HomeMy WebLinkAboutPLANSDesign Parameters 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category I. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region 8 Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VUv=160 MPH Exposure Category, Paragraph '"1609.4.3: B Applicable Codes. Regulation and Standards . 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition General Notes 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all lowland regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is subject to approval. Specifications The following specifications are applicable to this projects: 1. Where concrete specification are required, whether in the screen enclosure scopE or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 3/4" max - ASTM C 33 1.1.3. Air entraining +/-1 % -ASTM C 260 1.1A. Water reducing agent-ASTM C494 1.1.5. Clean Potable water 1.1.6. Other admixture not permitted 1.2. Metal accessories shall conform to: 1.2.1. Reinforcing Bars-ASTM A615, grade 60 1.2.2. Welded wire fabric-ASTM At 85 1.3. Concrete slump at discharge per chute not less then 3" or more than 5. Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hotweather recommendation 1.5. Moist cure or polyethylene curing required. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. All aluminum components embedded within concrete shall be coated with 6 bituminous paint or epoxy. 1.8. Fiber reinforced concrete per ASTSM C1116 is an acceptable alternative to 6X6 WI A/W1.4 WWF. 2. Aluminum extrusions shall be 6005 TS Alloy. 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Self Mating Beam Sections are to be stitched with either 914 screws 6" from end 24" on center or #12 screws 6" from end 1Y' on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the anchors must extend past the pavers and reach proper embedment into the underlying foundation. 8. All Flashing and waterproofing shall be provided by the contractor. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. 10. Vinyl and acrylic panels shall be rerwved when wind speeds exceed 75mph Foundation Design: Existing a"xS" Thlckend Edge 4" Slab on Grade Existing concrete. No additional concrete fooling is required to resist the loads imposed by the proposed construction if the existing footing is in sound condition, free from structural cracking, spelling, or other deterioration. Roof Type Screen Size Full Mansard 18114 HOLLOW SECT10N5 SELF MATING BEAN (sMa) 2xz 2xr[O.NT 2x4SMa: z Px0.Bu•v0.10P 2.1 rx3•gOZSV 2M56MB: ffxSxOL50't O.tOP 2XC r[Px0.05P 2x6sMB: rx6•x0.OW.G.1m 2.5: rx5•x0MV 2x2SMB: 7xr'x0.05r'x0.120- 414: rx4-xa 6x6: "T.0.12S MINIMUM FASTENER CmE DISTANCE: 117 :TIONs I MMIMUMFABIENERSPACNG:YS RC:REC.CH NE r xrx 0.04r CONCRETE SCREWANGNORI SHIEUMATEL SCREWS(SMS): rx Yx 0.0w 61MPSONTRENNGGREpUNAIENT RW W6DIXGREWNAtEM r:4-x D.54r NOTE: THIS DRAWING IS FOR ILLUSTRATIVE PURPOSES. DRAWING NOT TO SCALE. USE DIMENSIONS GIVEN. CABLE BRACING MAY TERMINATE AT SLAB IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL ea 3 • GHOST a GUrIER ■ in(TYP) c-+ z \M1 V3 2n V3 2x] '1X1 M '1X] V3 • i$E �F �S �N �E r-r I r-r r-r I r-r I r-r 1 r-r x'-e- R a z P%106MB Cary Beam 2%105M9 In (TYPI 3 I eft'—o• I 5'-3•� 00000�®�� p�`yp >� ? f� o o ooOOO��O®� I� 7 St. LuciPCounty File Copy RrwIEWE® FOR CODECOMPLIANCE ST. LUCIE ON BOCC SHEET 1 N 4 Ile• BRACKET CUT FROM V x 5-ANGLE. CONNECT WITH (9) #14 X 3I4' SMS UPRIGHT DOUBLE COMPRESSION SLEEVES BRICK PAVERS MAY NOT BE PRESENT. ENSURE MIN. REQUIREDANCHOR EMBEDMENTINTO CONCRETE FOUNDATION PER PLAN 4BR-1 CABLE BRACING 2 SCALE:NTS 2�NVB-ANGLE EA SIDE I tf �c4 SIDE VIEW (1) NO' DIA CONCRETE SCREW ANCHORS INTO EACH LEG EVE RAIL EYE BOLT FOR CABLE TENSION 1M'S.S.CABLE 1-114 x SS19' x 1 W ALUM. FLAT BAR. WITH (2) 31e' OW CONCRETE ANCHORS. MIN. 2-316' EMBEDMENT < •d (I) In-DIA TRRU BOLT WITH NYLOCKJAM NUT (JAM NUT WITH THREADLOCKER MAY BE USED, IN LIEU). DO NOT OVER TIGHTEN. TIGHTEN ONLY UNTIL CONTACT. FOR 2X2 AND 2X3 UPRIGHTS, USE (4) #14 x Sl4' SMS INTO POST BRICK PAVERS. MAY NOT BE PRESENT, ENSURE MINIMUM CONCRETE EMBEDMENT. TOP VIEW AT INTERMEDIATE FOUNDATION PER PLAN UPRIGHT PER PLAN O.S. ANCHORED TO CONCRETE WITH 1I4' DIA CONCRETE SCREW ANCHOR ® 24. O.C. MAX (4) #14 x 3I4' SMS INTO POST FOR CORNER CONNECTION FASTEN 1X2 WITH#12 x W4' SMS 024.O.O. 0TX2 U 4 J" 4 u < (4)#14x2-SMSTHRU IX2 NTO POST FRONT VIEW nB-1 DATI UPRIGHT TO FOUNON CONNECTION 2 SCALE:NTS ® O UPRIGHT TOP VIEW AT CORNER — Note - Orientation may be different. NOTES: 1. SEE THE NOTE BELOW FOR SCREWS SPACING. THE NUMBER OF SCREWS SHOWN ARE FOR ILLUSTRATIVE PURPOSES. DO NOT COUNT SCREWS ON DRAWING. 2. GUSSET DIMENSIONS AREA MINIMUM (2) REDD-(1) FA SIDE OF BEAM -MAY BE INTERNAL OREXTERNAL 3. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 11A'GC SPACING. 4. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. t TYPICAL INTERNAIJEXTERAL GUSSET CONNECTION SCALE:NTS • (4)#14x314SMSINTO O O POST O O BRICK PAVERS MAY NOT FOLLOW BECHOR MID EEMBM CONCRETE CONCRETE EMBEDMENT • OO ' w OM 2E d w - a d a SIDE VIEW --OI PER PLAN laO.B. ANCHORED TO CONCRETE WITH 11V DIA. ANCHOR (MIN. 1-1/4- III 24. O.C. SMS INTO > L24� ) w DIA CONC. im NCHOR. EMBED MIN. d i. a FRO"VIEW DETAILS .SEE PLAN FOR iDJ-1 DOORJAMB CONNECTION 2 SCALE:NTS OPTION 2: 2- x 2' x 1I9'ANGLE WITH (2) #10 x WV SMS IN EACH FLANGE, EACH SIDE(iYP) WITH (4) #10 x 3- WOOD SCREWS Lay 6- FROM ENDS & 12' O.C. CONC. lie DIA. x 3-CONCRETE SCREW ANCHOR ® 6-FROM ENDS & 24 O.C. M-1 PURLIN / GIRT / O.B TO HOST CONNECTION lll-2 SCALE:NTS PLATE PER (DETAILS f0.1 C PURLIN m o PURMN 0 0 d V c00 10 flyyl � C Y 0f2 ee4' D)014 X 2- SMS THRU BRACE INTO BEAMTHRUGUSSETPLATE LL /6 M #3 9 M 0 n7 A LL BRACE AT INTERMEDIATE JOINT N a N C 9�0 'O Q LL m � REVIEWED. FOR f"' � •s 0 4'MAX e�� CODE 'L,#�tlWYdP�#I/" N � CODE a ST. LUCIE CUUN I eE- Y EAVE RAIL „ - • w 1I4' DIA. THRU BOLT WITH NYLON BRACE AT EAVE RAIL WASHER&STAINLESS STEELNUT SHEET B ROOFBRACING 2 2 SCALE: NTS f m—no"n Kti u�A6Cw 9NTHWWX3'LAGS(3 PER BRACKET) AND TO GUTTER WITH (1) W8'X 3• NOTE: (2) M" DR x 4' LAG SCREWS FOR TTACHN SIDEUSINFACE OF B ATTACH INSIDE FACE OF BEAM LAG (t424'O.C. SPANS GREATER THAN 30'-0' x BEAM COLUMDEPTH LONGANGLE WITH(8)#Ix x3I6• 1' X 2' OPEN BACK IS NOT NEEDED IF SMS EACH LEG. GUTTER HAS SPUNEGROGWE OTHERWISE, CONTO COLUMN PER PLAN. NOTCH COWM 3EAMIPUflUN WITH (2) i10 x 2-11r 2' WE TO ACCEPT CARRIER BEAM THRU BEALVPURUN INTO SCREW 1-IM'x IW x 0.125'AW M STRAP BOSSES. CONNECT 1X2 TO GUTTER (S 014 x W IN BOTH CARRIER BEAM WITH (1) 010 x MAI' SMS ® 6' FROM AND POST EACH SIDE. (10 TOTAL) EN AND24.O.C. 00 00 1 O0 00 1 00 io Z oq 00 00 A 00 0 NOTCH 6O I IOM RANGE OI PURUN TO OVERLAP UPRIGH DETAIL AT CORNER (PLAN VIEW) I EAVE RAIL INTERNALLY SCREWTHRU BEAM INTO / `--CONTRACTOR TO VERIFY FASCIA IS 2'x 2' x 1/6' x 2' ANGLE WTT11 (4 MINIMUM OF 2' x 0'.IF LESS, YX 4' 0 IItdx 3I6.6M61M0 BEAMIPURUN PTSUB FASCIA SHALL BE PLACED AND(4)((2) IF 1X21S SLREWEDTO BEHIND EKISTINGAND LAG LAG `�� 0 --- T� BEAM USING SCREW BOSSES)II14 SUPERG=R SCREWS SHALL BE LENGTHENED O X we SMS INTO IX2 (OR GUITERI- O FULLY PENETRATE SUB FASC01 9".. .D. ATTACH TO UPRIGHT REPEAT ON OTHER SIDE OF IFNOFASCIAISEXISTING,ADO2•x O WTTH(2)Y10x2lXSMSTHRU BEAMIPURUN 4° PT FASCIA WITH In' DR. LAG O UPRIGHTINTO 6CREWBOSSES WHEN BEAM IS LARGER THAN GUTTER, .082' BACKING PLATE BOLTS, EMBEDDING I-Vr INO 1"x2"O.B.ATTACHED—� PLUS 010 x 1 V2' SMS 6' FROM 21I8'x MS` x 0.06r(WN.) ALUM ON INSIDE OF GUTTER TRUSS TAILS.PRE-DRILL NATHW. EACH SIDE OF POST EACH SIDE OF UPRIGHTAND RECEMNG CHANNELWIMIN.(2) 612x DIABRO PREVENTSPLIITING WgTHp12x1-1I SMS TYPICALAT2d'O.C.MAX 3M-SMS (Q 6' FROM BOTTOM AND 24'O.C. RH-1 BEAMIPURLIN TO GUTTER CONNECTION RC 4 CARRIER BEAM TO COLUMN CONNECTION R I SCALE:NTS 3 SCALE:NTS r x 2'1l8• .2• LONG ANGLE WITH (2) 012 x 1-lW SMS INTO POST S (1) ale' DR X 2-IW CONCRETE SCREW ANCHORINTO UNCRACKED CONCRETE (HOLE DEPTH= 3.112j rxro.B COLUMN PER (2) 318' DR THRU BOLTS IN COLUMN ANDINTERNALANGLES. O 2 x2°x 114•(LENGTH =INTERIOR OF WDTH OF COLUMN) ANGLE WITH WW ® OO DR CONCRETE SCREW ANCHORS (BE TABLE 'A' FOR QUANTITY) MIN 2-12' INTO UNCRACKED CONCRETE MOLE DEPTH a 3-1TLj. (2) Ye' DIA BOLTS THRU COLUMN O.B. AT CORNER POST AT CENTER POST 6-3 POST TO FOUNDATION INTERNAL CONNECTION 3 SCALE:NTS CREWBOSSES WITH (3)Sjp x 1-lW SMS ATTACH 1X2 TO EAVE RAIL WITH II10 x�MS ®6• FROM 24. O.C. r x1ACPLATEII11 x 3/4'SM6 EACH SIDEDE OF BEM UPRIGHT PER PLAT RC-2 UPRIGHTTOPURLIN CONNECTION 3 SCALE:NTS C J ANCHOR MEMBER SIZE soF SCREWS 2X2.2X3 4 2X4-2X5 6 2X6-2%T B 2XB-2XB 10 1.11 2 ROOFBFAMI PURUN PER PLAN DOQ��ppAAAAAA00ppppppoOO - [coo c oOOOOoo®� � � .c.4���000o c _ REVI/E�WEE�® P RUNTOCARRIERB O®E" COMP I, CARRIER BEAM PER J 'WITH rxr x Imo' x [DE PLAN OF ROOF BEAM] LONG 1 �/'�CIE r/� ANGl.EWITH#14x W4-SMs-. N� SEE TABLE FOROUANTIIYBOCC OF6CREW5. RQEACH SECTION VIEW SIDE) C-5 CARRIER BEAM TO ROOF BEAM / PURLIN CONNECTION 3 SCALE:NTS 0m3 Cd 9 0 d N 21 T N � 7 A 'O 0 'r- L TLL •� ad+ N L � 0 may` N N O. 9 Lo O Q LL j V L 0 i .o it SHEET 3