Product Evaluation Report
Of
JELD-WEN, inc.
Energy Saver/Contour Wood Edge Steel Door
for
Florida Product Approval
FL# FL13540
Report No. 1562
Florida Building Code 2007 & 2010
Per Rule 9N-3
Method: 1— A (Certificate)
Category: Exterior Doors
Sub — Category: Swinging Exterior Door Assemblies
Product: Energy Saver/Contour Wood Edge Steel Door
Material: Steel/Wood
Product Dimensions: 74"x 81.75"
74"x80.5"
64.5"x95.25"
64.5"x94.5"
ALEX SPYROU
2012.01. 12
14:53:50 -05'00'
Prepared For:
JELD-WEN, inc.
3737 Lakeport Blvd.
Klamath Falls, OR. 97601
Prepared by:
Alexis Spyrou, P.E.
Florida Professional Engineer # 68101
Date: 12/01/2011
Contents:
Evaluation Report Pages 1— 4
Installation Details Pages 5
Alexis Spyrou, P.E.
Florida No. 68101
� f
BUILDING DROPS FL#: FL18s40
A Perfect Solution in Every Drop Date: 12/01
/2011 Report No: 1562562
it
Certificate of Authorization: 29578
Manufacturer: JELD WEN, Inc.
Product Category: Exterior Doors
Product sub -Category: Swinging Exterior Door Assemblies
Compliance Method: State Product Approval Rule 9N-3.005 (i)(a)
Product Name: Energy Saver/Contour Opaque Wood Edge Steel Door
(impact Rated- Doors Only)
74" x 81.75"
74" x 80.5"
64.5" x 95.25"
64.5" x 94.5"
Scope: This is a Product Evaluation Report issued by Alexis Spyrou, P.E. (FL # 68101) for Jetd-Wen Inc. based
on Rule Chapter No. 9N-3.005, Method la of the State of Florida Product Approval, Department of
Community Affairs - Florida Building Commission.
Code.
Limits of Use:
Alexis Spyrou, P.E. does not have nor will acquire financial interest in the company manufacturing or
distributing the product or in arty other entity involved in the approval process of the product named
herein.
This product has been evaluated for use in locations adhering to the 2007 & 2010 Florida Building
See installation Instructions JW162009, signed and sealed by Alexis Spyrou, P.E. (FL # 68101) for
specific use parameters.
1. This product has been evaluated and is in compliance with the 2007 & 2010 Florida Building
Code, excluding the "High Velocity Hurricane Zone" (HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Section 1609.1.2 of the 2007 & 2010 Florida Building Code and does not require an impact
resistant covering on single and double door systems. impact resistant shutters are required
for sidelites and transom.
4. Site conditions that deviate from the details of drawing JW162009 require further
engineering analysis by a licensed engineer or registered architect.
5. See installation Instructions JW162009 for size and design pressure limitations.
Alexis Spyrou, P.E.
Florida No. 68101
Page 2 of 5
BUILDING DROPS FL#:FL13540
A Perfect Solution tEvery Drop
IQ Certificate of Authorization:
Date: 12/01/2011
on: 2957$ Report No: 1562
Quality Assurance: The manufacturer has demonstrated compliance of door products in Accordance
with the Florida Building Code and Rule 9N-3.005 (3) for manufacturing under a
quality assurance program audited by anapproved quality assurance entity through
National Accreditation & Management Institute, Inc. (FBC Organization #QUA1789)
Performance Standards: The product described herein has been tested per:
Referenced Data:
• ASTM E 283-04
• ASTM E330-02
• ASTM E 331-00
• ASTM E 1886-05
• ASTM E 1996-05b
1. Product Testing performed by Quality Testing Inc.
(FSC Organization # TST7638)
Report #: SJW2009-199, Report pate: 1/18/2010
SJW2009-200, Report Date; 1/18/2010
2. Quality Assurance
National Accreditation and Management Institute
(FBC Organization #: QUA 1789)
Alexis Spyrou, P.E.
Florida No. 68101
Page 3 of 5
It
BUILDING DROPS FL#: FL13540
/2011
A Perfect Solution in Every Drop Date: 12/01562
Certificate of Authori ation:29578 Report No: 2562
installation: 1. Approved anchor types and substrates areas follows:
Through Frame Installation:
A. For two by (2X) wood buck substrate, use #10 Wood Screw type installation anchors of
sufficient length to achieve a minimum embedment of 1.50" into the wood substrate.
B. For concrete or masonry substrate where one by (1X), non-structural, wood bucking is
employed, use 3/16" diameter nW Tapcon type concrete screw anchors of sufficient
length to achieve minimum embedment of 1.25' Into concrete or masonry.
C. For concrete or masonry substrate where wood bucking is NOT employed, use 3/16"
diameter ITW Tapcon type concrete screw anchors of sufficient length to achieve
minimum embedment of 1.25' into concrete or masonry.
Refer to Installation Instructions (JW162009) for anchor spacing and more details of the installation
requirements.
Design Pressure:
Design Pressure 1
Positive 55 PSF*
Negative 55 PSF
*Product has not been rated for water infiltration. If authority having jurisdiction requires that
product meets this requirement, product shall be used when installed at location protected by
overhang such that overhang (OH) ratio = OH length/01-1 height is 1.0.
AlexisSpyrou, P.E.
Florida No. 68101
Page 4 of 5
BUILDING DROPS
A Perfect Solution in Every Drop
Certificate of Authorization: 79578
Installation Method
JELD-WEN, inc.
Energy Saver/Contour Opaque Wood Edge
Inswing/Outswing '
25 Ga. Steel Impact Door System
s
rvP. 3•TYP.
1 I I IIIII I 1
{
b _ j
i O �
� F �
iQ S
m C �
-
T'
FL*:FL13540
Date: 12/01/2011
Report No: 1562
Alexis Spyrou, P.E.
Florida No. 68101
Page 5 of 5
74' MAX FRAME MOTH
(O/OXO)
3'TYP.
d
�ETYP.
fTYR
t T-
�
I I
I j
I i I
I j
-
I
i I
I I
I j
I j
I j
I j j
b
L T
� j
I I j i l `T
FL*:FL13540
Date: 12/01/2011
Report No: 1562
Alexis Spyrou, P.E.
Florida No. 68101
Page 5 of 5