HomeMy WebLinkAboutGENERAC PAPERWORKProtector® QS
Series
INCLUDES:
• Two-Une LCD Multilingual Digital
Evolution'" Controller (English/Spanish/
French/Portuguese) with external viewing
window for easy indication of generator
status and breaker position.
• True Power'" Electrical Technology
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• -*1%Voltage Regulation
• Natural Gas or LP Operation
GENERAC®
SCANNED
PROTECTOR@ QS SERIES
BY Standby Generators
StludeCOunty Liquid -Cooled Gaseous Engine
Standby Power Rating
Model RG022 (Aluminum - Bisque) - 22 kW 60 Hz
Model RG027 (Aluminum - Bisque) - 27 kW 60 Hz
Model RG032 (Aluminum - Bisque) - 32 kW 60 Hz
Model RG038 (Aluminum - Bisque) - 38 kW 60 Hz
Model RG048 (Aluminum - Bisque) - 48 kW 60 Hz
• 5 Year Limited Warranty
• UL 2200 Listed ce QUIFF
• Capability to be installed within 18"
(457) mm of a building* Meets EPA Emission Regulations
'Only if located away from doors, windows, and fresh air 22 & 27 kW are CAIMA emissions compliant
intakes, and unless otherwise directed by local codes. 32 & 38 kW not for sale in CA / MA
FEATURES
O INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC'S success in "IMPROVING POWER BY DESIGN." But it
doesn't stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
O SOLIDSTATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque -matching the surge loads to the engine. Digital
voltage regulation at ±1%.
O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
O TEST CRITERIA: 0 GENERAC TRANSFER SWITCHES. Long life and reliability are
• PROTOTYPE TESTED v NEMA MG1-22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
• SYSTEM TORSIONAL TESTED v MOTOR STARTING ABILITY confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
22.27.32.38.48kW
GENERATOR
Type
Synchronous
Rotor Insulation Class
H (22 &27 kW) or
F (32,38 & 48 R
Stator Insulation Class
H
Telephone Interference Factor (TIF)
<50
Alternator Output leads 1-Phase
4 wire
Alternator Output leads 3-Phase
6 wire
Bearings
Sealed Ball
Coupling
Flexible Disc
Excitation System
Direct
VOLTAGE REGULATION
Type r
Electronic
Sensing
Single Phase
Regulation
1%
GOVERNOR SPECIFICATIONS
Type
Electronic
Frequency Regulation
Isochronous
Steady State Regulation
. 0.25%
ELECTRICAL SYSTEM
Battery Charge Alternator
12 Volt 30 Amp
Static Battery Charger
2.5 Amp
Recommended Battery (battery not included)
Group 26 (22, 27, 32 & 38 kW)
or Group 24F (48 M, 525CCA
System Voltage
12 Volts
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Class H insulation is NEMA rated
Class F insulation is NEMA rated
All models fully prototyped tested
ENCLOSURE FEATURES
Aluminum weather
Ensures protection against mother nature.
Electrostatically applied textured epoxy paint for added
protective enclosure
durability.
Enclosed critical grade
Quiet, critical grade muffler is mounted inside the unit
muffler
to prevent injuries.
Small, compact, attractive
Makes for an easy, eye appealing installation.
SAE
Sound attenuated enclosure ensures quiet operation.
(All ratings in accordance with BS5514, IS03046, IS08528, SAE J1349 and DIN6271)
GENERAC°
IIIIIIIIIIN
dicatip & engineering data
ENGINE SPECIFICATIONS: 22, 27, 32 & 38 kW
Make
Generac
Model
In -line
Cylinders
4
Displacement (Liters)
2.4
Bore (iNmm)
3.41/86.5
Stroke (iNmm)
3.94/100
Compression Ratio
9.5:1
Intake Air System
Nahualy Aspirated (22 & 27 kW) or
Turboclerged/Aftercooled
(32 & 38 kW)
Lifter Type
Hydraulic
ENGINE SPECIFICATIONS: 48 kW
Make
Genemc
Model
V-Type
Cylinders
8
Displacement (Liters)
5.4
Bare (iNmm)
3.55/90.2
Stroke (iNmm)
4.17/105.9
Compression Ratio
9:1
Intake Air System
Itturally Aspirated
Lifter Type
Hydraulic
ENGINE LUBRICATION SYSTEM
Oil Pump Type
Gear
Oil Filter Type
Full flow spin -on cartridge
4/3.8 (22, 27, 32 & 38 kW) or
Crankcase Capacity (qVl)
6/5.7 (48 kW)
ENGINE COOLING SYSTEM
Type
Closed
Water Pump
Belt driven
1980 - 22 & 27 kW
Fan Speed (rpm)
1500 - 32 & 38 kW
1954 - 48 kW
18.1/459.7 (22 & 27 kW) or
Fan Diameter (iNmm)
22/558.8 (32, 38 & 48 kW)
Pusher (22 & 27 kW) or
Fan Mode
Puller (32. 38 & 48 kW)
FUEL SYSTEM
Fuel Type
Natural gas, propane vapor
Carburetor
Down Draft
Secondary Fuel Regulator
Standard
Fuel Shut Off Solenoid
Standard
Operating Fuel Pressure
5-14° water colum/9-26 mm HG
LP Fuel Pressure
11 -141 Water Column
NG Fuel Pressure
5 -14° Water Column
I- \
Is
22.27.32.38.48kW
GENERATOR OUTPUT VOLTAGEAW - 60 Hz
GENERAC°
operating data
kW LPG Amp LPG kW Nat Gas Amp Nat. Gas CB Size (Both)
120/24O V, 10, 1-.0 pf
22
92
22
92
100 - -
RG022
120/208 V, 30, 0.8 of
22
76
22
76
80
120/240 V, 30, 0.8 pf
22
66
22
66
80
1201240 V, 10, 1.0 pf
27
113
25
104
125
RG027
120/208 V. 30, 0.8 of
27
94
25
87
100
120/240 V, 30, 0.8 of
27
81
25
75
90
120/240 V. 10, 1.0 of
32
133
32
133
150
120/208 V, 30, 0.8 pf
32
ill
32
111
125
RGO32
120/240 V, 30. 0.8 pf
32
96
32
96
100
277/480 V, 30, 0.8 pf
32
48
32
48
60
120/240 V, 10, 1.0 pf
38
158
38
158
175
120/208 V, 30, 0.8 pf
38
132
38
132
150
RG038
120/240 V. 30, 0.8 of
38
114
38
114
125
277/480 V, 30. 0.8 pf
38
57
38
57
60
120/240 V, 10. 1.0 pf
48
200
48
200
200
120/208 V, 30, 0.8 pf
48
167
48
167
175
RG048
120/240 V, 30, 0.8 pf
48
1 144
48
144
150
277/480 V, 30, 0.8 pf
46
1 72
48
72
80
SURGE CAPACITY IN AMPS ENGINE FUEL CONSUMPTION
Voltage Dip Q <.4 pf Natural Gas Propane
15% 30% (ft3/hr) (m3/hr) (gaVhr) (Vhr) W/hr)
120/240 V, 10
55
135
RG022
120/208 V, 30
40
92
120/240 V, 30
35
80
120/240 V, 10
62
170
RG027
1201208 V, 30
70
120
1201240 V, 30
61
103
120/240 V. 10
75
180
RG032
1201208 V. 30
87
210
120/240 V, 30
75
182
277/480 V, 30
36
87
120/240 V. 10
75
180
120/208 V. 30
87
210
RGO38
120/240 V, 30
75
182
277/480 V, 30
36
87
120/240 V, 10
85
195
120/208 V, 30
90
218
RG048
1201240 V, 30
78
189
277/480 V, 30
36
87
Note: Fuel pipe must be sized for full load.
For Btu content, multiply W/hr x 2520 (IP) or ft3/hr x 1000 (NG)
For megajoule content, multiply m3/hr x 93.15 (LP) or m3/hrx 37.26 ING)
Refer to "Emissions Data Sheets' for maximum fuel flow for EPA and
SCAOMD permitting purposes.
Exercise cycle
42
1.2
0.44
1.7
16
25% of rated load
100
2.8
1.1
4.2
40
RGO22
50% of rated load
190
5.4
2.1
7.8
75
75% of rated load
255
7.2
2.8
10.5
101
100% of rated load
316
9
3.4
13
125
Exercise cycle
42
1.2
0.44
1.7
16
25% of rated load
108
3.1
1.2
4.5
43
RGO27
50% of rated load
197
5.6
2.1
8.1
78
75% of rated load
287
8.2
3.1
11.8
114
100% of rated load
359
10.2
3.9
14.8
143
Exercise cycle
79
2.2
0.8
3.2
30
25% of rated load
144
4.1
1.7
6.3
60
RG032
50% of rated load
226
6.4
2.7
10.3
97
75% of rated load
298
6.4
3.7
13.9
132
100% of rated load
375
1 10.6
4.6
17.5
166
Exercise cycle
83
2.3
0.9
3.2
31
25% of rated load
162
4.6
1.7
6.6
62
RG038 -
50% of rated load
255
7.2
2.9
10.8
103
75% of rated load
345
9.8
4
15
142
100% of rated load
437
12.4
5.2
19
185
Exercise cycle
95
2.7
1
3.9
38
25% of rated load
204
5.8
2.16
8.5
82
RG048
50% of rated load
392
11.1
4.14
15.7
1 151
75% of rated load
547
15.5
5.8
22.8
220
100% of rated load
756
21.5
7.96
31.3
302
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
GENERAC'
22.27.32.38.48kW
operating data
ENGINE COOLING
22 kW 27 kW 32 & 38 kW 48 kW
Air flow (inlet air including alternator and combustion air in cfrrVcmm)
2400/68
1 2400/68
1 2200/62.3
4350/123.2
System coolant capacity(gal/lilers)
2.5/9.5
2.5/9.5
1 2.5/9.5
3/11.4
Heat rejection to coolant (BTU per hr/MJ per Inn)
99,000/104.5
105.000/110.8
1 145,000/153
186,000/196.2
Maximum operation air temperature on radiator (°C/°F)
60/150
Maximum ambient temperature (°C/'F)
50/140
COMBUSTION REQUIREMENTS
Flow at rated power(cfm/cmm) 68/1.9 1 68/1.9 106/3 163/4.6
SOUND EMISSIONS
Sound output in dB(A) at 23 ff (7 m) with generator in exercise mode'
61
1 61
1 58
1 63
Sound output in dB(A) at 23 it (7 m) with generator operating at normal load'
70
1 70
1 64
1 68
'Sound levels are Wlren from the front of the generator. Sound levels baleen from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfrrVcmm)
1 165/4.7
1 180/5.1
1 300/8.5
1 414/11.7
Exhaust temperature at muffler outlet(°C/°F)
1 482/900
1 538/1000
1 579/1075
1 552/1025
ENGINE PARAMETERS
Rated Synchronous rpm 1800
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration....................
Altitude Deration (22, 27 & 48 kW)
Altitude Deletion (32 & 38 I(W) .....
CONTROLLER FEATURES
...3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F
..1 % for every 100 m above 183 m or 3% for every 1000 it above 600 it
1 % for every 100 m above 915 m or 3% for every 1000 it above 30001t
Two -Line Plain Text LCD Display....................................................................................................................................Simple
user interface for ease of operation.
Mode Switch: Auto..............................................................................................................................................Automatic
Star) on Utility failure. 7 day exerciser
Off...........................................................................................................................Stops
unit. Power is removed. Control and charger still operate.
Manual.........................................................................................
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds.................................................................................................................................................10
sec standard
Engine Start Sequence.....................................................................................................................
Cyclic cranking:16 sec on, 7 rest (90 sec maximum duration)
EngineWarm-up.....................................................................................................................................................................................................................5
sec
EngineCool-Down..................................................................................................................................................................................................................1
min
Starter Lock-out................................................................................................................................Starter
cannot re-engage until 5 sec after engine has stopped.
SmartBattery Charger........................................................................................................................................................................................................
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection................................................................................................................................
Standard
AutomaticLow Oil Pressure Shutdown...............................................................................................................................................................................
Standard
OverspeedShutdown..............................................................................................................................................................................................Standard,
72 Hz
HighTemperature Shutdown...............................................................................................................................................................................................Standard
OvercrankProtection..........................................................................................................................................................................................................Standard
SafelyFused......................................................................................................................................................................................................................Standard
Failureto Transfer Protection..............................................................................................................................................................................................
Standard
LowBattery Protection........................................................................................................................................................................................................
Standard
50 Event RunLog...............................................................................................................................................................................................................
Standard
FutureSet Capable Exerciser..............................................................................................................................................................................................
Standard
IncorrectWiring Protection.................................................................................................................................................................................................Standard
InternalFault Protection.....................................................................................................................................................................................................Standard
CommonExternal Fault Capability ......................................................................................................................................................................................Standard
GovernorFailure Protection................................................................................................................................................................................................
Standard
RADIATORIEXHAUST
DISCHARGEAIR
(BOTHSIDES)
AIR INTAKE
(BOTIH SSIIDES)
BATTERY 12"
1 I NEOAT 0774
J
3ND
ENCLOSEDWITHIN
GENERATOR ENCLOSURE
DISCHARGE AIR
TOP VIEW
1040
48 (40.9j
I1.91 EL LINT
LEFT SIDE VIEW
NOTE 5)
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PART LISTINGS.
NOTES
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (431 WIDE X 1885 (74.2') LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA TO STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL I CIRCUIT BREAKER INFORMATION:
-SEE SPECIFICATION SHEET OR OWNERS MANUAL
-ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUMP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SNITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR ANDIOR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
S. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 51&11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAMMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EIKKAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
980
SEE NOTE
138.61
JERAU.
EIGHT
IEIGNT
ACCESS
ASSELACCEONTROL
ASSEMBLY,
I48
t
L
PANELACCESS,
ryp
YP
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
776 j30.61
45
OVERALL WIDTH
I1.
REARVIEW
TYI
KFIGHT WTA
GIHEMT
ENCLOSURE
WEIGXT
GEN6ETGNLY
MIGHT
SNIPPING 6KIG
6XN%NO WEGH!
WA
MATS RVA
KO 61
KG 11881
K<1M1S61
MMIWN
FSINGLEPMSE21.6.
SE I7AKVSEt
A2ALAIWH21
AL
42616/01
JORSI
CVWA1WH21
DIMENSIONS: MM IINCHI
RIGHT SIDE VIEW
0
45
LEFT SIDE VIEW
DIMENSIONS: MM UNCHI
REAR VIEW
LS)
71
C/
m
z
m
m
D
n
s
— Protector?
QS Series
UENERAC®
Automatic
Transfer Switches Service and non -Service rated
Automatic -Smart Transfer Switches
100 - 400 Amps, Single Phase
YL
C @us
C @us
LISTED
s ; �--
*CUL only applies to non -service rated switches
Description
Generac Automatic Transfer Switches are designed for use with single phase generators that utilize an Evolution"" or Nexus'"
Controller. The 100, 200, and 400 amp open transition switches are available in single phase in both service equipment rated and
non -service equipment rated configurations. The 150 and 300 amp open transition switches are only available in a service rated
equipment configuration.
Standard Features
Service rated (RXSW) Generac Automatic Transfer Switches are housed in an aluminum NEMA/UL Type 313 enclosure', with -
electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for
years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. All
switches are covered by a 5 year limited warranty.
* Non -service rated (RXSC) switches are housed in a steel enclosure.
DPM Technology
Through the use of digital power technology (DPM), these switches have the capability to manage up to 4 individual HVAC (24 VAC
controlled) loads with no additional hardware. When used in tandem with Smart Management Modules, up to 8 more loads can be
managed as well, providing the most installation efficient power management options available.
ISO /zoos
GENERAC`
100-400 Amps, Single Phase Automatic Smart Transfer Switches
Functions
All timing and sensing functions originate in the generator controller
Utilityvoltage drop-out............................................................................................................................................................................................._......................<6S%
Timer to generator start..................................................................................................10
second factory set, adjustable between 2-1500 seconds by a qualified dealer'
Enginewarm up delay.................................................................................................................................................................................................................5
seconds
Standbyvoltage sensor..................................................................................................................................................................................................65%
for 5 seconds
Utilityvoltage pickup.........................................................................................................................................................................................................................>80%
Re -transfer time delay...............................................................................................................................................................................................................
15 seconds
Enginecool -down timer............................................................................................................................................................................................................60
seconds
Exerciser..............................................................................................................................................................5
or 12 minutes adjustable weekly/Ri-weekly/Monthly'•
The transfer switch can be operated manually without power applied.
'When used in conjunction with units utilizing Evolution- controls "Adjustable via the controller
Specifications
Model
RXSC100A3
RXSW100A3
RXSW15OA3
RXSC20OA3
RXSW200A3
RXSW30OA3
RXSG400A3
RXSW40OA3
Amps
100
100
150
200
200
300
400
400
Voltage
120/240, 10
120/240, to
120/240, 10
120/240, to
120/240, 10
120/240, to
120/240, to
120/240, to
Load Transition Type
(Automatic)
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Enclosure Type
NEMA/UL 3R
NEMA/UL 313
NEM1A/UL 311
NEMtA/UL 3R
NEMA7UL 3R
NEM1A/UL 311
NEMA/UL 3R
NEMA/11L 311
UL Rating
UUCUL
UL
UL
UUCUL
UL
UL
UUCUL
UL
Withstand Rating
(Amps)
10,000
10,000
22,000
10,000
22,000
22,000
22,000
22,000
Lug Range
1/0 - #14
250 MGM - #6
600 MC - #4 or 1/0 - 250 MGM
Dimensions
R
Model
RXSC100A3
8XSWIGGA3
RXSWl50A3
RXSC200A3
RXSW20oA3
RXSW300A3
RXSC400A3
RXSW40OA3
Height
Hit17.24/437.9
17.24/437.9
26.75/679.4
17.24/437.9
26.76/679.4
42.91/1089.9
31.25/793.8
42.91/1089.9
(inJmm)
H2
20/508
20/508
30/762
201508
30/762
48/1219.2
36/914.4
4811219.2
Width
Wl
12.5/317.5
12.5/317.5
10.5266.7
12.5/317.5
10.51266.7
16.69/423.9
19.181487.2
16.69/423.9
(inJmm)
W2
146/370.8
14.61370.8
13.5/342.9
14.6/370.8
13.5/342.9
21.821554.2
24/609.6
21.82/654.2
DepN (inJmm)
7.09/180.1
7.09/180.1
6.3/160.1
7.09/180.1
6.31160.1
10.06255.5
10.06255.5
10.06255.6
Weignt (Ibslkilas)
20/9.07
22.5/10.21
39/17.69
20/9.07
39/17.69
140/63.5
133/60.33
140/63.5
GE N ERAC Generac Power Systems, Inc. - S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com