours in Cold Room
Applications)
LIFE EXPECTANCY Average of 5 to 7 years in
normal environments
AVAILABLE GAS SENSORS (Part Numbers)
Machinery Room/Walk-In Cooler Application
RI - 60-0057 R12 - 60-0104 R22 - 60-0053
R23 - 60-0232 R123 - 60-0137 R125 - 60-0466
R134a - 60-0054 R401a - 60-0465 R402a - 60-0231
R404a - 60-0052 R407a - 60-0223 R407c - 60-0214
R407f - 60-0514 R408a - 60-0184 R409a - 60-0066
R410a - 60-0165 R422d - 60-0546 R424a - 60-0469
R438a - 60-0246 R448a - 60-0544 R500 - 60-0067
R502 - 60-0059 R507 - 60-0061 R513a - 60-0542
R514a - 60-0550 R1233zd - 60-0548 R1234yf- 60-0551
Ammonia/NH3 - 60-0095
Extended Temperature/Freezer Application
RI 1 - 60-0058 R22 - 60-0047 R402a - 60-0142
R404a - 60-0051 R407a - 60-0526 R407c - 60-0473
R407f - 60-0528 R408a - 60-0065 R438a - 60-0464
R448a - 60-0545 R500 - 60-0068 R502 - 60-0060
R507 - 60-0062 Ammonia/NH3 - 60-0096
Please contact Genesis if your sensor type is not listed.
MULTIPLE 60 NUMBERS ON SHEET, NEMA 3R 09-12-19
DTMENSTONS
O O
C�
1
0
12.861
<
L
>
0
O O
4.8
�I
2.413
O
WARNING!!!! The infrared sensor is not to be applied
Into all refrigerated storage applications where other toxic
�- _ gases are used in the same room. Some installations are
not suitable for Infrared technology. Misapplication may
result in damage to sensor. Contact the factory for a
specific list of approved applications.
1316110110161
206 DIA.
IIOLES
O
O O
1236
—J3JG
Sensor Placement -- The
Sherlock IR Sensor must be
placed in locations where
a refrigerant leak is likely
to occur and where leaked
refrigerant gas is likely to
concentrate so as to pro-
vide warning of a poten-
tially hazardous condition.
Mounting locations are
dependent upon the appli-
cation and the refrigerant
gas to be monitored.
For Halocarbon refriger-
ants such as R11, R22,
R123, R134a, R404a, etc...
Place the sensor 18 to 24
inches off the floor. For
Ammonia, place the sensor
18 to 24 inches from the
ceiling.
HVAC/Refrigeralion
Machinery Room — Prior
to placement of the IR
Sensor, the room air currents need to be determined. The maxi-
mum air flow rate past the sensor should not exceed 3 feet per
second.
Mounting - The sensor must be mounted with the wire termi-
nal blocks oriented to the lower right and the sampling chamber
in a vertical position. Failure to mount the sensor in this fash-
ion may result in inaccurate readings and can allow moisture to
enter the housing and destroy the sensor.
SHERLOCK / WIZARD
STAND ALONE (PLC, BAS)
INFRARED SENSOR
R R
4GND
I
Al V+
— V+
4GND
V+
G
3 V+
1
pLC
..
3 V+
SNRA IN
B G
20UT-
I
G
z+2 8�60
2OUT-
GND
1 OUT+
7 OUT+
1
SIG
COMM-
1
—_
COMM-
V+
COMM+
I
COMM+
SNR B IN
GND
SENSOR POWERED BY 12V DC TO 32V DC POWER SUPPLY. SIGNAL
IR SENSOR
I
IS 4-20MA. PLC INPUT SET TO 4-20MA INPUT. MAXIMUM
I
CURRENT LOOP RESISTANCE - 250 OWN. INFRARED SENSOR
IN
1
I
V+
AI
4 GND
IN
1
1
PL
^
3 V+
2
G
2+1 6260
1
1 OUT+
1
SIG
HORN/
I
COMM-
STROBE
1
_
COMM+
STROBE
SENSOR POWERED BY PLC PRODUCING 12V DC TO 32V DC, 400MA.
1
I
SIGNAL IS 4-20MA. PLC INPUT SET To 4-20MA INPUT. MAXIMCM
I
CURRENT LOOP RESISTANCE - 250 OWN.
GENESIS INTERNATIONAL, INC.
0 1040 FOX CHASE INDUSTRIAL DRIVE PHONE: (636) 282.0011
ARNOLD, MISSOURI 63010 FAX: (636) 282.2722
WEBSITE: EMAIL:
;tAt WWW.GENESIS-INTERNATIONAL.COM MAIL@GENESIS-INTERNATIONAL.COM
DOC #44-0493-00