HomeMy WebLinkAboutGENERATOR CONCRETE PADs,
AMERICAST GENERATOR CONCRETE PAD r�(LC9°'i'0 a XL. BENNARO�P.E.
`SF, Q1O PE 00
y
r
GENERATOR
I- \ ��
w \p
i°4,0
PAD
THICKNESS
?PO `ENGtN
ISOMETRIC VIEW
PAD DIMENSIONS: GENERATOR TABLE:
GENERATOR
GENERATOR UNIT BY
SEPARATE SU
BMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT
REQUIRED)
54" LENGTH --1
PLAN VIEW
CONCRETE PAD
ROAD MESH
MASTERFIBER-�
MAC - 100 3" MIN �
�-' A" MIN
-
GROUND�
- - �J17� 2" MIN
501, 54"--:
(ON -GRADE APPLICATIONS ONLY)
AUP3��"
�'.ImP1•S 5
•aTentoy UCIZRIZ
FEOTAxam-crzw ucEs�aswamsarm
HVHZ ORNON-HVHZ
COUNTY
RISK
EXPOSURE(EXP)
RISK EXPOSURE (EXP)
RISK
EXPOSURE(EXP
C
D
II C
I D
III, IV -
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH 39.09 Psf
147.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
139.95 Psf
1170 MPH 139.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH 41.43 Psf
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LEN
HEIGHT
WEIGHT
-
ALLOWABLEGTH
PRESSURE
COMMENTS
Generac 005871 & 005883
30 KW
25.00 "
48.00 "
29 00'
3871bs
41.43 Psf
EXP C 175 MPH & 0156 MPH
Generac 005872 & 005884
14 KW
25.00"
48.00"
29.00"'
439lbs
47.44 Psf
EXP C 186 MPH & D L56 MPH
Generac 6459, 6461, 6462
16 KW
25.00"
48.00"
29.00"
513lbs
47.44 Psf
Generac 006721
16 KW
25.00"
48.00"
29.00"
4481bs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00"
48.00"
29.00"
455lbs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00"
48.00"
29.00"
421lbs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00"
48.00"
29.00"
451lbs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00"
48.00"
29.00"
Sl61hs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00"
48.00"
29.00"
526lbs
47.44 Psf
Kohler 14RES&20RE5
14-20 KW
26.00"
48.00"
29.00"
500lbs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00"
39.40"
39.00"
5401bS
39.09 Psf
EXP C 170 MPH & D L56 MPH
GE 040382 ISKW
15 KW
33.00"
48.00"
30.50"
4841hs
43.83 Psf
EXP C180 MPH &D 156 MPH
GE 04037817KW
17 KW
33.00"
48.00"
30.50"
484lbs
43.83 Psf
GE 40330GE&40331GE
20 KW
33.00"
49.00"
30.50"
600lbs
43.83 Psf
Briggs& Stratton 040243-0
10 KW
31.00"
32.00"
34.00"
4301bS
43.83 Psf
Briggs & Stratton 040302.2
12 KW
33.75"
50.00"
31.60"
507lbs
41A3 Psf
EXP C 175 MPH & D -56 MPH
Briggs &Stratton 040303-1
15 KW
33.75"
49.00"
31.60"
562lbs
43.83 Psf
EXP C 190 MPH & D 156 MPH
Briggs & Stratton 040304.1
18 KW
33.75"
49.00"
31.60"
568lbs
44.00 Psf
Briggs& Stratton 040305-1
20 KW
33.75"
49.00"
31.60"
570lbs
44.00 Psf
Generac 7035, 7036, 7037
1 16 KW
25.00"
48.00"
29.00"
406lbs
47.44 Psf
EXPC 186 MPH&D 156 MPH
GeneracOW038&007039
20 KW
25.00"
48.00"
29.00"
448lbs
47.44 Psf
Generac 007042&7043
22 KW
25.00"
48.00"
29.00"
466lbs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
VI/ (4) #10 SS 316 SELF -DRILLING
OE SCREWS
r- �- _ T_ _ TO GENERATOR
I
GENERATOR
LD .U. (SEE CONCRETE PAD
_ = SCHEDULE FOR
It DIMENSIONS & WEIGHT
REQUIRED)
4� i n�
I
--32" WIDTH f-54" LENGTH
SIDE VIEW
FRONT VIEW
FILE COPY
I SUBSTRATE DESCRIPTION I
(2)-3/8"0 TITEN HD
OR EQUIVALENT,
2-3/4" FULL EMBED
O CONCRETE, 3" MIT
EDGE DISTANCE, 6"
IIN. SPACING TO AN'
ADJACENT ANCHOR.
DATE: ND�_
1. ANCHOR QUANTITY PER LONG SIDE
MECHz UUW=FNT AND EDGE. DISTANCE
EXCLUDES FINISHES, IF
DATE: APPI iren LE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE.MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
GENERATOR
L9 SON CTE
SEE ANCHNCHS
OR SCHEDULEDULE
I 2'z3'z3,'a" GALV. STEEL
\ I WASHER RUBBER VIBRATIONAD
(SEE GENERATOR SPECSV-, 3s"THICK GALVANIZE
\ \
WASHER& RUBBER / \ I�
VIBRATION PAD/ I Z
� CONCRETE PAD -
6,000 PSI
CONCRETE PAD . ' \r- X CONCRETE MIX `
6,000 PSI I
LIGHTWEIGHT FIAST-eRFIBER MAC 100 -/
CONCRETE MIX & ROAD MESH
NOTES: FOAM CORE
1. Y DISTANCE DEPEND Oil GENERATOR BASE LENGTH, NO LESS THAN 2'.
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
a
WIND DESIGN REQUIREMENTS_
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION (2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED VDIt = 196 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = WA
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd= 0.85
ENCLOSURE CATEGORY = N/A HEIGHT H - AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh - 77.56 Ib/ft2
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE:
P = qh G Cf = 56.80 Ib/R2 (ASD)
GENERAL NOTES
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED
IN ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
BUILDING CODE SIXTH EDITION (2017).
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR
USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER
SEPARATE CERTIFICATION ON A JOB -SPECIFIC BASIS IN
ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC
LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR
EQUAL TO THE DESIGN PRESSURE "ASD" CAPACITY VALUES
LISTED HEREIN FOR ANY ASSEMBLY AS SHOWN.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO
SPECIFICATIONS STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES
HAVING EQUAL CLEARANCE. A MINIMUM DISTANCE FROM UNIT
TO PAD EDGE IS SPECIFIED.
S. CALCULATIONS MADE'USING LIGHTWEIGHT CONCRETE 125 PCF
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE
ALL VEGETATION, STUMPS, ROOTS,. AND FOREIGN MATERIALS
REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS
VERIFIED BY OTHERS.
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT
PART OF THIS DOCUMENT AS SOIL CHARACTERISTICS AND PAD
PLACEMENT VARIES.
S. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED &
INSTALLED BY OTHERS. ALL MECHANICAL SPECIFICATIONS
(CLEAR SPACE, TONNAGE, ETC.) SHALL BE AS PER
MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS
RESPONSIBILITY OF THE, CONTRACTOR.
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL
DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY
CONTRACTOR, et. al. INDEMNIFIES & SAVES HARMLESS THIS
ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES
& APPELLATE FEES RESULTIN
G FROM MATERIAL FABRICATION,
SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES &
FROM DEVIATIONS OF THIS PLAN.
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
RESPONSIBILITY OF THE INSTALLING CONTRACTOR.
CONTRACTOR SHALL ENSURE THAT ANY REMOVED OR ALTERED
WATERPROOFING MEMBRANE IS RESTORED AFTER
FABRICATION AND INSTALLATION OF STRUCTURE PROPOSED
HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF
THE INSTALLING CONTRACTOR.
11: THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF
SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD.
CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL
BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING
SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED
BY THE PERMITTING CONTRACTOR.
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY
SPECIFIC PROJECT SITE. INFORMATION CONTAINED HEREIN IS
- - BASED ON CONTRACTOR-SUPPLIED:DATA AND MEASUREMENTS.
ENGINEERING EXPRESS SHALL NOT BE HELD RESPONSIBLE OR
LIABLE IN ANY WAY FOR ERRONEOUS OR INACCURATE DATA
OR MEASUREMENTS. DIMENSIONS ARE SHOWN TOdLLUSTRATE
DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY
I v VARY SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS
SPECIFIED HEREIN. WORK SHALL BE FIELD VERIFIED BY
OTHERS PRIOR TO CONSTRUCTION. ENGINEERING EXPRESS
SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
��� -i
REEVALUATE OUR WORK UPON DISCOVERY OF ANY
INACCURATE INFORMATION PRIORTO MODIFICATION OF
SCANNED
EXISTING FIELD CONDITIONS AND FABRICATION AND
INSTALLATION OF MATERIALS. ALTERATIONS OR ADDITIONS
i�V
TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE
OUR CERTIFICATION.
St. Lucie Countv
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL
CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED,
01; 04J20V
U1NK L BENNARDO, F.E.
146549
SLID FOR I� PERMS ITOMLy Uj.
OTICE: IF THIS SHEET DDE
CT CONTAIN AN ORIGINAL
IGNATURE & ENGINEER SE
'THERE IS A DIGITAL
IGNATURE ON SHEET 1, THIS
1EET IS PART OF A DIGTrI
IGNED FILE, SHALLREMAIN If
WIFACFORMAT, 9 PRINTED
OPIES OF THIS DOCUMENT
RE NOT CONSIDERED SIGN
ND SEALED. IF THERE IS NO
IGITAL SIGNATURE ON SHEET
R THIS SHEET DOES NOT
DWAIN AN ENGMEERS
U 0 N
Z �v
_ IT 0
a wMmus
�(jJ �r-" 2;wU A
W� V�wSaNm
WW LLU) XWu
Z O =P02x
QW ---Z O. t-
r>Q'C'z wx
c�a 5a W ow�o
OL m yu:4 .
W W x m i w w
ON J^w.ZU
Ibj/
O wP0
E w 7
w Z
U)�axw
OLL
1 17-3961.1 1