HomeMy WebLinkAboutA M ENGINEERING PAPERWORKC A. M. ENGINEERING AND TESTING INC. 35041NDUSTRIAL33RDSTREET RECEIVE FT PIERCE, FLORIDA 34946 LOCALOFFICE: (772)461-7508 (772)461 8880AIJ(j 0 7 2006 POS REPORT OF STEM WALL BACKFILL COMPACTION - --C-lient:—MB-Corporation Site: 728 Nettles Blvd. St. Lucie County, Florida Stem Wall Backfill Report Date: 8%7/06 Project No: Report No: 9899 Permit No: 0606-0476 SCANNED BY St LudeConots Density tests and Hand Cone Penetrometer (HCP) readings were made in the stem wall backfill (slab area) to a depth of one foot at a minimum of three locations. Density tests were performed in the upper one foot of fill. HCP readings were taken in hand auger boreholes at one foot intervals from slab grade through the depth of fill. At the time of our testing no information was available regarding the foundation setbacks. The density tests were performed in general compliance with ASTM D 2922. The HCP test, in conjunction with information about the soil type, is empirically correlated to the relative density of subsurface soils. Density Test No. Date Tested Location Elevation (feet) D Densi s Percent I Compaction In Placel Proctor 9899 8/4/2006 SE Comer 0-1 110.3 115.0 1 95.9 North Side, Center 0-1 112.1 115.0 97.5 SW Comer 0-1 111.7 115.0 97.1 * All elevations are below footing grade. In the locations and depths that were tested, the stem wall backfill (slab area) has been compacted to a minimum of 95 percent of the modified Proctor maximum dry density (ASTM D 1557). No soil borings were performed below the recently placed fill. Distribution: Submitted b Client - 2 A. . ENCID EERFN. AND-T STING, INC. SLC Bldg. Dept. - I ebecca Grant As oli,=P.E. Florida Registration No.:5-1863t; ` r . S:IFort Pierce OfjiceWeiAppsUTTLE LOG BOOKWouse JobsWisc. Noose JobsLSaint Lucie CountyWB(9899)728 Nettles Blvd. SW.doc t l A. M. ENGINEERING AND TESTING, INC. 3504 INDUSTRIAL 33PD STREET FT PIERCE, FLORIDA 34946 LocAL OFFICE: (772) 461-7508 FAx: (772) 461-8880 SCANNED BY St-. Wr'.Iprnifffi REPORT OF STEM WALL BACKFILL COMPACTION AUG 2 4 2006 Project No: Report No: 10029 Site: 728 Nettles Blvd., Nettles Island $Ir: Permit No: 0 0_476 St.Lucie County, Florida Stem Wall Backfill (Slab Area) POSTED pip Density tests and Hand Cone Penetrometer (HCP) readings were made in the stem wall backfill (slab area) to a depth of two feet at a minimum of three locations. Density tests were performed in the upper one foot of fill. HCP readings were taken in hand auger boreholes at one foot intervals from slab grade through the depth of fill. At the time of our testing no information was available regarding the foundation setbacks. The density tests were performed in general compliance with ASTM D 2922. The HCP test, in conjunction with information about the soil type, is empirically correlated to the relative density of subsurface soils. Density Test No. Date Tested Location Elevation (feet) D Densitys Percent Compaction In Placel Proctor 10029 8/18/06 NE Comer 0-1 113.4 115.0 98.6 Center 0-1 112.7 115.0 98.0 SW Comer 0-1 114.2 115.0 99.3 * All elevations are below slab grade. In the locations and depths that were tested, the stem wall backfill (slab area) has been compacted to a minimum of 95 percent of the modified Proctor maximum dry density (ASTM: D 1557). No soil borings were performed below the recently placed fill. Distribution: Client - 1 SLC Bldg. Dept. - 1 Submitted by: AEERING:IND TESTING, INC. Richard Boyette, P Florida Registration No. 42485 SAFort Pierce OJfceWeLippsILITTLE LOG BOOKVfouse JobsWisc. House JobASaint Lucie CountyWB Corp. (10029) 728 Nettles Blvd..doc