February 13, 2020
Century Complete Homes
8GA1YP4F FEB 2 7 2020
3300 Battleground Avenue Suite 101 BY ST. Lucie County, Permitting
Greensboro, NC 27410 St
Ltj&. Corot,
Attention: Mr. Dan Murray
Reference: Final Foundation Certification for HUD Guidelines
Lakewood Park - Lot 0005- 6303 Hummingbird Way. 79G Fill Soil Lot Conformation
5303 Hummingbird Way, Ft. Pierce, St. Lucie County, FL
UES Project No.:0310.1900516.0006
Dear Mr. Murray:
Universal Engineering Sciences, Inc. was retained by Wade Jurney Homes to provide inspection and testing services
during the construction of the Lakewood Park- Lot 0005 - 5303 Humingbird Way. in 7501 Brookline Avenue, Ft. Pierce,
Indian River County, FL. We provided materials testing services in an effort to ascertain whether the earthwork and
placement of structural fill material for the foundation were performed in general conformance to the approved
specifications and HUD guidelines.
To the best of our knowledge, the foundation soil bearing capacity was satisfied within the depth tested according to
the compaction testing dated 01/2&2020, and meets HUD guidelines. We do not undertake the
guarantee of the work, nor do we relieve the contractor of their responsibility to produce a completed project
conforming to the project plans and specifications, including any deeper site improvement measures.
We appreciate to have had the opportunity to provide material testing services for this project. Please do not hesitate to
contact us if you should have any questions, or if we can be of further assistance.
Universal
COA No.:
submitted
14 i
��f•rlrU a �.•
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
y�z��2en-o
Visit us on the web at www.UniversalEngineering.com
�f
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering - Environmental Sciences
Geophysical Services - Materials Testing - Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310-1900516.0006
UES DOCS No:
UES Report No: 120750-1 DT 012820
In -Place Density Test Report
Client: Century Complete Homes FKA Wade Jurney
3300 Battleground Avenue Suite 101
Greensboro, NC 27410
Project: Lakewood Park - Lot 0005 5303 Hummingbird Way
5303 Hummingbird Way, Ft. Pierce, St. Lucie County, FL
Area Tested: House lot
Type of Test: Field: ASTM D-2937 Drive Cylinder Method Date of Test: 01/28/2020
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
oniv and do not acidrpcs the r nnrlifinn of the __a_ . .
..
..
�•�'•'• v — , yW ul 1 Illdl Vlduu
(2)
ta) comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min, requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
Universal performed two 5 feet deep hand auger borings at the northwest and southeast comers.
No organics, deleterious materials or expansive, highly plastic clays were encountered.
Maximum
Optimum
rri
Proctor
Dry
Moisture
#
Density
Content
25061
106.0
12.5
The proposed residence can be supported upon conventional shallow footing foundation designed for a maximum allowable soil
bearing pressure of 2,000 pounds per square foot (psf).
Notes:
In Place Density Testing must be scheduled for stem wall backfill and footings prior to concrete placement.
These tests are in addition to the tests performed.
Any additional fill placed will require additional testing at standard unit fees.
This testing covers the house pad only.
Pool and deck areas were not included in this study, these items can only be tested as they are constructed.
Please notify us in the event you wish to test pool subgrade and backfill.
This test was performed without deviation from ASTM pmcedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
UNIVERSAL 0
EN.GINEE'RING' SCIENCES
Consultants 16: Geotechnical Engineering •:En'vironmental Sciences
Geophysical _Services'- Materials Testing' -Threshold Inspection
Building Code Administration, Compliance inspection &Plan Review
820 Brevard Avenue • Rockledge FL 32955 - 321.638.0808 • Fax 321.638.0978 ! q /,-c\V �f-/_ qq
February 13, 2020 (�
Century Complete Homes
3300 Battleground Avenue, Suite 101 SCANNED
Greensboro, NC 27410 _ _ BY-
-
Attention: Mr. Dan Murray
Reference: Final Foundation Certification for HUD Guidelines
Lakewood Park Lot 0008 79G Fill Soil Lot Conformation
5305 Hummingbird Way, Ft. Pierce, St. Lucie County, FL 32967
LIES Project No.: 0310.1900516.0006
Dear Mr. Murray;
Universal Engineering Sciences, Inc. was retained by Lally Development, Inc. to provide inspection and testing
Services during the construction of the Lakewood Park Lot 0005 — 6305 Hummingbird Way 79G Fill Soil Lot
Conformation in Ft. Pierce, St. Lucie County, Florida. We provided professional observation and materials
testing services and have made every effort to ascertain whether the earthwork and placement of structural fill
material for the foundation were performed in general conformance to the approved specifications and HUD
guidelines.
To the best of ourknowledge, the foundation soil bearing capacity was satisfied according to the compaction
testing dated 0112812020, and meets HUD's guidelines. We do not undertake the guarantee of the work, nor
do we relieve the contractor of their responsibility to produce a completed project conforming to the project
plans and specifications.
We appreciate to have had the opportunity to provide material testing services forthis project. Please do not
hesitate to contact us if you should have any questions, or if we can be of further assistance.
Respectfully submitted
+;�tt ltllfrritf; Universal Engineering Sciences
E�j� COA No.: 00000549
Digitally signed by
Richard E Hoaglin
DN: c=US, o=UNIVERSAL
NO -4 • ENGINEERING SCIENCES
• rC.ta.G>d`eC�L �i��il-JiNC,
ou=A01410D00D0016656
sS,;rQF .` 96604900003A80,
�
��.` 'rcn=Richard'E:Hoaglin
Date: 2020.02.1408:38:10
-05'00'
This item has been electronically signed and Richard E. Hoaglin, P.E.
sealed by Richard E. Hoaglin, P.E. using a FLORIDA
Digital signature. Printed copies of this meet No. 48796
Professional En
document are not considered signed and g
sealed and the signature must be ved5ed on
any electronic copies.
Visit us on the web at www.Universa[Engineering.com
U N 1 ` iE R S A L ES DProject No:
OCS No: 0310.1900516.0006
ENGINEERING SCIENCES LIES Report No: 120750-1 DT012820
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client: Century Complete Homes FKA Wade Jurney
3300 Battleground Avenue Suite 101
Greensboro, NC 27410
Project:_ _Lakewood Park - Lot-0005-5305 Hummingbird Way -
5305 Hummingbird Way, Ft. Pierce, St. Lucie County, FL
Area Tested: House lot
Type of Test: Field: ASTM D-2937 Drive Cylinder Method Date of Test: 01/28/2020
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
Drive sleeve west side of pad
0-1 ft
12.00
25061
104.4
8.1
98
A
2
Drive sleeve west side of pad
1-2 ft
12.00
25061
105.4
9.2
99
A
3
Drive sleeve east side of pad
0-1 ft
12.00
25061
105.5
8.6
100
A
4
Drive sleeve east side of pad
1-2 ft
12.00
25061
103.7
8.2
98
A
5
Drive sleeve north side of pad
0-1 It
12.00
25061
105.0
9.0
99
A
6
Drive sleeve north side of pad
1-2 ft
12.00
25061
103.8
9.2
98
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
25061
106.0
12.5
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
Universal performed two 5 feet deep hand auger borings at the northwest and southeast comers.
No organics, deleterious materials or expansive, highly plastic clays were encountered.
The proposed residence can be supported upon conventional shallow footing foundation designed for a maximum allowable soil
bearing pressure of 2,000 pounds per square foot (psf).
Notes:
In Place Density Testing must be scheduled for stem wall backfill and footings pdor to concrete placement.
These tests are in addition to the tests performed.
Any additional fill placed will require additional testing at standard unit fees.
This testing covers the house pad only.
Pool and deck areas were not included in this study; these items can only be tested as they are constructed.
Please notify us in the event you wish to test pool subgrade and backfill.
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.