HomeMy WebLinkAboutEngineeringCONSTRUCTION MATERIALS_
€LA� TECHNOLOGIES
CR C
t = V
i
July 23, 2013
IKO Industries, Ltd CJ
40 Hansen Road South
Brampton, ON L6W 31-14
Canada
Re: Shingle Installation Instructions for 2010 Florida Building Cone —
Sir(s),
PRI Construction Materials Technologies has completed a technical review and attached sealed shingle
instructions in compliance the 2010 Florida Building Code.
This review was completed based on the receipt of following evidence from IKO Industries, Ltd:
1) IKO Shingle Application Instructions — 3 -Tab Shingles
(EN-3Tab_Appins_8AGXEFS-2012-11 reformatted 2013-02-rev07/13-Florida)
2) IKO Laminated Shingles Application Instructions
(EN -Laminated Appins_8TTEFS-2012-04_reformatted 2013-02-rev07/13-Florida)
3) ASTM D3161 Test Report (FM Approvals Project No. 3040947)
4) ASTM D7158 Test Report (PRI Project No. IKO-091-02-01)
The attached instructions should be used in conjunction with the published manufacturer's application
instructions and applicable code. In the event the instructions conflict, these instructions shall govern.
Regards,
-Duc Nguyen
Attachments: A) IKO Shingle Application Instructions - 3 -Tab
B) IKO Laminated Shingles Application Instructions
-)A' �/1L
17vC -r r,T(,rvyresj
No $5034
STATE OF
PRIConshcUm M&Aals Teclmologles,LLC. 64128adguDAx Tmnpa,FL33610 Tel:813.6215T77 Fac813.621-5840 e- mal:mmerialslesting®pricmLcom WebSle:hrpJAw .pdcmtwm
IKO
Installation Instructions for
3 -Tab and Laminated Shingles
Page 2 of 3
IKO Shingle Application Instructions — 3 -Tab Shingles
(ASTM D3161, Class F — IKO Marathon 25 AR and CRC Superglass 25 AR)
(ASTM D3161, Class F — IKO Marathon Ultra AR and CRC Superglass Ultra AR)
(ASTM D7158, CLASS H - IKO Marathon 20 and CRC Superglass 20)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKOIS PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
ROOF DECK: Solidly sheathed and fastened deck conforming to 2010 FBC
UNDERLAYMENT: Applied in accordance with building code requirements. For areas where the roof slope is
less than 4" per foot down to 2" per foot, use 2 layers of underlayment conforming to building code
requirements, the first sheet overlapping the save protection by 19", followed by full 36" widths overlapping
each preceding course by 19" or other Approved underlayments in accordance with the qualified application
instructions. For areas where the roof slope is 4" per foot or greater, cover the deck with one ply of
underlayment laid parallel to the eaves, with 2" horizontal laps and 4" end laps. Apply metal drip edges on top
of any underlay along rake edges and directly to the deck along eaves in accordance with building code
requirements.
NAILING: Use galvanized (zinc coated) roofing nails, 11 or 12 gauge, with at least 3/8" diameter heads, long
enough to penetrate through plywood or 3/4" into boards. Use 4 nails per shingle placed 6-1/8" above the butt
edge, approx. 1" and 13" from each end and 1/2" above each cutout. Drive nails straight so that nail head is
flush with, but not cutting into shingle surface.
NAILING ON STEEP SLOPES: For steep slopes of 21" per foot (600) or more, use 6 nails per shingle placed
as shown below. Ensure that no nail is within 2" of a joint/cutout of the underlying shingle. Seal down each
shingle at time of application with three 1" diameter (approx. size and thickness of a quarter) spots of asphalt
plastic cement placed under the shingle 2" above the bottom edge and equally spaced along the shingle.
Apply plastic cement in moderation since excessive amounts may cause blistering. CAUTION: Shingles
should seal to the underlying course when the factory applied asphalt sealant is sufficiently warmed by the
heat of direct sunlight.
STEEPSLOPES
•—
1
SEA UN SIdP6-14T 10
� � • • —� i • � ��
I— 6-1m-
NAILS NAILS
DO NOT NAIL INTO ORABOVE THE SEALING STRIP
ID vtr T, M-r�v `(5i1
'p.c. No: G503.4
)daft : x%83/
PRI ConsWcton Matedals Tedmologig, LLC. 641211adgerDdoa TanpAFL33610 Tel:813.621-5777 Fac813-621-5840 WebSde:htlpJAM pncmtcam
IKO
Installation Instructions for
3 -Tab and Laminated Shingles
Page 3 of 3
IKO Laminated Shingles Application Instructions
(ASTM D3161, Class F — IKO Cambridge AR and CRC Biltmore AR)
(ASTM D3161, Class F — IKO Grandeur)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKO'S PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
ROOF DECK: Solidly sheathed and fastened deck conforming to 2010 FBC.
UNDERLAYMENT: Applied in accordance with building code requirements. For areas where the roof slope is
less than 4" per foot down to 2" per foot, use 2 layers of underlayment conforming to building code
requirements, the first sheet overlapping the eave protection by 19", followed by full 36" widths overlapping
each preceding course by 19" or other Approved underlayments in accordance with the qualified application
instructions. For areas where the roof slope is 4" per foot or greater, cover the deck with one ply of
undedayment laid parallel to the eaves, with 2" horizontal laps and 4" end laps. Apply metal drip edges on top
of any underlay along rake edges and directly to the deck along eaves in accordance with building code
requirements.
NAILING: Use galvanized (zinc coated) roofing nails, 11 or 12 gauge, with at least 3/8" diameter heads, long
enough to penetrate through plywood or 3/4" into boards. Use 4 nails per shingle placed in the nail line 7-3/8"
below the top edge, approx. 1" and 13" in from each end. Drive nails straight so that nail head is flush with,
but not cutting into shingle surface.
NAILING ON STEEP SLOPES: For steep slopes of 21" perfoot (600) or more, use 6 nails per shingle placed
as shown below. Ensure that no nail is within 2" of a joint/cutout of the underlying shingle. Seal down each
shingle at time of application with three 1"diameter (approx. size and thickness of a quarter) spots of asphalt
plastic cement placed under the shingle 2" above the bottom edge and equally spaced along the shingle.
Apply plastic cement in moderation since excessive amounts may cause blistering. CAUTION: Shingles
should seal to the underlying course when the factory applied asphalt sealant is sufficiently warmed by the
heat of direct sunlight.
NAILING -STEEP SLOPES APPLICATION
Use six nails asshown.
7 3/B•
t r NAIL LII
NAILS � CEMENT
PROPER APPLICATION REQUIRES THAT THE NAILS PENETRATE BOTH THE OVERLAY AND UNDERLAY PORTIONS OFTHE SHINGLE
Qv ••y\v...r5 •'h'i
65034•••:2'%
*' Ar '* °
Dvc i-,
9-r�vYl5N
STATE OF .•��
'P,'E , N 0
GJ�?lf
.'�,.
PPIConsvudm MatedalsTechnal lm,LLC.6412BadguOrivs Tampa.F03610 Td:813b215M Fmc813-821-5840 e-mml:Mted S%3b g@PdCmtC0M Websiw.lopjAx ..P&MLMm
TURQUOISE Engineering, LLC
Structural Engineering, Design & Testing, CA #28948, NOA #13-0222.02
6915 Washington Rd, W Palm Beach, FL 33405 / Ph. (561) 804-9908 / Fax (561) 8049907 / e-mail: turginc@aol.com
February 06, 2015
TO: Ft Pierce County / Building Department
FROM: Riza N. ALTAN, P.E.
SUBJECT: Flat Roof Uplift Pressures & Base Sheet Enhanced Fastening
ADDRESS: McBRIDE Residence / 7007 Plumosa Ln., Ft. Pierce, FL 34951
CONTRACTOR: Code Red Roofers
Dear Sir;
The re -roofing specifications of flat roof area of the subject residential building are
reviewed by myself. The purpose of this letter is to determine the wind uplift pressures
and enhanced spacing of mechanical fasteners.
The one-story building is located in Exposure C area. The flat roof has 5/8" CDX
plywood with positive drainage. The roof mean height is 15 ft.
As per 2010 Florida Bldg. Code, ASCE 7-10, for Risk Category II, 170 MPH ultimate wind
velocity in Exposure C area, using Wind Load Factor of 0.6 for ASD; the wind pressures
are determined as follows:
Field: P1= -44 psf /Perimeter (4' wide): P2 = - 74 psf / Corner (4'x4'): P3 = -111 psf
The proposed CertainTeed Modified Bitumen Roof System over Wood Decks
(NOA #14-0224.03) consists of mechanically attached 75 -lbs GlasBase base sheet followed
by torched down Flinti-astic GTA modified bitumen cap sheet.
The system max. design pressure of -52.5 psf [Deck 1I, Syst.E(1), page 12/16, Limitation #7]
is specified by tin -tagging the base sheet with 11 ga., 1'/4" long ring-shanked roofing
nails, spaced at 8"o.c. along the laps and 8"o.c., three rows staggered in mid -sheet.
It is required that, as per RAS 117 in order to meet the actual roof pressures, the base
sheet is tin -tagged to the existing 5/8" plywood deck in the following enhanced pattern:
Zone 1: Field (Intermediate areas): @ 8" o.c., staggered three rows in mid -sheet,
Zone 2: Perimeter (4' from edges): @ 4" o.c., staggered three rows in mid -sheet,
Zone 3: Corner (4' from ea. side): @4" o.c., staggered foul rows in mid -sheet.
Laps: Field areas @ 8" o.c., Perimeter @ 4" o.c., Corners @ 4"o.c.
Therefore, thin letter is to certify that installation of CertainTeed Modified Bitumen Roof
System (NOA #14-0224.03) torched -down re -roofing system conforms to requirements of
2010 Florida. Building Code which specifies 170 MPH ultimate wind speed for Risk
Category II in Exposure C area.
If you have any questions regarding this matter or I may be oV01WIA- Wstance, please
do not hesitate to call me. ,�°��1 �;,AQ0?:r
Sincerely _
No. 38521 a
Riza N. ALTAN, Pa.815211 v I ttVV i �, e sT�' cE , n
Consulting Engineer o�°=�(
IVAL
9i,i?£nfilo