HomeMy WebLinkAboutHVAC LOAD CALCULATIONSSCANNFD
HVAC Load Calculations 13Y
for St ucieCoun /
Patricia Ross
7606 Fort Walton Ave.
Fort Pierce, Florida 34951
www.KoEnergyDesign.com
Prepared By:
K Oliver
KO Energy Design
561 327-7272
Wednesday, June 05, 2013
Rhvac is an ACCA approved Manual J and Manual D computer program.,
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvae -Residential &Lght Commercial HVAC, Loads
'_ _ _ ,- -_ - _ _ Elite Softwa{e Development, Inc.
KO Energy Desigh LLC ` - " - - _" _ -
West Palm Beach. FL 33411 - - _ - Paue.2
Designed By:
Project Date:
Client Name:
Client Address:
Client City:
Company Name:
Company Representative:
Company Phone:
Company E-Mail Address:
Karen Oliver
Wednesday, June 05, 2013
Patricia Ross
7606 Fort Walton Ave.
Fort Pierce, Florida 34951
KO Energy Design
K Oliver
561 327-7272
www.koenergydesign.com
Desi n Data
Reference City:
Fort Pierce, Florida
Building Orientation:
Front door faces South
Daily Temperature Range:
Medium
Latitude:
27 Degrees
Elevation:
25 ft.
Altitude Factor:
0.999
Outdoor
Outdoor
Outdoor
Indoor
Indoor
Grains
Dry Bulb
Wet Bulb
Rel.Hum
Rel.Hum
Dry Bulb
Difference
Winter: 42
39.4
n/a
n/a
70
n/a
Summer: 90
78
59%
55%
75
55
Check Fi ures
Total Building Supply CFM: 665
CFM Per Square ft.:
0.555
Square ft. of Room Area: 1,199
Square ft. Per Ton:
729
Volume (ft') of Cond. Space: 9;592
Building Loads
Total Heating Required Including Ventilation Air:
20,676
Btuh 20.676
MBH
Total Sensible Gain:
14,615
Btuh 74
%
Total Latent Gain:
5,125
Btuh 26
%
Total Cooling Required Including Ventilation Air:
19,739
Btuh 1.64
Tons (Based On Sensible + Latent)
Knvac is an ACCA approved Manual J and Manual U computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Dan\koenergy\Dropbox\dan\In Progress\SILVIA\ross\ross.rh9 Wednesday, June 05, 2013, 11:20 AM
Rhvac--Residentral8 Llght Commercial HVAC Loads.
-,_,--- - '• , -
_ :__,- -
- _._. -
Elite_So twar_e, Development, Inc:
KO Energy Design LLC
West Palm Beach FL _ 33411
-
-
-
Page 3.
Duct.S►ze Preview
Roan or
Source
Minimum
Meuimum
Rough.
Desig
SP
Duct
Duct
Htg
Clg
Acl.
Duct
Duct Name
Velocit
Velocity
Factor
U1
Loss
Velocity
Lengl
Flow
Flux
Flow
Size
System 1
Supply Runarts
Zone 1
1-Great Room
BuilFln
0
0 0
0.1
519.5
75 ®3 139
1--
2-Kitchen
BuilFln
0
0 0
0.1
672.5
69®I 235
1-
3-Bedroom 1
Built -In
0
0 0
0.1
658.9
56®2
129
1-
4-Bath 1
BuilFln
0
0 0
0.1
196.1
9®
17
1-
5-Bedroorn2
Built -In
0
0 0
0.1
656,6
- 50 WI 129
1--6
6-Bath2
Built-in
0
0 0
0.1
183.3
10®I 16
1-
Other Ducts In System 1
Supply Man Trunk
Built-in
0
, 0 0
0.1
846.6
269 66
1 665
12
Summary
System 1
Heating Flow 269
Cooling Flow 665
C:\Users\Dan\koenergy\Dropbolddan\In Progress\SILVIA\ross\roSS.rh9 Wednesday, June 05, 2013, 11:20 AM
Rhvac.- Residential & Light Commercial HVAC Loads _ .' .1 __ _ ,_.
- -. -.-- .. `.-. -.
_,
--
_ _ Elite Sofhw eDevelopmerd, Inc.
- _ ..
KOEnergy Design LLC
West Palm Beach FL. 33411
Pa e4
'T6tal.8uildin Summa Loads' •
Component Area'
San
Let
San
Total
,.Description ; ouan
Loss
Gain
Gain
Gain
rs1: Glazing -per cust, u-value 0.65, SHGC 0.35 59
1,074
0
1,404
1,404
11 N: Door -Metal - Polystyrene Core 40
392
0
364
364
13A-4ocs: Wall -Block, board insulation only, R4 board 1022.3
4,092
0
2,237
2,237
insulation, open core, siding finish
1613-30: Roof/Ceiling-Under Attic with Insulation on Attic 1199
1,073
0
1,917
1,917
Floor (also use for Knee Walls and Partition Ceilings),
Vented Attic, No Radiant Barrier, Dark Asphalt
Shingles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation
22A-phpt: Floor -Slab on grade, No edge insulation, no 140
5,324
0
0
0
insulation below floor, tile covering, passive, heavy
moist soil
Subtotals for structure:
11,955
0
5,922
5,922
People: 3
600
690
1,290
Equipment:
600
1,500
2,100
Lighting: 0
0
0
Ductwork:
5,277
1,794
5,554
7,347
Infiltration: Winter CFM: 112, Summer CFM: 58
3,444
2,131
949
3,080
Ventilation: Winter CFM: 0, Summer CFM: 0
0
0
0
0
Total Building Load Totals:
20,676
5,125
14,615
19,739
Check Figures
Total Building Supply CFM: 665 CFM Per
Square ft.:
-
0.555
Square ft. of Room Area: 1,199 Square ft.
Per Ton:
729
Volume (W) of Cond. Space: 9,592
Buildin Loads -- - - -- - - __
Total Heating Required Including Ventilation Air: 20,676 Btuh
20.676
MBH
Total Sensible Gain: 14,615 Btuh
74
%
Total Latent Gain: 5,125 Btuh
26
%
Total Cooling Required Including Ventilation Air: 19,739 Btuh
1.64
Tons (Based On Sensible
+ Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and
ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Dan\koenergy\Dropbox\dan\In Progress\SILVIA\ross\ross.rh9 Wednesday, June 05, 2013, 11:20 AM
h'Commercial HVAC=Loads
Elite Software Developme
334
West Pam BeachnFL
ate5
S stem 1 System #T_Summary Loads
Component
Area
Sen
Leto
Sen
Total
Descri tion
�-
Quan..-_
_ Loss
Gain -
Gain
rs1: Glazing -per cust, u-value 0.65, SHGC 0.35 59
1,074
0
1,404
1,404
11 N: Door -Metal - Polystyrene Core 40
392
0
364
364
13A-4ocs: Wall -Block, board insulation only, R-4 board 1022.3
4,092
0
2,237
2,237
insulation, open core, siding finish
16B-30: Roof/Ceiling-Under Attic with Insulation on Attic 1199
1,073
0
1,917
1,917
Floor (also use for Knee Walls and Partition Ceilings),
Vented Attic, No Radiant Barrier, Dark Asphalt
Shingles or Dark Metal, Tar and Gavel or
Membrane, R-30 insulation
22A-ph-t: Floor -Slab on grade, No edge insulation, no 140
5,324
0
0
0
insulation below floor, tile covering, passive, heavy
moist soil
Subtotals for structure:
11,955
0
5,922
5,922
People: 3
600
690
1,290
Equipment:
600
1,500
2,100
Lighting: 0
0
0
Ductwork:
5,277
1,794
5,554
7,347
Infiltration: Winter CFM: 112, Summer CFM: 58
3,444
2,131
949
3,080
Ventilation: Winter CFM: 0, Summer CFM: 0
0
0
0
0
System 1 System #1 Load Totals:
20,676
5,125
14,615
19,739
Check-Figiures
Supply CFM: 665 CFM Per
Square it.:
0.555
Square ft. of Room Area: 1,199 Square ft.
Per Ton:
729
Volume (W) of Cond. Space: 9,592
System Loads
Total Heating Required Including Ventilation Air: 20,676 Btuh
20.676
MBH
Total Sensible Gain: 14,615 Btuh
74
%
Total Latent Gain: 5,125 Btuh
26
%
Total Cooling Required Including Ventilation Air: 19,739 Btuh
1.64
Tons (Based On Sensible
+ Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and
ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Dan\koenergy\Dropbox\dan\In Progress\SILVIA\ross\ross.rh9 Wednesday, June 05, 2013, 11:20 AM