HomeMy WebLinkAboutSCREEN PLANSGeneral Notes and Specifications: 1. Contractor shall field verify all dimensions before construction and shall notify engineer of discrepancies for immediate consideration. 2. Concrete shall be minimum 28 day compressive strength of f'c=2500 psi, and be in accordance with the requirements of ACI 318. Reinforcing steel shall have a min. yield strength of 40,000 psi (grade 40) and be provided with cover in accordance with ACI 318. 3. All dimensions are provided by contractor, 00 Kim & Associates, LLC have made interpretations where necessary. 4. The following structures are designed to be attached to block and wood frame structures of adequate structural capacity. The contractor shall verify that the host structure is in good condition and of sufficient strength to hold the proposed addition. If there Is a question about the host structure, the owner (at his own expense) shall hire an architect or engineer to verify host structure capacity. S. Screen density shall be a maximum of 18 x 14 x 0.013" mesh. Aluminum shall be 7005-T53 Alloy, 6005-TS Alloy; for secondary components 6063-T6, Alloy based on industry standard shapes, thicknesses, and tolerances unless otherwise noted. 6. Unless otherwise noted, SMB shall be stitched with #100/4" SMS at 24"o.c., top and bottom. 7. Connections using screw bosses shall have minimum (4)-#10x2" per connection unless shown otherwise. 8. Unless otherwise shown, screws shall have minimum edge distance and center -to -center distances as shown in this table. C-1022 Low Carbon Steel SMS & Self -Drilling (TEK) Screws (Industry Standard Screws) Screw Nominal Screw Diameter (in) Minimum Edge Distance Minimum Center to Center Distance #10 0.188 IS" #12 0.219 )/;' '/; #1411/4") 0.250 Y2" '/;' 9. Structure has been designed to meet the 6" Edition FBC 12011 FBC). Project is sited where the ultimate design wind speed, Vult, is 150 mph (3-sec gust) for risk category I buildings and other structures. Exposure B. Design pressures are from Table 2002.4. 2011 FBC reduced by 0.88 for screen mesh factor, 0.6 for allowable stress design (ASO). 10. Concrete anchors may be "Large Diameter Tapcons" (LTDs), Tapcon concrete screws, Simpson Strong -Tie Anchors or Titian Screws or approved equal. 1.14' BY 2• LONG 11. Aluminum roof pans shall be of aluminum alloy 3105-1114 or 3105-H28. Composite panel skins shall be of aluminum alloy 3105-1115 ANGLE. EACH SIDE (TYP.) or 3105-1125. 12. Screen enclosure structure shall meet Section 454.2.17 Residential Swimming Barrier Requirements and the screen enclosure per 454.2.17.1,11. if enclosing a pool. zv / -(5) Q12x3/4• S.M.S. Ix5x14' ANGLE 6' LONG la O.B. ATfACHED_.TO BEAM W/ (TYP, a EACH BEAM) (2)-flOn- S.M.S. IWO SCREW BOSS L_ (2) Y'mx3' I.G. a EACH ANGLE 0)-1/_4'xW S.S. THRU-BOLT W/ )''NUT AND WASHER IRFACH SIDE OF BEAM COMBINED/TOTAL FACIA TO BE /1 O 24-O.C. HIN 1ACTUAL WOOD DEPTH, .pit O.B.O. TO TO SUPER CUTTER SPP. OR WESTER RED CEDAR qI STRUCTURAL MADE 2 (4) (12x3/4- S.M.S. (U Y'Ox2' I.G. LAG SCREW a 24' O.C. ENTIRE LENGTH OF GUTTER ROOF BEMs SECURE FASCIA TO EACH RAFTER TAIL (MT OR SLOPED) — �« V/ (1) %'mx4' LONG PAN HEAD LAG SCREWS BEFORE ATTACHING SUPER GUTTER I (1) Y<'mx2' LG. LAG SCREWS (4) f12x3/4• s.N.S (OR B•IF--------�\ (TYP. 8 EACH BEAM) ViC (1)#I2x2• SX.S a 12• ao (MAX) BETWEEN BEAMS EACH LEG. ANG SICK CONTINUOUS51 ]• SUPER GUTTER MIN..Q090' THICK W/ (1) BEFORE j10x3/4• 0 2' D.C. TO CONSTRUCTION (4) 114A7 S.M.S.. 2 SCREWS EACH LEG (TYP.) HOLLOW POST — SPACE E EQUALLY 00C AAA BEAM STITCHING SCREWS (SEE TABLE) a 24' O.C. e) JAR t j pORL ROOFBEAM CONNECTION DETAIL 2x CIRT/CWVR RAIL (SEE PLAN) MIN. (4) /10x2• LONG S.M.S. IWO SCREW BOSSES (1YP. ALTERNATVE) T.M.B. POST CHAIR RAIL / GIRT TO POST CONNECTION DETAIL 2x PURUN (WLY BE SLOPED (2) @1Ux4• S.M.S. THRU. 2x3 OR FLAT) EAVE RAIL INTO PURLIN SCREW � BOSSES USE /OdV4• SN.S. O O.0 TO CONNECTTO O.B. TO 2x3. la O.B. FASTENED TO COLUMN/POST PURUN FASTENED TO COLUMN/POST 1INIA• S.M.S. INTO SCREW BOSSES WnMI (4) f12x1• S.N.S. (EACH LEG) (EACH END, TYP.) USING )6• THICK FLAT BAR BENT :RUN (6063-T6 ALLOY) �WLUMN/POsr NIL SCREWS SIDEWALL POST / COLUMN TO PURLIN CONNECTION DETAIL (EACH SIDE OF BEAM) Y DR EQUAL, 1/8' THICKNESS �r � (2) f14x15' S.M.S., EACH LEG AND 4) 114A' S.M.S. CHANNEL TO BEAM 8) SCREW TOTAL 2. 1 x 2 1/8 x 1 x 2" LG. (TYP. ALTERNATIVE) 204.045 EAVERNL ATTACHED BEAMS WITH (3)-f10x2• S.M! INTO SCREW BOSS. A USE /10x1)Q B.M.S. 0 24' D.C. - TO CONNECT TO la O.B. TO W. EACH SIDE. EACH SIDE COLUMN TO MIN. (4) /10x2• LONG S.M.S. IWO SCREW BOSSES (1YP. ALTERNATIVE) BEAM STITCHING 0 24' O.C. (TYP. TOP AND BOTTOM OF SMB SEE TABLE FOR SIZES) Ix14' BY 2• LONG ANGLE, EACH SIDE C".) (2) /141Jj• S.M.S.. EACH LEG (4) TOTAL (TYP.) PURLIN TO BEAM CONNECTION ,Q✓ )S' MIN., 3 Y' MAX. C-C SPACING OF FASTENERS (TYP.) ➢ISTANCE (TYP.MIR BM �� 3AEBY NNED CONNECTION DETAIL DO KIM & ASSOCIATES, LLC CONSULTING STRUCTURAL ENGINEERS PO Box 10039 Tampa, FL 33679 Tel: (813) 374-0321 ISSUED J h W U ❑ c W C) U m C 0 N Z U W N W C Z Q CL O 0) DO YEON KIM, P.E. FLA. REG. NUMBER 49497 DO 110 f $SOCIATES, LLC YY//// CC((gq�gp�gp26B97 PO X 10039 Tampa, FL 33679 Drawing No. - 060811 SHEET 1 OF 2 3' MIN. PURLIN SUPPORT COWMN/POST 2.2x1/8' x 2' LG. ANGLE W/ (4) /12x3/4- S.M.S (EACH SIDE) 34'0 CONCRETE ANCHOR W/2%" EMBEDMENT INTO STRUCTURAL CONCRETE (EACH SLOE) S.M.S WNH MIN. 4F EDGE`ST DISTANCE 1 A, SIDEWALL COLUMN TO CONCRETE CONNECTION EfAIL—"9 ,B®SEE PUN FOR SIZE 1.2 ¢B. FASTENED TO COME SECTION WITH 014x1Y4' S.M.S.4 F4 D.C. , 2x'A- ANGLE 2- LONG (EACH W/(2) p14rK' S.M.S. TO POS h 3/8b N.D. GALV. DIP. Got W/ 2 1/2- MIN. EMBEDMENT \1 C Ya- ANGLE, EACH SIDE (TYP.) S.M.S.-+...� EIIGE DISTANCE CONCRETE MC14OR W�2%' EMBEDMENT INTO CONCRETE s STRUCTLRA (TYP., SEE NOTE 10) 11x2' O.B. SOLE PLATE 9jr Y 0.2YI CONCRETE iru SCREW ANCHOR O 24- O.� ;F6 NW AND 9- FROM POST 0W.) 1x2 O.B. SOLE PLATE (TYP.) 3' MIN. Y' ANGLE. EACH 510E (M.) j:'0 CONCRETE ANCHOR - W/2)6' EMBEDMENT INTO STRUCTURAL CONCRETE (M.. )EE NOTE 10) �1%2' O.B. SOLE PLATE PLATE •e?`'� � _ 2xSx3fi' ANGLE (2' LONG) V/ (2)-014 ///---TENS INTO TOP OF 2x3 CAVE RAIL AND (2)- 014 TEKS MID THE FRONT OF THE CORNER POST I] K I M BT \ J & ASSOCIATES, LLC PURLIN ��~'-'• CONSULTING r) 1xz o.e. tOP FRAME STRUCTURAL ENGINEERS 2x2A' ANGLE CLIP, CUT AT k'1 ix3 O.B. FASTENED TO CORNER CORNER POST A 45' (4/-) ANGLE AND• ATTACHED TO THE SCREEN ROOF�(3 SECTION WITH /10x2' S.M.S. W/ i§' DW WASHER O 1B' O.C. BEAM MAY BEN M BEAM WIRI ONE ft) Y.'0 TNRU- BOLT, WITH FEND EERR WASHER. �) 1. O.B. SIDE WALL CORNER UPRIGHT PO Box 10039 Tampa, FL 33679 OR SLOPED ATTACHED TO BENT OR FAVE RAL.'• DIAGONAL BRACING SHALL NOT BE Ve Tel: (813) 374-0321 O ATTACHED TO ROOF N LINS. ' 2.L0.093 SPACE �: Rat evJO Description (SEE PLAN) / l ELEVATION VIEW QB ojj ISSUED '^ POST / COLUMN PLAN -TYPICAL DIAGONALCORNER ROOF 0 BRACE -CONNECTION O UPRIGHT DETAIL A n THICK BRICK PAVERS '.4BTAR ON TOP OF FOOTER O.B. 501E PLATE 3 t'- Y- 0x5- CONCRETE SCREWS Y 24- D.C. 2%' MIN. CONC. BEAM SUPPORT, DYP.), 1)j' CONC. EMBEDMENT (MIN.) ENBEOMFM MP.) COLUMN/POSF�- 2x2xl/S' x 2' LG,IANGLE W/ (4) /12.3/4' SM.s TYPCIAL FRONT VIEW OF POST TO (EACH SIDE) U, t FOUNDATION CONNECTION WITH PAVERS POST 4' NOMINAL CONCRETE 4AB (2500 PM. MIN.) W/6x6x10/10 W.W.M. OR FIBER REINFORCED [POLYPROPYLENE FIBER - 1.5 POUND (MIN.)PER C.Y.) 4e. eb G e e •4 \\ `UNDISTUREED SOIL OR COMPACTED CRUSHED UMEROCK (90K PROCTOR) MIN. (1)-85 REBAR CONTINUOUS, SAUCE MUST OVERLAP 20' MIN. 3- COVER (TYP.) B'MINJ FOUNDATION/SLAB DETAIL 2500 PSI MIN. CONCRETE STRENGTH APPROXIMATE GR ., a _ I J II ea' = COMPACTED OR _ F Q. a UNDISTURBED SOIL/SAND — W I G (1)-#5 REM, CONTINUOUS L) 0 3' MIN. CONC. COVER, 36- MIN. — LU Of LAP SPLICE 0 Z) 0 (n c O 12' MIN. N J z U W MIN. CONTINUOUS PERIMETER FOOTING 4) W c Z Of O EL In � � J Q W (Vie a U O �t'Q ° G� o% k ®f ®�-- --DO YEON KIM, P.E. FLA. REG. NUMBER 49497 IV g��� OGG DO KI ANOCIATES, LLC 2668 7 0039 Tampa, FL 33879 g 2L.(y Drawing No. - 060811 SHEET 2OF2