16/20/22 W GUARDIAN° SERIES
SCANNED Residential Standby Generators
BY Air -Cooled Gas Engine
St. Lucie County
INCLUDES:
• True Power- Electrical Technology
• Two Line LCD Multilingual Digital
Evolution" Controller (Engfish/SpanistV
French/Portuguese)
• Two Transfer Switch Options Available:
100 Amp, 16 Circuit Switch or
200 Amp Service Rated Smart Switch.
See Page 5 for Details.
• Electronic Governor
• Standard Wi-Ft" Remote Monitoring
• System Status & Maintenance Interval LED Indicators
• Sound Attenuated Enclosure
• Flexible Fuel Line Connector
• Direct -To -Dirt Composite Mounting Pad
• Natural Gas or LP Gas Operation
• 5 Year Limited Warranty
• * Listed and Labeled by the Southwest Research Institute allowing
installation as close as 18' (457 mm) to a structure.'
'Must be located away from doors, windows, and fresh air
intakes and in accordance with local codes.
hops: Bassets. svm.orrgg/BbrdryiDirecroWfUsledPmducfsl
ccuL clian/ndusfryl973 DoC 204 13204-01-01 Reo9.Pdr
FEATURES
Standby Power Rating
pR,gdr:w ^igyY nl;.i 007037 .-.:::w,nip, ij'a,r.�pFl IGkI".'Ei.14'.
!J,:<kfi;DD70,�5 :'lgx[;:n:R"Pr.L sl Ib k`h'1•J `Ir
6'L r.¢`I 64K,7•0' GOD7033-t <(,i I"
vV 14)',.
:dlnrinl5 'v: Y:Yr)d.1n Gn37N4i..'iiU.:R ininln L�:'3lillri . 22 kW fgl:
CEI D .L us QUIET. —
LISTED
DATE'
Note: cuL certification only applies to unbundled units and units packaged with
limited circuit switches. Units packaged with the Small Switch are UL certified in
FILE"I only.
PIr I
O INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING areal the heart of Generac's O
success in providing the most reliable generators possible. Generac's G-Force engine
lineup ollers added peace of mind and reliability fur when you need it the most. The
G-Force series engines are purpose built and designed to handle the rigors of
extended run limes in high temperatures and extreme operating conditions.
O TRUE POWER" ELECTRICAL TECHNOLOGY: Superior harmonics and sine wave O
form produce less [ban 5%Total Harmonic Distortion for utirity, quality power. This allows
confident operation of sensitive electronic equipment and micro-cNp based appliances,
such as variable speed HVAC systems.
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION:
This state-of-the-art power maximizing regulation system is standard on
all Genera; models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque -matching the surge loads to the engine. Digital
vollage regulation at .I%.
SINGLE SOURCE SERVICE RESPONSE Irom Generac s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
O TEST CRITERIA: O GENERAC TRANSFER SWITCHES: Long file and reliability are
V PROTOTYPE TESTED v NEMA MG1.22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
v' SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY - confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility. -
O MOBILE LINK'" REMOTE MONITORING: FREE with every Guardian Series Home he w G E N E RA C _
standby generator. Allows you to monitor the status of your generator Irom anywhere in t_ <
world using a smarlpbone, tablet- or PC. Easily access Information such as the current � PROMISE
�.
operating status and maintenance alerts. Connect your account to your authorized service .....- ..
dealer for last. friendly and proactive service. With Mobile Link. you are taken care of before
the next power outage.
GENERAC
16/20/22 kW
features and benefits
Engine
•
Genelac G-Farce design
Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cylinder walls and plasma moly
rings helps the engine run cooler, reducing oil consumption resulting in longer engine life.
•
"Spiny-lok" cast iron cylinder walls
Rigid construction and added durability provide long engine life.
•
Electronic ignilion/sparkadvance
These features combine to assure smooth, quick starling every time.
•
Full pressure lubrication system
Pressurized lubrication to all vital bearings means better performance, less maintenance and longer engine
life. Now featuring up to a 2 year/200 hour oil change interval.
•-
Low oil pressure shutdown system
Shutdown protection prevents catastrophic engine damage due to low oil.
•
High temperature shutdown
Prevents damage due to overheating. -
Generator
•
Revolving field
Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature
generator.
•
Skewed stalor
Produces a smooth output waveform for compatibility with electronic equipment.
•
Displaced phase excitation
Maximizes motor starting capability.
•
Automatic voltage regulation
Regulates the output voltage to t1% prevents damaging voltage spikes.
•
UL2200listed
For your safety.
Transfer Switch (if applicable)
•
Fully automatic
Transfers your vital electrical loads to the energized source of power.
•
NEMA 3R
Can be installed inside or outside for maximum flexibility.
•
Remote mounting
Mounts near your existing distribution panel for simple, low-cost installation.
Evolution'" Controls
•
Auto/Manual/Off illuminated buttons
Selects the operating mode and provides easy, al -a -glance status indication in any condition.
•
Two-line LCD multilingual display
Provides homeowners easily visible logs of history, maintenance and events up to 5o occurrences.
•
Sealed, raised buttons
Smooth, weather -resistant user interface for programming and operations.
•
Utility voltagesensing
Constantly monitors utility voltage. setpoints65%dropout, 80%pick-up,of standard voltage.
•
Generator voltage sensing
Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
•
Utility interrupt delay
Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default selling of
five (5) seconds by a qualified dealer.
•
Engine warm-up
Ensures engine is ready to assume the load, selpoinl approximately 5 seconds.
•
Engine cool -down
Allows engine to cool prior to shutdown, selpoinl approximately 1 minute.
•
Programmable exercise
Operates engine to prevent oil seal drying and damage between power outages by running the generator
for 5 minutes every other week. Also offers a selectable setting for weekly or monthly operation providing
flexibility and potentially lower fuel costs to the owner.
•
Smart battery charger
Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Compatible with lead acid and AGM -style batteries.
•
Main line circuit breaker
Prolects generator from overload.
•
'Electronic governor
Maintains constant 60 Hz'frequency. .
Unit
• SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding
winds up to 150 mph. Hinged key locking roof panel for security. Lift -out front for easy access to all routine
maintenance items. Electrostatically applied textured epoxy paint for added durability.
• Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
• Small, compacl, attractive Makes for an easy, eye appealing installation, as close as 18" (457 mm) away from a building.
GENERAL'
16/20/22 kW
features and benefits
Installation System
• 1 it (305 mm) flexible fuel line connector
Absorbs any generator vibration when connected to rigid pipe.
• Direct-lo-dirt composite mounting pad
Complex lattice design prevents settling or sinking of the generator system.
• Integral sediment trap
Prevents particles and moisture from entering the fuel regulator and engine, prolonging engine life.
Remote Monitoring
• Ability to view generator status
Monitor your generator via your smadphone, tablet, or computer at any time via the Mobile Link application for
. _
complete peace of mind _
• Ability to view generator Exercise/Run and Total Hours
Review the generator's complete protection profile for exercise hours and total hours
• Ability to view generator maintenance information
Provides maintenance information for your specific model generator when scheduled maintenance is due
• Monthly report with previous month's activity.
Detailed monthly reports provide historical generator information
• Ability to view generator battery information
Built in battery diagnostics displaying current slate of the battery
• Weather information
Provides detailed local ambient weather conditions for generator location
16/20/22 W
GENERAC
specifications
Generator
Made]
G907035-1, G097035-1,
C007038-1, G007039-1
6007042-2. G007043-2
G007037-1 (16 kffl
(20 kW)
(22 kW)
1W WTurnfConthunrus Power Capaci(y.(LP)
16.000Watbi!.{
:,4,.126,qpQWatts- -
Rated Maximum Continuous Power Capacity (NG)
16.000 Walls'
18,000 watts*
19,500 Watts
]"pq -
- : 240
:24 .
240,
Rated Maximum Continuous Load Current — 240 Volls (LP/NG)
66.7/66.7
83.3/75.0
91.7181.3
Jotil Ii2q6traceDis'larlion s- v
Lesithan5%
_Jess thin 5%
Larks0iapf3%
Main Line Circuit Breaker
70 Amp
96 Amp
100 Amp
A
Number of Rolo'r'poles
2
2
6H:.
Power Factor
1.0
1.0
1.0
s'. .12 V611s, 0 CCA M* Gre 0.36A 9650 CGA Minimll
. _T - §4 _jq[gujrff:or, u ... G QI
Ural Weight (lh(kg)
409/186
4481203
• 4661211
inisi Ps7CLx-,
Scmndpupul in dB(A) at 23 it (7 an) with generator operating at normal load"
6
67
67
i 2311(7`1pr Lh:b��daft@rfq Ti -1mv-sladedeurih senridde" -7, - IS X��
_2121��
",5
Type of Engine
GENERAC G-Force 1000 Sores
CORK, Kiq
2: .ZR ,,
Displacement
999 cc 999 cc 999 cc
10010
Valve Arrangement
Overhead Valve Overhead Valve Overheadvalve
,j �%. - , s z -'.Solid-state.
W
7. . , .. . . .. . . .
A 604 qqlia -
4Q . Ma Q -qt3teV,__qqQlQ- t,
04W . . Ma
Governor System
Electronic Electronic Electronic
V -
Siemer
12 VDC 12 VOC 12 VDC
L61 Ziz
Operstingfrinm
3,600 3.600 3.600
'Nits
228 AQ
�zV..
24(6;fT)�
--- Fu41 Bad
327
6)
IF- Z
I-s T
-04
5fi)
f .4 :j42(190)'(1,477.js
rota.
Note: Fuel pipe must be sized for full load. Required Netpressure to generator fuel inlet at all load ranges-
3.5-7- water column (7-13 man mercury) for natural gas, 10-12' water column (19-22 mm mercury)
for LP gas. for BTU conled, multiply fix/fur x 2500 U) or N x 1000 (NG).
Far Megajoule content, multiply m3lbrx 93.15 (LP) or ml/hr x 37.26 (NG)
Controls
Two -Line Plain Teed Multilingual LCD Display
Simple user interface roi ease of operation.
,Made Buffmis*fl'
-ps—
Utomauc%Slbp_ y
Manual
Start with starter Controls Unit St* on. if utility falls. transfer 10 load takes place.
z
s.topsupiLFp�irii.ieiF6ved..Conholaqd,d.ial &(stilloper4le.
Ready to Run/Mahmenance Messages
Standard
%ininutil-16teftificallon .-:
. , S6hdud
Programmable start delay between 2-1500 seconds
Standard (programmable by dealer only)
Utility Valtage Losia(Relum to Utility Adjustable (Brownout Selling)
FromJ40-171 V/ISD-2151(.-*
Future Set Capable Exorciser/Exercise Set Error Warning
Standard
Runt/Namn/Malntimunce Logs.
50 Events Each
Engine Start Sequence
Cyclic creaking: 16 sac on. 7 rest fell see maximum duration).
Starer Lack -out
Siamir carm6l re-engage until 5 see after engine has stopped.
Smart Battery Charger
Standard
Chargit FardbrMissifill AC Warning
Standard
Law Battery/Battery Problem Protection and Battery Condition indication
Standard
Autocrat Voltage Regulation with Over and Under Voltage PmlecOrm
Standard
Under-Frequency/Overload/Stepper Dvmcumml Protection
Standard
Safety Fused(Fuse Problem Protection
Standard
Automatic Low Oil Pressunatf-figh Oil lemperahoe Shutdown
Standard
OvesciadvOnvarspeed (Q 72 Hz)Apm Sense Loss Shutdown
Standard
High Engine Temperature Shutdown
Standard
Internal Faull/brocomactIffiflng Protection
Standard
Common External Fault Capability
Standard
Field Upgmdable Firmware
Standard
"SoLmd [eletsue WWIfmthe kod a1degenelalw.6mmaIMLSCheneomaxestyes at me gtnesum may cenkro dmenaig -stawny.ApDFcstUeI,x suppionomigew.1" to ftowation
ccalm tic
16/20/22 kW
Limited Circuits Switch Features
• 16 space, 24 circuit, breakers not included,
• Electrically operated, mechanically -held contacts for fast, positive
connections
• Rated for all classes of load,100% equipment rated, both inductive and
resistive.
• 2-pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil design.
• Rated for bath copper and aluminum conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMANL 311 aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
• Multi listed for use with 1° standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexibleand cost effective
install.
Dimensions
Height
width
Depth
H1
H2
Wl
W2
in
26.75
30.1
I
10.5
I 13.5
6.91
mm
679.4
1 764.3
266.7
1 343.0
175.4
wire Ranges
Conductor Lug
Neutral Lug
Ground Lug
1/0-#14
2/0-#14
7/0-#14
Service Rated Smart Switch Features
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages up to four air conditioner loads with no additional
hardware.
• Up to four more large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMs).
• Electrically operated, mechanically -held contacts [or fast, clean connections.
• Rated fat all classes of load,100% equipment rated, bothinductive and resis-
tive.
• 2-pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMML 3R aluminum outdoor enclosure allows for indoor or outdoor mount-
ing flexibility.
Dimensions
200 Amps 1201240, to
Open Transition Service Rated
Height
Width
Depth
Hi
H2
wl
W2
in
26.75
30.1
10.5
13.5
6.91
min
1 679.4
764.3
266.7
343.0
175.4
GENERAC"
switch options
Model
G007036.1 (16kNq
Current Rating (Amps)
100
4ollaAeJleW9lVAC) -
..
120'y240,10
utility Voltage Monitor (Rioul -
-Pick-up
80%
-Dropout
';,:+
65%
Heftirnim tjUlltyl_:''',
'.
•apprbi.�15.'sec
Exercises hi -weekly far 5 minutes'
Standard
Total Circuits Available _
24
•Tdndem Biealrei;Czgahilltles--. ,' ..;",','•3`
-: 8rndemk`
Circuit Breaker Protected
'
Available RMS symmetrical
10,000
Fault Current @ 250 Volts
"Function of Evolution
Controller
Exercise can be set to weekly or monthly
d
tp
�.
N1
Model G007037-1 (15 kMIG007039-1 (20 Will
G007043.2 (22 kW)
•Nu a6+Pu135}: `ci*^' .. ?: a, :25�=` - ,J'•`�`jixyi'
Current Rating (Amps) 200
Voi ge Az�InsNACj. ..r^F,� 1201240, 1$: , , w=7'i
Utility Voltage Monitor (Rxed)-
Pick- up
-Dropout
RetumtoUtRity•
Exercises bi-weekly to; 5 minutes'
Enclosure Type
chiu09iealsr Protected
Lug Range
'Function of Evolution Controller
Exercise can be set to weekly or monthly
80%
65%
approx. 13 sec
Standard
Standard
NEMAAIL 311
22,000
250 MCM - #5
16/20/22 kW
GENERAC
available accessories
.Model# ,; . _Product f �• .
.Deseription
The Wf-Fi enabled LP fuel level monitor provides constant monitoring of the connected LP fuel tank. Mon-
Boring the LP tank's fuel level is an important step in making sure your generator is ready to run during an
G007005-0 Wi-Fi LP Fuel Level Monitor
unexpected power failure. Status alerts are available through a free application 10 notify when your LP tank
is in need of a refill.
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet
G005819-0 26R Wet Cell Battery
cell battery for use with all air-cooled standby product (excluding PowerPact®). _
The pad warmer rests underthe battery:Recommended toruse if the temperature regularly falls below
G007101-o Battery Pad Warmer
0 IF (48 •C). (Not necessary for use with AGM -style batteries).
00 warmer slips directly over the oil fitter. Recommended for use if the temperature regularly falls below 0 IF
G007102-0 Oil Wanner
(-18 •C).
The breather wanner is for use in extreme cold weather applications. For use with Evolution controllers
G007103-1 Breather Wanner
only in climates where heavy icing occurs.
Auxiliary Transfer Switch
. The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load
G005621-0
Contact IQ
you may not need. Not compatible with 50 amp pre -wired switches.
The fascia base wrap snaps together around the bottom of the new air cooled generators. This offers a
Base Wrap it
Fascia BaraK
G007027-0 - Bisque
sleek, contoured appearance as well as offering protection from rodents and insects by covering the li ing
(Standardse
holes located in the base.
tl the generator enclosure is scratched or damaged, it is important to touch up the paint to protect from
G005703-0 - Bisque Paint Kit
future corrosion. The paint kit includes the necessary paint to properly maintain or touch up a generator
'
enclosure.
Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine
G006485-0 Scheduled Maintenance Kit
maintenance on a Generac automatic standby generator.
Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its
Management Module
Smart G006873-0 Smart Ma)
power management capabilities. It provides additional power managementflexiblitynotfoundinany other
(50
power management system.
dimensions & UPCs
Denersions shovmme ao;xo* ale. Rft to insmllmionrnwnl for mot (R neimaons. 00 NOT USE THESE DIMENSIONS FOR INSTALLATION FURPOSES.
SN rem -
} In]
LEFT SIDE VIEW
GENERAC'
Ra.a of
Model
UPC
G007035-1
696471074161
G007036-1
696471074154
G007037-1
696471074178
G007038-1
696471074185
G007039-1
696471074192
G007042-2
696471074208
G007043-2
696471074215
I=rem
085NI
FROM VIEW
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
6M'..r F.n ._.i�:I: nu: .�G IF+x. ...e .... .... .. ..... -.: n,@Ip �n.iL•�,.,n�.•Yc :n�iic ,Ptai,Yi ... ..... ..
Automatic
Transfer Switches
Description .
Service and non -Service rated
Automatic Smart Transfer Switches
100 - 400 Amps, Single Phase
C @us
LISTED
ee --
'CUL only applies to non -service rated switches
Generac Automatic Transfer Switches are designed for use with single phase generators that utilize an Evolution'" or Nexus'"
Controller. The 100, 200, and 400 amp open transition switches are available in single phase in both service equipment rated and
non -service equipment rated configurations. The 150 and 300 amp open transition switches are only available in a service rated
equipment configuration.
Standard Features
Service rated (RXSW) Generac Automatic Transfer Switches are housed in an aluminum NEMA/UL Type 3R enclosure', with
electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for
years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. All
switches are covered by a 5 year limited warranty.
Non -service rated (RXSC) switches are housed in a steel enclosure.
DPM Technology
Through the use of digital power technology (DPM), these switches have the capability to manage up to 4 individual HVAC (24 VAC
controlled) loads with no additional hardware. When used In tandem with Smart Management Modules, up to B more loads can be
managed as well, providing the most installation efficient power management options available.
ISO
100-400 Amps, Single Phase Automatic Smart Transfer Switches
Functions
All liming and sensing functions originate in the generator conlmHer
Utirity voltage drop -out .................................. ...... _.......... ......
Engine warm up delay...
Standby voltage sensor.
Utility voltage pickup.....
Re -transfer time delay...
Engine cool -down rimer
Exerciser ... _._.............
10 second factory set adjustable between 2-1500 seconds by a qualified dealer'
...._............................................:..._....................... - ...... ........ ..... .... 5 seconds
.-.. ................. -.................................... _............... _................ 65% for 5 seconds
The transfer switch can be operated manually without power applied.
'When used in conjunction with units'utlliting Evolution— controls "Adjustable via the controller
Specifications
15 seconds
or 12 minutes adjustable weeklyBi-weekiy/Monthly"
Model
RXSC10OA3
10(SW100A3
RXSWISOA3
RRSC20013
RXSW20OA3
RXSW300A3
RXSG40OA3
RXSW400A3 .
Amps
100
100
150
200
200
300
400
400
Voltage
120/240,10
120/240, io
120/240, to
120/240,10
120/240, to
120240, to
120240, to
120/240,10
Load Transition Type
(Automatic)
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Enclosure Type
NEMAAIL 3R
NEMA(UL 3R
NEMA/UL 3R
NEMA/UL 3R
NEMA41L 311
NEMA/UL 3R
NEMA/UL3R
NENIANL 3R
UL Rating
UUCUL
UL
UL
UUCUL
UL
UL
UUCUL
UL
Withstand Rating
(Amps}
10,000
10.000
22,000
10.000
22,000
22.000
22,000
22,000
Lug Range
110-#14
250 MCM-#6
600 MGM -#4 or 1B-250 MCM
Dimensions
Model
RXSCIGOA3
RXSW10GM
F=1150A3
RXSC200A3
n%SW200A3
WSW300A3
RXSC400A3
R1(3W400A3
Height
HI
17.24/437.9
17241437.9
26.75/679.4
17.24/437.9
26.75/679.4
42.91/1089.9
3125/793.8
291/1069.9
pnhrvn)
H2
201508
20/506
30/762
201508
301762
4811219.2
3W4A
48/1219.2
Wnam
W1
125/311.5
125/317.5
10i/266.7
12$a17.5
10.5266.7
16.69/423.9
19.1814872
I6.69/423.9
(in/min)
W2
14.6ia70.8
14.61370.8
13.5/3429
14.67370.E
13.5/342.9
21.87/554.2
2409.6
21.87(554.2
Depth pnJmm)
7.09/180.1
7.09/1801
6.31160.1
7.09/180.1
6.31160.1
10.06255.5
10.05/255.5
1026255.5
Weight p0471d1U4)
20/9.0T
225/1021
39/17.69
20I9.07
39/17.69
140/63.5
133/60,33
140/63.5
:3w :::•
Y-
OEM
GENERAC' General; Power Systems, Inc. • S45 W29290 HWY. 59. Waukesha, WI53189 • generac.com
02017 G menc Power Symms. Inc. All d4ld5 inerve4. An specifia44na are sublecl 10 change 02mvt w ce. Bulletin 10000013459A 04/24/17
GENERAC°
' 16/20/22 kW
switch options
Limited Circuits Switch Features
Model
G00T036-0(161AN)
_ • 16 space, 24 circuit, breakers not included.
• Electrically operated, mechanically -held contacts forfast, positive
Current Rating (Amps)
voRa9e Aabng NAq)
100
: ;20240 �6 w, s
connections.
M , ,.... : . •.
UUIlryvoltags monitor (Faedt-
-
• Rated for all classes of load,100% equipment rated, both inductive and
-Pak-trp
80%
resistive.
-Oropanl
65%
• 2-pale,250VAC contac[ors.
.:,,
6elum.io''ti�ny�:;?a�;;«;�,'=.:t;:;u:.
• 30 millisecond transfer time.
Fwc=bii kyfar5morutes•t
Standard
• Dual coil design.
• Rated for both copper and aluminum conductors.
• Main contacts are silver plated or sllveralloy to resislwetding and sticking.
• NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
• Multi listed for use with I' standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexible and cost effec-
tive install.
Dimensions
Height
Widlh
Hl
H2
W1
W2
DepN
in
26.75
30.1
10.5
13.5
6.91
min
679.4
764.3
266.7
343.0
175.4
Wire flanges
conductor Lug
Neutral Lug
Ground Lug
110-014
210-#14
2/0-#14
Service Rated Smart Switch Features
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages up to four air conditioner loads with no additional
hardware.
• Up to four more large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMs).
• Electrically operated, mechanically -held contacts far fall, clean connections.
• Rated for all classes 0f coed, 100% equipment rated, both inductive and resis-
live.
• 2-pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• Main contacts are silver plated or silver alloy to resist welding and slicking.
• NEMAIUL 311 aluminum outdoor enclosure at lows for indoor or outdoor mount-
ing flexibility.
Dimensions
200 Amps 120240. 1e
Open Transition Service Rated
Height
Moth
till
Vyt
W2
Depth
in
26.75
30.1
10.5
13.5
6.91
mm
679.4
1 764.3
1 266.7
343.0
175.4
Total Circuits Available
24
eieakei5.'yyf:>><''':�
yYanUdm .
-`:736_;}_nae�`ss_tsi.::h=fit
Circuit erealar Protected
Available RMS Symmetrical
10,000
Fault Currant p 250 Volts
'Function of Evolution Controller
Exercise can be set to weekly or monthly
Darin
Model G007037-0 (16 kMI0007039-0120 Wituf
^:�--^�a•�_.- G007043-0 (22 kW)
current Rating (Amps) 200
L1 GT•'. L PFrp^..Y.'Y•
0110ryVoltage Monitor (Fixed)'
-NOV eo%
-OmPoul 65%
rPeGmrgzu all
,Exercisesbl-weeklylor5minmas' Standard
ni)�f1,5Rd`;ii=v.�i f:'r.' �R?,--c�=.....�.r.r,r~•�', �sa":::;5-�'''::i`
Enclosure Type NEMAAIL 3R
'Cu"aid
Lug Range•-,.ma.�..,� - 250 MCM-#6
'Function of Evolution Controller
Exercise can be set to weekly of monthly
General Information
Specifications
Generator
Model
9 kW
11 kW
16 kW
20 kW
22 kW
Rated Voltage
240
Rated Maximum Load
-
Current (Amps) at Rated
37.5
45.3
66.6
83.3
91.7
Voltage with LP'
Main Line CircuitBreaker.40
Amp
50 Amp
70 Amp
100 Amp
100 Amp
(Generator Disconnect)
Phase
1
Rated AC Frequency
60 Hz
Battery Requirement
12 volts, Group 26R-540CCA Minimum or Group 35AGM-650CCA Minimum
(Field supplied)
(see Replacement Parts)
Enclosure
Aluminum
Weight (lbslkilos)
340/154
346/158
I
409/186
448/203
465/211
(without battery)
I
"
This unit is tested in accordance to UL 2200 standards with an operating temperature of -20'F (-29 'C) to 122 °F
Normal Operating Range
(50 °C). For areas where temperatures fall below 32 °F (0 °C) a cold weather kit is recommended. When operated
above 77'F (25 °C) there may be a decrease in engine power. See Engine.
These generators are rated in accordance with UL 2200. Safety Standard for Stationary Engine Generator Assemblies, and GSA-C22.2 No. 100-04
Standard for Motors and Generators.
' Natural Gas ratings will depend on specific fuel joules/BTU content. Typical demtes are between 10-20% off the LP gas rating.
Engine
Model
9 kW
11 kW
16/20/22 kW
Type of Engine
GH-426
GTH-530
GT-999
Number of Cylinders
. 1
2
2
Displacement
426 cc
.530 cc
999 cc
Cylinder Block
Aluminum wl cast iron sleeve
Recommended Spark Plug
See Replacement Parts
Spark Plug Gap
0.020 in (0.508 mm)
0.030 in (0.76 mm)
0.040 in (1.02 mm)
Valve Clearance
0.002-0.004 in
(0.05-0.1 mm)
0.002-0.004 in
(0.05-0.1 mm)
0.002-0.004 in
(0.05-0.1 mm)
Starter
12 VDC
Oil Capacity Including Filler
Approx. 1.1 qt (1.03 L)
Approx. 1.7 qt (1.6 L)
Approx. 1.9 qt (1.8 L)
Recommended Oil Filter
See Replacement Parts
Recommended Air Filter
See Replacement Parts
Engine power is subject to and limitad by such factors as fuel BTU/loules, amhient temperature and altitude. Engine power decreases about 3.5% for
each 1000 ft (304.3 m) above sea level, and also will decrease about 1 % for each 10 °F (6'C) above 60 °F (15 °C) ambient temperature.
The specification sheet for your generator was included in the documentation provided with the unit at the time of
purchase. For additional copies, consul( your local Independent Authorized Service Dealer (IASD) for your specific
generator model.
Ovvner's Manual for 60 Hz Air -Cooled Generators