HomeMy WebLinkAboutCONCRETE PAD PAPERWORKI
JIM REISNER ELECTRIC, LLC
4886 SW 'HONEV TERRACE SCANNED
PALM CITY, FL 34990 "
-EG000Z442- - — RECEI-V-ED. _ BY
S4: mclecoapty
772=260-0732 JUL 17 2019
iamesre isner19bellsouth.net
ST. Lucie county, Permitting
CONCRETE P.AUFOR27'KW GENERATORS
SIZE: 80"X 46" X & WITH 1/8" DIA.4" WIRE MESH & 4000 .LB. CONCRETE.
GENERATOR WEIGHT. 426LBS
80"x 40" X 6" = .432 CU. YARDS _X'4000 LB; (weight of'1 cu. yd. of concrete
according to the Mineral Information Institute).
The proposed slab.will weigh approximately 2600 lbs. +_426•Lbs. (weight of
Generator)='30261bs:;appr9minate
3/8" X 3" -Stainless Tapcori Fasteners X 4-Von ea. Side_) X 7415 lbs. rating ea. _
29660. lbs.
No Realistic uplift load: I
Side Profile Dimensions of the Generator = 38.6" H-x 62.2" L =16.8 sq/ft.of wind
facin&profile.
3026lb.s. (offset weight) /.16;8 sq/ft (wind.facing.profile)=180.2'lbs. per sq/ft of
horizontal imposed load offset capability_:
This Pad is.adequate for this generator..
.n