TRIANGLE TESTING LAB, INC.
CoA#31 01
4750 ROYAL PALM BEACH BOULEVARD
WEST PALM BEACH, FLORIDA 33411
(561)790-3049
e-mail: triangle2992(dqmaii.com
Date: October 17, 2019 -SCANNED
To: The City of Port St. Lucie Building Department BY
Re: Soil Compaction Report -Density of In -Place Compacted Soil Lucie Counti
SYNERGY HOMES - RESIDENCE
12192 RIVERBEND TRACE
PORT SAINT LUCIE, FL
Test Date
Test #
Test Location
Elevation
In -Place Readings
MMPD Values
%
Density
Moisture
Density
Moisture
10/16/19
1
Southeast Area
1'-2'
105.8
7.4
109.5
6.6
96.6
10116/19
2
Center Area
0-11
106.5
6-8
109.6
5.6
97.3
10/16/19
3
Northwest Area
t 1-2'
1 105.9
7.1
109.5
6.6
96.7
Remarks: All elevations are measured from top of pad grade. (Mod Proctor Test #1)
Verffication Statement
This statement shall serve as verification that the soil beneath the proposed structure has been tested in accordance
with Section R401.4 of the 2017 Florida Building Code, Residential edition. The tests were conducted from the
existing grade.
Density tests were taken at a minimum of three (3) locations throughout the total depth of fill. The depth of fill was
approximately 2.0 feet. The foundation setbacks were based on information furnished by the client, at the time of
testing.
Based on the location and depths tested, we verify that the fill has been compacted to a minimum of 95% of the
maximum dry density as determined by ASTM D-1 557 and that the minimum soil bearing value beneath the proposed
foundation area is 2.500 Dounds Der sauare foot.
Respectfully submitted,
NS
C,
0
Richard Boyette, FL PE #42485
Vice President ov cc
Lij Z
October 17, 2019
V
File # 21546 N""'
Permit # 1908-0177
N4
OCT 2 4 2019
Permitting Department
St. Lucie County, FL