Loading...
HomeMy WebLinkAboutCONCRETE PAD PAPERWORKI JIM REISNER ELECTRIC, LLC 4886 SW 'HONEV TERRACE SCANNED PALM CITY, FL 34990 " -EG000Z442- - — RECEI-V-ED. _ BY S4: mclecoapty 772=260-0732 JUL 17 2019 iamesre isner19bellsouth.net ST. Lucie county, Permitting CONCRETE P.AUFOR27'KW GENERATORS SIZE: 80"X 46" X & WITH 1/8" DIA.4" WIRE MESH & 4000 .LB. CONCRETE. GENERATOR WEIGHT. 426LBS 80"x 40" X 6" = .432 CU. YARDS _X'4000 LB; (weight of'1 cu. yd. of concrete according to the Mineral Information Institute). The proposed slab.will weigh approximately 2600 lbs. +_426•Lbs. (weight of Generator)='30261bs:;appr9minate 3/8" X 3" -Stainless Tapcori Fasteners X 4-Von ea. Side_) X 7415 lbs. rating ea. _ 29660. lbs. No Realistic uplift load: I Side Profile Dimensions of the Generator = 38.6" H-x 62.2" L =16.8 sq/ft.of wind facin&profile. 3026lb.s. (offset weight) /.16;8 sq/ft (wind.facing.profile)=180.2'lbs. per sq/ft of horizontal imposed load offset capability_: This Pad is.adequate for this generator.. .n