HomeMy WebLinkAboutGENERATOR CONCRETE PAD�Letl 1 �W
I \ \ rOTh
\ \ GENERATOR
AMERICAST GENERATOR CONCRETE PAD
PAD
THICKNESS
�Z 1 1� 4P0 LENGTH
ISOMETRIC VIEW
PAD DIMENSIONS: GENERATOR TABLE:
CONCRETE PAD
GENERATOR =_\_
x
GENERATOR UNIT BY
o
SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
N
MINIMUM WEIGHT
REQUIRED)
I
1
-- 54" LENGTH j
1
PLAN VIEW
CONCRETE PAD
ROAD MESH
MASTERFIBER
ry MACI00 3" MIN _q^ MIN
" GROUND--li_I_ -
3
2"h1IN
5U
94„ -_
Y
(ON -GRADE APPLICATIONS ONLY)
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE EXP)
RISK
EXPOSURE (EXP)
RISK
EXPOSURE
EXP
I
C
D
II
C
_ D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf,
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
1196 MPH
46.80 Psf
156.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005983
10 KW
25.00 '
48.00 ".
29.00 ".
3871bs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & 005884
14 KW
25.00'
48.00"
29.00-"
4391bs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459 6461 6462
16 KW
25.00'
48.00"
2900"
5331bs
47.44 Psf
Generac 006721
16 KW
25.00"
48.00"
2800"
4481bs
47.44 Psf
Generac OOS873 & 005885
17 KW
25.00"
48.00'
2900"
4551bs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00"
48.00"
29.00"
421 Ibs
47.44 Psf
Generac 005875 & 005887
1 20 KW
25.00"
48.00"
29.00"
4511bs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00"
4sxv
29.00"
5161bs
47.44 Psf
Generac 006551 & 006552
22 KW
25,00"
48.00"
29.00"
5261bs
47.44 Psf
Kohler 14RE5&20RES
14-20 KW
26.00"
48.00"
29.00"
5001bs
47.44 Psf
GE40323GE&40324GE
13 KW
35.00"
39.40"
39.00"
5401bs
39.09 Psf 1EXP
C170 MPH &D 156 MPH
GE 040382 ISKW
15 KW
33D0"
48.00"
30.50"
484163
43.83 Psf
EXPC 180 MPH &D 156 MPH
GE 04037317KW
17 KW
33.00"
48.00"
30.50"
484lbs
43.13 Psf
GE 40330GE&40331GE
20 KW
33.00"
48.00"
30.50"
600lbs
43.83 Psf
Briggs& Stratton 040243-0
10 KW
31.00"
32.00"
34.00"
430lbs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75"
50.00"
31.60"
507lbs
41.43 Psf
EXP C 175 MPH it[) 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75"
49.00"
31.60"
-562 lbs
43.83Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75"
49.00"
31.60"
5681bs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75"
49.00"
31.60"
570lbs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00'
48.00"
29.00-
406lbs
47.44 Psf
EXP C18614H&D 156 MPH
Generac 007038 & 007039
-20 KW
25.00"
48.00"
29.00"
448lbs
47.44 Psf
Generac007042&7043
22KW
25A0"
48.00"
29.00"
4661Bs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/.(4) C10 SS 316 SELF -DRILLING
SCREWS
V_ TO GENERATOR
(SEE GENERATOR SPECS
i 3'e' THICK GALVANIZED
GENERATOR I WASHER& RUBBER
S = I VIBRATION PAD-
Q) l7
(SEE CONCRETE PAD
w w
SCHEDULEFOR
DIMENSIONS & WEIGHT
REQUIRED)
- 4"
_ I�
-32" WIDTH: t
54" LE_NGTH-
m
n SIDE VIEW
FRONT VIEW
CONCRETE PAD
6,000 PSI
LIGHTWEIGHT
CONCRETE MIX
FILE Cop
RECEIVFD%
AUGG1 ZUIJ
ST. Lucie County, Permitting
WIND DESIGN REQUIREMENTS_
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION (2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Volt = 186 mph
NOMINAL DESIGN WIND SPEED VaSd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF - N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd= 0.85
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56 Ib/R2
FORCE COEFFICIENT Cf = 1.44 �����®
WIND PRESSURE- S -
P = qh G Cf= 56.80Ib/R2 (ASD) BY
GENERAL NOTES S4.LudeCountf
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED
IN ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
BUILDING CODE SIXTH EDITION (2017).
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR
USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER
SEPARATE CERTIFICATION ON A JOB -SPECIFIC BASIS IN
ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC
LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR
EQUAL TO THE DESIGN PRESSURE "ASD" CAPACITY VALUES
LISTED HEREIN FOR'ANY ASSEMBLY AS SHOWN.:
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO
SPECIFICATIONS STATED HEREIN.
ANCHOR TO PAD SCHEDULE: 4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES
HAVING EQUAL CLEARANCE. A_MINIMUM DISTANCE FROM UNIT
TO PAD EDGE IS SPECIFIED.
5. CALCULATIONS MAD,E'USING LIGHTWEIGHT CONCRETE 125 PCF
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE
ALL VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS
REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS
VERIFIED BY OTHERS.
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT
PART OF THIS DOCUMENT AS SOIL CHARACTERISTICS AND PAD
PLACEMENT VARIES.
8. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED &
INSTALLED BY OTHERS. ALL MECHANICAL SPECIFICATIONS
NOTES: (CLEAR SPACE TONNAGE ETC.) SHALL BE AS PER
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE 9
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED III ANCHOR SCHEDULE.
4. ENSURE.MINIMUM n�PgqCC,{{{{yyGG rrTT�
ANY ADJACEN7$ITdW 9`a"UNTY
S. FOLLOW MANUFAGRjMREVIEW
INSTALLATION INSIS1IGiGN6-�
INSTALL ANCHORS. 10
BLDG:
DATE:
GENERATOR ELE
ATTACHMENT BASE,
VARIES WITH MODEL DATE:
SEE GENERATOR SPECS
PLUMB: 11
3a" SIMPSON TITEN HD,
SEE ANCHOR SCHEOVLE DATE:
2" X3"Af e" GALL. STEEL
DimADD .,.DD.. ,ASHER� KtECH'
CONCRETE PAD
6PSI
X LIGHTWEIGHT
CONCREONCRETE MIX
MASTERFIBER MAC 100
& ROAD MESH
I SUBSTRATE I DESCRIPTION I
CONCRETE: (2)-3/8"0 TITEN HD
(6000 PSI OR EQUIVALENT,
MIN) 2-3/4" FULL EMBED
TO CONCRETE, 3" MIN,
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES: FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2'.
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS
RESPONSIBILITY OF THE CONTRACTOR.
ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL
DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY
CONTRACTOR, et. al. INDEMNIFIES & SAVES HARMLESS THIS
ENGINEER FOR ALL COST '& DAMAGES INCLUDING LEGAL FEES
& APPELLATE FEES RESULTING FROM MATERIAL FABRICATION,
SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES &
FROM DEVIATIONS OF THIS PLAN.
WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
RESPONSIBILITY OF THE INSTALLING CONTRACTOR.
CONTRACTOR SHALL ENSURE THAT ANY REMOVED OR ALTERED
WATERPROOFING MEMBRANE IS RESTORED AFTER
FABRICATION AND INSTALLATION OF STRUCTURE PROPOSED
HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF
THE INSTALLING CONTRACTOR.
THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF
SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD.
CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL
BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING
SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED
BY THE PERMITTING CONTRACTOR.
_
12,
THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY
SPECIFIC PROJECT SITE. INFORMATION CONTAINED HEREIN IS
-
1
BASED ON CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS.
ENGINEERING EXPRESS SHALL NOT BE RESPONSIBLE OR
LIABLE IN ANY WAY FOR ERRONEOUS OR INACCURATE DATA
OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO ILLUSTRATE
DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY
VARY SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS
SPECIFIED HEREIN. WORK SHALL BE FIELD VERIFIED BY
OTHERS PRIORTO CONSTRUCTION. ENGINEERING EXPRESS
I
SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
�-- -�-
REEVALUATE OUR WORK UPON DISCOVERY OF ANY
-2"--!
INACCURATE INFORMATION PRIOR TO MODIFICATION OF
EXISTING FIELD CONDITIONS AND FABRICATION AND
INSTALLATION OF MATERIALS. ALTERATIONS OR ADDITIONS
TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE
OUR CERTIFICATION.
13.
EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL
CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED.
X L. BENNARDO, P.E.
OliANK oL
L BENNARDe, P:E
)46.
W6849
ALID FOR 1 PERMR ON -V�
OLnCE: IF THIS SHEET DOE
OT CONTAIN AN ORIGINAL
IGNATURE & ENGINEER SE
'THERE IS A DIGITAL
IGNATURE ON SHEET 1, THIS
HEET 15 PART OF A WGITAW
IGNED FILE, SHALL REMAIN 11
IGUAL FORMAT,& PRINTED.
OPIES OF THIS DOCUMENT
RE NOT CONSIDERED SIGN
ND SEALED, IF THERE IS NO
IGITAL SIGNATURE ON SHEET
R THIS SHEET DOES NOT
ONTAIN AN ENGINEERS
ORIGINAL SIGNATURE & SEAL