HomeMy WebLinkAboutEVALUATION REPORTEXTERIOR RESEARCH ut DESIGN,9503
SCANNED
Certificate of Authorization #9503
N STREET, UNIT #13
TRINITY ERD SCANNED 353 CHRISTIAOXFORD, CT 6478
w�aa
BY PHONE: (203) 262-9245
EVALUATION REPORT
st- Cuc)e rainfv FAX: (203) 262-9243
East Coast Metals, Inc. Evaluation Report E10240.08.08-R4
2301 West 8 Lane FL5374-R4
Hialeah, FL 33010 Date of Issuance: 09/03/20D8
Revision 4:03/17/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for
use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described
herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code sections noted herein.
DESCRIPTION: East Coast Metals Channel Metals
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity IERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinityJERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPEchON: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Robert J.M. Nieminen, P.E. oT b .�=s. merammdereal appearmgwas aethnrheae,Rpnnweminen.
J, �' P.E. on 03/17/2015. This does not rem as an electmnlall, signed
Florida Registration No. 59166, Florida OCA ANE1983 c.:%S� E;.•h 9 %aj�p ��sss dominant. Signed, sealed hardmples haw been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest In any company manufacturing or
distributing products it evaluates.
2. Trinity) ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
�l I RJNIIY J ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Roofing Accessories that are an Integral Part of the Roofing System
Compliance Statement: East Coast Metals Channel Metals, as produced by East Coast Metals, have demonstrated compliance
with the fallowing sections of the Florida Building Code through testing in accordance with the following Standards. Compliance
is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.3.7
Installation, non-HVHZ
FRSA/TRI April 2012 (04-12)
2012
1518.8.1
Installation, HVHZ
RAS 118,119 & 120
1995
1523.6.5.2.2
Static Uplift Resistance
TAS 101
1995
1711.2.1
Static Uplift Resistance
SBCCI SSTD 11
1997
3. REFERENCES:
Enfilly
Examination
Reference
Date
ERD (TST6049)
Static Uplift Resistance
E42730.08.13
08/23/2013
ERD (TST6049)
Static Uplift Resistance
ECM-SC6795.12.14-1
02/27/2015
ERD (TST6049)
Static Uplift Resistance
ECM-SC6795.12.14-2
02/27/2015
Florida TEC (TST7393)
TAS 101
530-628R
10/27/2010
FRI(TST5878)
TAS 101
ECM-001-02-01
09/21/2001
PRI (TST5878)
TAS 101
ECM-003-02-01
06/13/2008
PRI (TST5878)
TAS 101
ECM-004-02-01
06/13/2008
PRI(TST5878)
TAS 101
ECM-005-02-01
O6/13/2008
PRI (TST5878)
TAS 101
ECM-006-02-01
06/13/2008
PRI (TSTS878)
TAS 101
ECM-007-02-01
06/13/2008
PRI (TST5878)
TAS 101
ECM-008-02-01
O6/13/2008
Florida Building Code
Attachment Requirements
FRSA/TRI April 2012 (04-12)
04/2012
Florida Building Code -HVHZ
Attachment Requirements
RAS 118,119 and 120
1995
East Coast Metals
Metal Quality
Mill Certifications
Various
Architectural Testing (QUA1944)
Quality Control
Participation Letter
Exp. 12/31/2018
4. PRODUCT DESCRIPTION:
4.1 Hip & Ridge Channel Metal: Pre -formed metal channel
designed for use as a hip and ridge base to which roof tiles
are bonded in FBC Approved roof tile adhesive.
Hip & Ridge Channel Metal is available in 119-3/8-inch L
3/8-inch) length by 2.5, 3, 3.5, 4, 5, 6 or 7-inch (± 3/8-inch)
heights with 1.5-inch L 1/16-inch) deck -flanges.
Exterior Research and Design, U.C. Evaluation Report E3024D.08.08-R4
CMIfimte of Authorization a9503 FL5374-R4
Revision 4: 03/17/2015
Page 2 of 7
�1 TRINITY ERD
4.2 Trim Lock Channel Metal: Pre -formed metal channel
designed for use as a hip and ridge base to which roof tiles
are bonded in FBC Approved roof tile adhesive. Trim Lock
Channel Metal is characterized by its profiled and
perforated upper horizontal flange designed to receive
and allow for interlock with the overlying tile adhesive.
Trim Lock Channel Metal is available in 119-3/8-inch (±
3/8") length by 3, 3.5, 4, 5 or 6-inch I+ 3/8-inch) heights
with 1.5-inch L 1/16-inch) deck -flanges.
4.2 Trim Lock Plus Channel Metal: Pre -formed metal channel
designed for use as a hip and ridge base to which roof tiles
are bonded in FBC Approved roof tile adhesive. Trim Lock
Plus Channel Metal is characterized by its profiled and
perforated upper horizontal flange designed to receive
and allow for interlock with the overlying tile adhesive
and its perforated deck flanges, designed for installation
atop the roof underlayment via placement in FBC
Approved roof tile adhesive, which flows -through and
interlocks with the underlying adhesive.
Trim Lock Plus Channel Metal is available In 119-3/8-inch
�+3/8") length by 3, 3.5, 4, 5 or 6-inch (± 3/8-inch) heights
with 1.5-inch (±1/16-inch) deck -flanges.
4.4 East Coast Metals Channel Metals are fabricated of the following metals:
➢ Galvanized Steel: Min. 0.019 ± 0.002-inch, ASTM A653 (G-90), min. 33 KSI.
➢ Galvalume Steel: Min. 0.019±0.002-inch, ASTM A792, AZ55, min. 35 KSI.
➢ Aluminum: Min. 0.032±0.002-inch, ASTM B209, 3003-H14, min. 21 KSI.
➢ Stainless Steel: Min. 0.019 ± 0.002-Inch, ASTM A240/A480, T304, min. 35 KSI.
_ S. LimrrnoNs:
5.1 This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in anyway, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically forthat purpose.
Exterior Research and Design, I.I.C. Evaluation Report E10240.08.08-R4
Certificate of Authorization n9503 FL5374-R4
Revision 4: 03/17/2015
Page 3 of 7
�t TRINITY I ERD
5.2 FOR HVHZIURISDICTIONS:
5.2.1 For Hip & Ridge Channel Metal or Trim Lock Channel Metal, refer to FBC RAS 118, Drawing 13, Detail 3; RAS 119,
Drawing 12, Detail 3; or RAS 120, Drawing 15, Detail 3. For Trim Lock Plus Channel Metal, refer to the installation
instructions herein.
5.2.2 For HVHZ jurisdictions, installations of Hip & Ridge Channel Metal and Trim Lock are prescriptive by RAS 118, 119 and
120, and the data in Tables 1A and 1B is supplemental to these prescriptive allowances.
Installations of Trim Lock Plus are limited to projects having a required moment resistance (Mr) or uplift resistance (F,j,
as determined in accordance with RAS 127, not greater than the following values.
Refer to the tile adhesive manufacturer's published Installation instructions for adhesive paddy placement details.
➢ "INDEPENDENT" paddy placement means each individual tile is bonded to the Channel Metal in its own, single
foam paddy; tile head laps are not bonded. This method Is limited to 2-part tile adhesives. Allowable
performance data below for "INDEPENDENT" paddy placement already has a 2 to 1 margin of safety applied to
ultimate performance.
➢ "INTERDEPENDENT" paddy placement means each individual tile is bonded to the Channel Metal in a foam paddy,
and a second foam paddy bonds the tile head lap, or two tiles are bonded to the Channel Metal using a single
foam paddy. Allowable performance data below for "INTERDEPENDENT" paddy placement already has a 4 to 1
margin of safety applied to ultimate performance.
TABLE IA:. PERFORMANCE LIMITATIONS/HVHZ, INDEPENDENT PADDY PLACEMENT
_ (2 To 1 MARGIN OFSAFETYALREADYAPPNED)
Hill Ridge Metal
Tile
Adhesive
Allowable Performance
Moment Based
Uplift Based
Design
Metal Type
Type
Placement
M,(ft-lbf)
F'(Ibf)
Hip &Ridge
galvanized
clay or
3M'"2-Component Foam
Independent
p
127
169
Channel Metal
concrete
Roof Tile Adhesive AH-160
Trim Lock
galvanized, Galvalume•,
clay or
3M"' 2-Component Foam
Independent
171
159
aluminum or stainless steel
concrete
Roof Tile Adhesive AH-160
Trim Lock Plus
galvanized, Galvalume•,
clay or
31VI'" 2-Component Foam
Independent
177
165
aluminum or stainless steel
concrete
Roof Tile Adhesive AH-160
TABLE IB: PERFORMANCE LIMITATIONS -HVHZ, INTERDEPENDENT PADDY PLACEMENT _
(4 TO I MARGIN OFSAFETYALREADYAPPOED/ _
Hip/Ridge Metal
Tile
Adhesive
Allowable Performance
Moment Based
Uplift Based
Design
Metal Type
Type
Placement
M,(ft-ibff
F'(Ibf)
Trim Lock or Trim
galvanized, Galvalume°,
clay or
3M-2-Component Foam
Interdependent
95
88
Lock Plus
aluminum or stainless steel
concrete
Roof Tile Adhesive AH-160
Trim Lock
galvanized, Galvalume®,
clayor
3M"' Roof Tile Adhesive
Interdependent
99
94
stainless steel
concrete
RTA-1
Trim Lock
aluminum
clay or
3M"' Foam Roof Tile
Interdependent
90
84
concrete
Adhesive RTA-1
Trim Lock Plus
galvanized, Galvalume®,
clayor
3M" Foam RoofTlle
Interdependent
90
84
aluminum or stainless steel
concrete
Adhesive RTA-1
Trim Lock
galvanized, Galvalume° or
clay or
TILE BOND'" Roof Tile
Interdependent
123
117
stainless steel
concrete
Adhesive
Trim Lock
aluminum
clay or
TILE BOND- Roof Tile
Interdependent
79
73
concrete
Adhesive
Trim Lock Plus
galvanized, Galvalume®,
clay or
TILE BOND" Roof Tile
Interdependent
79
73
aluminum or stainless steel
Concrete
Adhesive
galvanized, Galvalume® or
clay or
Touch'n Seal StormBond
Interdependent
146
139
Trim Lock
stainless steel
concrete
Roof Tile Adhesive
Trim Lock
Aluminum
clay or
Touch'n Seal StormBond
Interdependent
58
54
concrete
Roof Tile Adhesive
galvanized, Galvalume°,
clay or
Touch 'in Seal StormBond
Interdependent
58
54
Trim Lock Plus
aluminum or stainless steel
concrete
Roof Tile Adhesive
Exterior Research and Design, U.C. Evaluation Report E30240.08.08-R4
Cert(JTcate ofAuthafkadon A9303 FL5374-R4
Revision 4: 03/17/2015
Page 4 of 7
�I I �NIN ERD
5.3 FOR NON-HVHZ JURISDICTIONS:
5.3.1 For Hip & Ridge Channel Metal or Trim Lock Channel Metal, refer to FRSA/TRI April 2012 (04-12). For Trim Lock Plus
Channel Metal, refer to the installation instructions herein
5.3.2 For non-HVHZ, installations are limited to projects having hip and ridge design pressure requirements, determined in
accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the following values. Refer to the tile
adhesive manufacturers published installation instructions for adhesive paddy placement details.
D "INDEPENDENT" paddy placement means each individual tile is bonded to the Channel Metal in its own, single
foam paddy; tile head laps are not bonded. This method is limited to 2-part tile adhesives. This method is limited
to 2-part tile adhesives. Allowable performance data below for "INDEPENDENT" paddy placement already has a 2
to 1 margin of safety applied to ultimate performance.
D "INTERDEPENDENT" paddy placement means each individual tile is bonded to the Channel Metal In a foam paddy,
and a second foam paddy bonds the tile head lap, or two tiles are bonded to the Channel Metal using a single
foam paddy. Allowable performance data below for "INTERDEPENDENT" paddy placement already has a 4 to 1
margin of safety applied to ultimate performance.
TABLE 2A:. PERFORMANCE LIMITATIONS —NON-HVHZ, INDEPENDENT PADDY PLACEMENT `
(2 TO MARGIN OFSAFETYADIEADYAP➢LIED)
Hip/Ridge Metal
Tile
Adhesive
Allowable Uplift
(Psf)
Design
Metal Type
Type
Placement
Hip &Ridge
galvanized
clay or
3M-2-Component Foam Roof
Independent
169
Channel Metal
concrete
Tile Adhesive AH-160
Trim Lock
galvanized, Galvalume•, aluminum or
clay or
3M- 2-Component Foam Roof
Independent
173
stainless steel
concrete
Tile Adhesive AH-160
Trim Lock Plus
galvanized, Galvalume•, aluminum or
clay or
3M-2-Component Foam Roof
Independent
178
stainless steel
concrete
Tile Adhesive AH-160
TABLE$B: PERFORMANCE LIMITATIONS-NON•HVHZ, INTERDEPENDENTPADDY PLACEMENT
_. (4701 MARGW OFSAFETYALREADYAP➢UED)
Hip/Ridge Metal
'rile
Adhesive
Allowable Uplift
IPsfl
Design
Metal Type
Type
Placement
Trim Lock or Trim
galvanized, Galvalume•, aluminum or
clay or
3M-2-Component Foam Roof
Lock Plus
stainless steel
concrete
Tile Adhesive AH-160
Interdependent
98
Trim Lock
galvanized, Galvalume• or stainless
clay or
3M- Foam Roof Tile Adhesive
Interdependent
110
steel
concrete
RTA-1
Trim Lock
aluminum
clay or
3M- Foam Roof Tile Adhesive
Interdependent
93
concrete
RTA-1
Trim Lock Plus
galvanized, Galvalume®, aluminum or
clay or
3M- Foam Roof Tile Adhesive
Interdependent
93
stainless steel
concrete
RTA-1
Trim Lock
galvanized, Galvalume® or stainless
clay or
TILE BOND- Roof Tile Adhesive
Interdependent
152
steel
concrete
Trim Lock
aluminum
clay or
TILE BOND" Roof Tile Adhesive
Interdependent
82
concrete
Trim Lock Plus
galvanized, Galvalume°, aluminum or
clay or
TILE BOND'" Roof Tile Adhesive
Interdependent
82
stainless steel
concrete
Trim Lock
galvanized, Galvalume• or stainless
dayor
Touch'n Seal Starmliond Roof
steel
concrete
Tile Adhesive
Interdependent
148
Trim Lock
Aluminum
clay or
Touch'n Seal Storm Bond Roof
Interdependent
61
concrete
Tile Adhesive
Trim Lack Plus
galvanized, Galvalume•, aluminum or
clay or
Touch'n Seal StormBond Roof
Interdependent
61
stainless steel
concrete
Tile Adhesive
Exterior Research and Design, L1C. Evaluation Report E30240.08.08-R4
Certlfwte ofAuthorhadon x9503 FL5374-R4
Revision 4: 03/17/2015
Page 5 of 7
�l I KINITY ERD
6. INSTALLATION:
6.1 The roof deck shall be minimum 15/32-inch plywood (non-HVHZ) or minimum 19/32-inch plywood (HVHZ) attached in
accordance with FBC Chapter 23 to the satisfaction of the AHJ.
6.2 Hip & Ridge Channel Metal and Trim Lock Channel Metal shall be installed using min. 11 ga. x 1Y.-inch long x 3/8-inch
head diameter galvanized annular ring shank nails spaced 6-inch o.c. along both deck -flanges. Fasteners shall be
positioned''/. -inch from the outside edge of each deck -flange, set in a bed plastic roof cement. For FBC HVHZ, refer to
FBC RAS 118, Drawing 13, Detail 3; RAS 119, Drawing 12, Detail 3; or RAS 120, Drawing 15, Detail 3.
6.3 Trim Lock Plus Channel Metal shall be installed atop the Approved roof underlayment In continuous 2-inch wide ribbons
of tile adhesive centered beneath each 1.5-Inch wide deck flange. Place the Trim Lock Plus Channel Metal Into the wet
adhesive and allow it to set-up prior to installation of roof tiles.
View of Polyset AH160 Placement for Trim Lock Plus Channel Metal Installation
6.3.1 It is critical that the bond between the Trim Lock Plus Channel Metal, the tile adhesive and the underlayment is not
disturbed prior to or during placement of the ridge tiles.
6.3.2 Approved underlayments are the codified '30/90' system or other FBC Approved roof underlayments listing approved
use of the subject tile adhesive.
Exterior Research and Design, LLC. Evaluation Report E10Z40.08.08-R4
Cer#Amte afAuthariradon #9503 FL5374.R4
Revision 4: 03/17/2015
Page 6 of 7
�, TRINITY ERD
6.4 Tile shall be installed atop the Channel Metal in accordance with the tile adhesive manufacturers Approved, published
installation instructions, subject to the limitations outlined in Section 5 herein. The exposed edges shall be packed and
pointed with Approved mortar or weather blocking adhesive in accordance with FRSA/TRI April 2012 (04-12) or RAS
118, RAS 119, RAS 120 requirements.
Hip / Ridge Tile
Tile Adhesive
Trim Lock Plus
Mortar or Weather Block
Adhesive
Tile Adhesive
View of Trim Lock Plus Channel Metal Installation after Weather Blocked
6.4.1 Channel Metal shall be free of dust, debris, oils or other bond -breaking substance prior to placement of adhesive.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
S. MANUFACTURING PLANTS: -
Contact the named CIA entity for manufacturingfacilities covered by F.A.C. Rule 61G20-3 CIA requirements.
9. QUALITY ASSURANCE ENTITY:
Architectural Testing, Inc.—QUA1844; (717) 764-7700
END OF EVALUATION REPORT -
Exterior Research and Design, U.C. Evaluation Report E10240.08.08-R4
Certll lmte o)Authorirodon A9503 FL5374-R4
Revision 4: 03/17/2015
Page 7 of 7