HomeMy WebLinkAboutGENERATOR PAPERWORKGENERAL° GUARDIAN° SERIES
STANDBY GENERATORS - PREPACKAGED
R
Ie �i'°i i
Air -Cooled Gas Engine Generator Sets
INCLUDES:
True Powers Electrical Technology
—`- Twe=Line-L-CD Tri-lingual
Digital Nexus' Controller
Electronic Governor
• 200 Amp Service Rated Nexus Smart
-Switch'" with Digital Load Management
Technolo NEMA 3R Rated
Standby Power Rating
Model 005875-1 (Aluminum - Gray) - 20 kW 60Hz
External Main Circuit Breakers
System Status & Maintenance Interval i'...-
a
LED Indicators and GFCI Duplex Outlet I t GENERAL
(`�'SoundAttenuated Enclosure
Flexible Fuel Line Connector ~- -
Composite Mounting Pad
Base Fascia f
•GOODS"•.
Natural Gas or LP Gas Operation IUD HOUSEKEEPING ! _ lU'F�F-Ft li-
�...�. ...Y,.: VC L. r r ESr
3 Year Limited Warranty f LISTED -
j • UL 2200 Listed
FEATURES
O INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC'S success in "IMPROVING POWER BY DESIGN." But it
doesn't stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable GSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
O SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This stale -of -the -art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY
by electronically torque -matching the surge loads to the engine. An
unequalled ±1°%voltage regulation.
O TRUE POWER`' ELECTRICAL TECHNOLOGY: Superior harmonics and O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer
sine wave form produce less than 5% Total Harmonic Distortion for utility network provides parts and service know-how for the entire unit, from the
quality power. This allows confident operation ofsensitive electronic equipment engine to the smallest electronic component
and micro -chip based appliances, such as variable speed HVAC.
O TE$T 9ITERIA:
O GENERAL TRANSFER SWITCHES. Long life and reliability are
41 RATYPE TESTED NEMA MG1-22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
SYSTEM TORSIONAL TESTED . MOTOR STARTING ABILITY confidence is that the GENERAC product line includes its own transfer
Z OW-1-7 systems and controls for total system compatibility.
ST. LC7CI`E COUNTY BUILDLNG DIVINIRN
REVIEWED FOREVIEWED BYR� iP�i1NC
DATE 2--- V-4 11 -2-- N E RAC® L .,
Fd.ANS AND PEIL\IlT AiIIST BE KEPT 0
OR NO INSPECTION WILL BE MADEi
FEATURES Generac@ GuardianO Series Standby Generator - 20 kW
•Generac (OHVI) Design
Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cylinder walls and plasma
moly rings help engine run cooler, reducing oil consumption. Because heat is the primary cause of
engine wear, the OHVI has a significantly longer life than competitive engines.
•"Spiny-lok" cast iron cylinder walls
Rigid construction and added durability provide long engine life.
•Electronic ignition/spark advance
These features combine to assure smooth, quick starting every time.
-Full pressure lubrication system
Superior lubrication to all vital bearings means better performance, less maintenance and significantly
longer engine life. Now featuring a 2 year/200 hour oil change interval.
• Low oil pressure shutdown system
Superior shutdown protection prevents catastrophic engine damage due to low oil.
• High temperature shutdown
Prevents damage due to overheating.
• Revolving field
Allows for smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
e
-Skewed stator
Produces a smooth output waveform for compatibility with electronic equipment.
-Displaced phase excitation
Maximizes motor starting capability.
-Automatic voltage regulation
Regulates the output voltage to ±1 % prevents damaging voltage spikes.
• UL 2200 Listed
For your safety
•Fully Automatic
Transfers your vital electrical loads to the energized source of power.
• DIM Technology
Digital Load Management technology allows for the smart control of two air conditioners without any
additional items.
-Remote Mounting
Mounts near your existing distribution panel for simple, low cost installation.
• ILL Listed
For your safety
-Manual/Auto/Off switch
Selects the operating mode.
-Utility voltage sensing
Constantly monitors utility voltage, setpoints 60% dropout. 80% pick-up, of standard voltage.
-Generator voltage sensing
Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
-Utility interrupt delay
Prevents nuisance start-ups of the engine, adjustable 10-30 seconds.
m • Engine warm-up
Ensures engine is ready to assume the load, setpoint approximately 5 seconds.
-Engine cool -down
Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
• Programmable seven day exerciser
Operates engine to prevent oil seal drying and damage between power outages by running the
generator for 12 minutes every week.
-Smart battery charger
Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
-Main Line Circuit Breaker
Protects generator from overload.
-Electronic governor
Maintains constant 60 Hz frequency.
-Weather protective enclosure
Ensures protection against mother nature. Hinged key locking roof panel for security.
Lift -out front for easy access to all routine maintenance items. Electrostatically applied
textured epoxy paint for added durability.
-Enclosed critical grade muffler
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
-Small, compact, attractive
Makes for an easy, eye appealing installation.
-S9iq
Sound attenuated enclosure ensures quiet operation
BLILDL�
DIVVION
ST.�jLU�CIE1�COLTrY
•�EVIE ED r° nnee IPL \
E
Eas Insta ion
_
•�iteMo '
RLANIS A\"D Y R.�f1T 11tUST B
KEPT ON JOB
OR NO INSPECTION q ILL BI
FIM
MADE'`
SPECIFICATIONS GENERAC'
Rated Maximum Continuous Power Capacity (LP)
" " --20,000 Wafts'
Rated Maximum Continuous_ Power Capacity ING)
18,000 Watts'
Rated Voltage
= - 240` -
Hated Maximum Continuous Load Current —240 Volts
83.3 LP/75 NG
Total Harmonic Distortion
Less than 5%
Main Line Circuit Breaker
100 Amp -
Phase -
.� - 1 ... ..
Number of Rotor Poles
2
Rated AC Frequency -• -
_
60Hz
Power Factor -
i
Battery-Requirement{not included) _
Group 26R-12Voltsand525Cold-cranking-AmperesMinii
Unit Weight (Pounds/Kilos)
451/204.5
Dimensions (L x W x Hj Inches/mm ..
4B x 25 x.29 (1218 x 638 x 732)
Sound output in dB(A) at 23 ft. with generator operating at normal load
66
Sound output in dB(A) at 23 ft. with generator in-OuietTest - low speed, exercise mode.. _
60
Number of Cylinders
Displacement
Cylinder Block
Valve Arrangement`
Compression Ratio
Starter
Oil Capacity Including Filter
Operating RPM • .,
Fuel Consumption
Natural Gas
Liquid Propane
For
'GENERAC OHVI V-TWIN
2
999co
Aluminum w/Cast Iron Sleeve
Overhead Valve
Solid-state w/Magneto
Electronic-
9.5:1
12 Vic
Approx. 1.9 Ots./l.8L
cu.ftJhr.
1/2 Load
206
Full Load
294
113mr (gal/hr) [Liler/hr]
1/2 Load
69 (1.89) [7.15]
Full Load
106 (2.90) [10.981
fissure to generatorfuelinlet at all load ranges - 5 to 7 inches of water column for natural gas, 10'to:12'inchesoFwater calming for LP gas
multiply fla/hr x 2520 (LP) or W/hnx 1000 (NG)
-I -
-Auto
-0ff
-ManuaVrest (start)
_
Programmable start delay between 10-30 seconds
Engine Start Sequence
Engine Warm-up
Engine Cool -Down
_
Starter Lock -out.
Smart Battery Charger
Automatic Voltage Regulahciii viith-Over and Under Voltage_ Protection
-
Automatic tow Oil Pressure Shutdown
Overspeed.Shutdovm ..,� _ .
.• ,.
High Temperature Shutdown
Overcrart Protection
Safety Fused
Failure to.Tianster;Protecuon
Low Battery Protection l�
C01
Event ST. LUCIE .
50 Run tog C
NVED'EOR O\ L
Future Set Capable Exercisey.EVIL
REVIEWED BY.
Incorrect Wiring Protection _^
���
Internal Fault Protection DATE .rre•r
w, Ke.c
ease
Automatic Start on Utility failure. 7 day exerciser
.Stops "unit. Power is removed. Control and charger still operate.
Start with starter control, unit slays on. If utility fails, transfer to load takes place.
Standard
Cyclic cranking: 16 sec. on, 7 rest (90 sec, maximum duration)
5seconds'
1 minute
.Starter cannot re-engage until 5 sec: after angfrre'hes stopped.
Standard
Standard:._ r
Standard
Standard
Standard
Standard
JI�L_ _,� Standard:
LU1V Standard
Standard .'.
Standard
�1rFTpg„c i Standard.�.`'
IS03046 and 01N6271). *Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient
decreases about 3.5 percent for each 1.000 feel above sea level.
Generac® GuardianO Series Standby Generator - 20 kW
Current Hating (amps)
Utility Voltage Monitor (fixed)
-Pick-up
-Dropout
Return to Utility
Exerciser weekly for 12 minutes
UL Listed
Enclosure Type
Withstand Rating (Amps)
DEPTH
200
250
80%
60%
approx.13 sec.
Standard
Standard
NEMA 3R
10,000
-------400MCM=#4--
Transfer Switch Features
• Includes Digital Load Management technology standard (DLM).
• Intelligently manages two air conditioner loads with no additional hardware.
• Up to four more large (240V) loads can be managed when used in
conjunction with DLM modules.
• Electrically operated, mechanically -held contacts for fast, clean
connections.
• Rated for all classes of load,100% equipment rated, both inductive and
resistive.
• Dual coil design.
• Service Rated
• NEMA 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
200 Amps 120/240, 1e
Open Transition Service Rated
Height
Width
Depth
H1
H2
W1
W2
Inches
27.24
30.0
11.4
13.5
7.09
mm
692.0
762.4
289.0
1 343.0
1 180.0
Design and speaifications subject to mange without notice. Dimensions shorn are appradmate. Contact your Geneac dealer for certified davAngs. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
OR NO INSPECTION WILL BE 11 "k'
GENEAC° STANDBY GENERATOR ACCESSORIES
DESCRIPTION
The DLM Load Control Module is a 50 amp contact housed in a NEMA 3R enclosure for indoor and outdoor installation applications. Through the use of the
DLM Modules in conjunction with any of the 100-400 amp Nexus Smart Switches, household or business loads can be intelligently managed enabling the
use of a smaller, more efficient generator system. Up to four DLM Modules can be used with a single switch.
SPECIFICATIONS
Power Supply Source....................................................................................--...........
Contactor module is supplied with 120VAC from the load control module in the transfer switch.
NominalSupply...........................................................................................................................................................................
........................................... .......................... 120VAC
CoilVA Inrush...........................................................................................................................................................................................................................................................30
CoilVA Sealed.........................................................................................................................................................................................................................................................
6.5
Poles..........................................................................................................................................................................................................................................................................
2
Voltages........................................................................................................................................................................................................................................................... 120/240
ResistiveAmps......................................................................................................................................................................................................................................................... 50
F/LInductive Amp ...........................................:
Locked Rotor Amp.....:37..... L:.Ci£...C4�.�.1,y BL LDE*G DIVISION.............................................................................................................................................40
\ii' .I\CE'...................................................................................................................................
...........
....-240@240V
UL50 ......................_-.................:.......:........................................................................................................................................................ Yes
e 'F'ti
'LAt , till RINHT ;\LUST BE KEPT ON JOB
Oit..0,'.SL'LCTtoLE N E RAC°
G,enerac® Standby Generator Accessories, DLM Load Control Module
DIMENSIONS
i� —177.Smm
7
107.3mm
T
92.6mm
1/2' Conduit Knockout
ST. LUCIE COUNTy BUILDING DIMION
REVIEIVED FOR CONPL NCE
REVIENVED By
DATE
BLANS A_\"D pER_NIIT MUST BE NUT ON J0�
OR NO INSPECTION WILL BE MADE+
GEN ERAC Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
02010 Geneac Power Systems. Inc. AB rights reserved. An specifications are subject to change without Must. Bulletin 0187410SBY.A/ Panted In U.S.A. 04107110
1
For tine most up to date equipmentlpad sizing guide, download
It at or
www.divers(tech:comiliterature/hurricanapadslzes. tdl
call Oiversilach at Uo0.995.,222. I
411 CladUteTm Hurricane Pads
Pads Bra
Hardware
l.itnited LINUI1e Warrant, —�
•y.
w p -80t Wersi7ecli
""'Uerunon DiVACR) Industry, ADlegruaV,.
Headquartered In suite Atlanta. GA mah'opolltBn area, DlverslTech
Mechanical. elect rical,och roduct s, v4 Ich Includes a wido range of
systems, The company maintains nP Aufoctur"turil and fordisHVACR
Is JDVd In key U,S, IBcatloas and In the Far East DlverslTech bas
endyod c candled history or successrul growth and has acquired
hndustry.recognlaA brand names Including Wagner Manuractudng
I'd Specialty Chemical,
Downdoolf all oloclmnic version of this brcchurr, at•
www,Jivarsiluuh,canl/Intern lure/IIL•flydnd�,pJf
DIVUSITech Car anallell
Gfiro Sllgarlaa�Parhway
D111111 GA 30097
tlna.005,2222
078,542,370o FAD(
wWWAIVOMiluch.min
rK IhKh lmpp;p,n
111.11'M1I.I nlx1 IIh,
CLADLITEaa HURRICANE