EVALUATION REPORT
Certificate of Authorization No. 29824
17520 Edinburgh Drive
SCANNED Tampa, FL33647
BY (813)480-3421
Lucie County
FLORIDA BUILDING CODE, 6nr EDITION (2017)
Manufacturer. OWENS CORNING ROOFING
AND ASPHALT LLC Issued October 11, 2017
1 Owens Coming Parkway
Toledo, OH 43657
(800)438-7465
www.owenscoming.com
Manufacturing Location: Brentwood, NH
Houston, TX
Quality Assurance: UL LLC (QUA9625)
SCOPE
Category: Roofing
Subcategory: Undedayments
Code Sections: 1504.3.1, 1507.1.1
Properties: Physical properties
REFERENCES
Enti
Report No.
Standard
Year
PRI Construction
Materials Technologies (TST5878)
NEI-039-02-01
ASTM D 1970
2015
PRI Construction
Materials Technologies (TS75878)
NEI-042-02-01REV2
ASTM D 1970
2015
PRI Construction
Materials Technologies (TST5878)
NEI-045-02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST5878)
NEI-045-02-01
ASTM G 155
2005a
PRI Construction
Materials Technologies (17ST5878)
NEI-053-02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST5878)
NEI-053-02-01
ASTM G 155
2005a
PRI Construction
Materials Technologies (TST5878)
NEI-093-02-02
ASTM.D 1970
2015
PRI Construction
Materials Technologies (TST5878)
OCF-213-02-01
ASTM D 1623
2009
PRI Construction
Materials Technologies (TST5878)
OCF-237-02-01
UL 1897
2012
PRI Construction
Materials Technologies (TST5878)
OCF-252-02-01
ASTM D 4798
2001
PRI Construction
Materials Technologies (TST5878)
OCF-252-02-01
ASTM D 1970
2015
PRI Construction
Materials Technologies (TST5878)
OCF-253-02-02
ASTM D 1970
2015
PRI Construction
Materials Technologies (TST5878)
OGF-272-02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST5878)
OCF-296-02-02
[CC -ES AC 188'
2012
PRI Construction
Materials Technologies (TST5878)
OCF-297-02-01.1
ICC-ES AC 48
ASTM D 1970
2012
2015
PRI Construction
Materials Technologies (TST5878)
OCF-318-02-01
ASTM D 197o
2015
PRI Construction
Materials Technologies (TST5878)
OCF-320.02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST5878)
OCF-320-02-01
ASTM G 155
2005a
PRI Construction
Materials Technologies (TST5878)
OCF-321-02.01
ASTM D 1623
2009
PRI Construction
Materials Technologies (TST5878)
OCF.322-02-01
UL 1897
2012
PRI Construction
Materials Technologies (TST5878)
OCF-355-02-01
UL 1897
2012
'Determined to be equivalent to ASTM D 226-09. Type I
and II
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
Specifically addressed herein.
P: CREEK OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLock® Self -Sealing Ice & Water Barriers
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION AND LIMITS OF USE
WeatherLock@ G WeatherLock@ G is an ASTM D 1970 self-adhesive undedayment constructed from SBS
(Brentwood, NH) modified asphalt, a fiberglass mat reinforcement and surfaced with granules. The
product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.7-ft.
WeatherLock@ G is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roofing coverings. Exposure on theroofdeck shall be limited to a
maximum 30 days.
WeatherLOck@ Mat
WeatherLock@ Mat is an ASTM D 1970 self-adhesive underlayment constructed from
(Brentwood, NH or
SBS modified asphalt with a fiberglass mat reinforcement The product is supplied in 1-
Houston, 7))
sq. rolls with nominal dimensions of 3-11 x 33.3-ft and 2 sq. rolls with nominal dimensions
of 3-ft x66.7-ft.
WeatherLock@ Mat is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roof coverings. Exposure on the roof deck shall be limited to a
maximum 30 days.
WeatherLock® Metal
WeatherLock@ Metal is an ASTM D 1970 self-adhesive undedayment constructed from
(Brentwood, NH)
SBS modified asphalt with a fiberglass mat reinforcement and plastic film surface. The
product is supplied in 2.0 sq. rolls with nominal dimensions of 3-ft x 66.7-ft.
WeatherLock® Metal is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roof coverings. Exposure on the roof deck shall be limited to a
maximum 90 days.
Weatherl-ockS
WeatherLock@ Specialty Tile & Metal is. an ASTM D 1970 self-adhesive undedayment
Specialty Tile & Metal
constructed from SBS modified asphalt and surfaced with a non -woven polyester fabric.
(Brentwood, NH or
The product Is supplied in 2.14 sq. rolls with nominal dimensions of 3-ft x 71.3-ft.
Houston, TX)
WeatherLock@ Specialty Tile & Metal is permitted to be used as prescribed in FBC
Section 1507.1.1. WeatherLock® Specialty Tile & Metal is permitted to be used with
adhered clay or concrete file roofing using either ICP Adhesives Polyset AH-160 (ICP
Adhesives and Sealants, Inc.) or TILE BONDTM Roof Tile Adhesive (The Dow Chemical
Company). Exposure on the roof deck shall be limited to a maximum 90 days.
The maximum roof slope shall be 6:12 when used with day or concrete file installations
without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles
shall not be stacked greater 10 tiles per stack.
WeatherLock® G (High
WeatherLock@ G (High Tear) is a self -adhered, undedayment used as an alternative to
Tear)
ASTM'D 226, Type I or Type.11 roofing felt and ASTM D 1970 self -adhering polymer
(Houston, TX)
modified bitumen undedayment. The underlayment is composed of SBS modified
asphalt with a fiberglass mat internal reinforcement and is surfaced with granules. The
product is supplied with a nominal thickness of 50 mils in 1.95-sq rolls with nominal
dimensions of 3-ft x 65-ft.
WeatherLock® G (High Tear) is permitted to be used as prescribed in FBC Section
1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be
limited to a maximum 30 days.
Technical Services, LLC of any product changes or quality assurance changes throughout the duration forwhich this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
PRODUCT APPLICATION
OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLoek® Self -Sealing lee & Water Barriers
Min. Roof Slope: 2:12 in accordance with the FBC
Application: All undedayments shall be Installed in accordance with the FBC.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All
fasteners in the deck shall be checked for protmslon and corrected prior to underayment
application. Prior to beginning Installation, the underfayment shall be unrolled and
allowed to relax fora minimum of 3-5 minutes.
The underlayment shall be installed with the release backer removed and pressed firmly
into place to ensure complete contact with the deck. The undedayment shall be installed
with the roll length parallel to the eave, starting at the save, and with minimum 3' side
laps and minimum 6" end laps staggered min. 6-ft.from preceding course. Additionally, if
applying WeatherLock® Specialty Tile & Metal, end laps shall be primed with ASTM D
41 primer or sealed with asphalt roof cement a minimum of 34 inches across the width
of the lap.
It is permissible to back nail the underfayment 12-inches on -center as needed (nails shall
be installed perpendicular to deck with the nail heads gush to the top surface of the
undedayment). Additionally, WeatherLock@ Specialty Tile & Metal shall be back nailed
when installed on roof slopes greater than 3:12.
Min. Application 40°F; Contact the manufacturer when installing at temperatures below the minimum
Temperature: application temperature.
RESISTANCE
The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9
Underiayment System No 1 — Weatherl-ock Specialty Tile & Metal Only
Roof Deck: Min. 15132-inch CDX plywood attached to wood supports spaced a maximum 24" o.c.
Undedayment: Weatherl-ock® Specialty Tile & Metal shall be applied in accordance with
manufacturer's installation instructions to the fastened deck and backnailed along the
selvage with minimum 12ga., 1-1/4-inch galvanized ring shank roofing nails through
optionally primed, 32ga. x 1-5/8-inch H tin caps spaced 12" o.c. The applied
undedayment shall be rolled with a minimum 751b steel roller immediately following
application.
Maximum Design -142.5 psf
Pressure:
ray r r r-m r Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule61G20.3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
GENERAL LIMITATIONS
OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLock® Self -Sealing Ice & Water Barriers
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturers published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction.
5) The space under the deck area shall be property ventilated In accordance with the FBC requirements.
6) All side lap seams shall be installed to shed water from the deck.
7) The underlayment may be used as described in other current FBC product approval documents.
8) Design wind load pressures shall be determined for components and cladding in accordance with FBC
1609.
9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind
load pressures for components and cladding.
10) Maximum Design Pressures for a given underlayment shall meet or exceed the design wind loads
determined for the roof assembly.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E, have demonstrated compliance with the Florida Building
Code (P Edition (2017) as evidenced In the referenced documents submitted by the named manufacturer.
ill
J�P�Y . R �rPA/,,,i
t.
No 74021
. STATE OF : <tr2
0T�%SA,4 O R 1 � r �\� �
�O'4'/ONA�tt ,`%
..........
2017.10.1
09:06:29
04'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have; nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
i cos evaluation report is provided for State of Florida product approval under Rule 61 G20S. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
TRINITY I ERQ
EVALUATION REPORT
uwens corning
One Owens Corning Parkway
Toledo, OH 43659
(740)404-7829
EXTERIOR RESEARCH & DESIGN, LLC.
SCANNED Certificate of Authorization Jl9503
353 CHRISTIAN STREET, UNIT #13
BY OXFORD, CT 06478
St. Lucie County (203) 262-9245
Evaluation Report 037940.02.12-R8
FL10674-11113
Date of Issuance: 02/06/2012
Revision 8: 10/09/2017
SCOPE:
This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted• has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1 / R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinityiERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words 'Trinity( ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. an 10/09/2017. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD Is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY i ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Pro a
Standard
Year
1507.2.5, R905.2.4.
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2011
3. REFERENCES:
Entity
Examination
Reference
Date
UL LLC(CER9626)
Physicals & Wind Resistance
File R2453, Vol.3
02/15/2007
UL LLC (CER9626)
Physicals & Wind Resistance
20120516-112453
05/16/2012
UL LLC (TST9628)
Physical Properties
06CA20263
04/18/2006
UL LLC (TST9628)
Wind Resistance
11CA34308
02/18/2012
UL LLC (TST9628)
Physicals & Wind Resistance
4786093137
02/01/2014
UL LLC (TST9628)
Wind Resistance
4786126532
D2/10/2014
UL LLC (TST9628)
Physical Properties
Classification letter
02/13/2014
UL LLC (TST9628)
Physical Properties
Classification letter
10/02/2015
Miami -Dade (CER1592)
FBC HVHZ Compliance
Varlous NOAs
Various
UL LLC (QUA9625)
Quality Control
Service Confirmation
Exp. 05/16/2020
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme
are fiberglass reinforced,
3-tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced, 4-tab asphalt roof shingles.
4.1.3 Devonshire"" are fiberglass reinforced, 5-tab asphalt roof shingles.
4.1.4 Duration., TruDefinition Duration*, Duration
Premium Cool, TruDefinition'
Duration Designer Color
Collection, TruDefinition Oakridge, Oakridge
and WeatherGuard HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip & Ridge Shingles:
4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and DuraRidge' Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles.
4.3 Accessary Starter Strips:
4.3.1 Starter Strip Shingle, Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-118
Cer Tuvte ofAuthodaflon M03 e EDITION (2017) FaC NON-HVHZ EVALUATION FL10674-R13
Owens Coming Asphalt Roof Shingles Revision B: 10/09/2017
Page 2 of 8
'V I KINITi j ERD
5_4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable
for use in all Wind zones up to Vaad = 150 mph (Van = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F,, indicating the
shingles are acceptable for use in all wind zones up to Va:d =150 mph (Val,= 194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 614320-3.
6. INSTALLATION:
6_1 Underlavment:
6.1.1 Under)ayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval, or be Locally Approved per Rule 6162D-3, per FBC 1507.2.3,1507.2.4 or R905.2.3.
6_2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five (5) nails per shingle.
➢ WeatherGuard HP shingles require minimum six (6) nails per shingle.
➢ Devonshire'" shingles require minimum six (6) nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and instaflation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing — Starter Strip Shingle and Starter Strip Plus:
Fenwdetleymern Deck
Seg•adhered
weathedAdre
undadapment
eDrip—
9
De a*
a'
We lacated
2 Themeava
InstallGst
Starter SNy
Sell•sedin aa0wsive
shin®k IN
painioaalongene
`.
it moored
Starter Strip shhNleovedwags eaves and rakes W 4r
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-RS
cexljlcate OfAuthoruation 99503 file E0rnON 12017)FHC NON-HVHZ EVALUATION FL30674-R13
Owens Coming Asphalt Roof Shingles Revision 8: 10/09/2017
Page 3 of 8
6.2.6 Minimum Nailing — UassicO&Supreme:
N�OM GrNs High 1rYind pars
Aye pore vfeMov dotourrs Am* vf�ntw Mmo
t
S°Eaposurn
£ipovfrfdo
6.2.7 Minimum Nailing — Berkshire®:
P
Standard Fastening Pattern
\l TRINITY I R
iE
Nontut Etontoed or Aron pam
Wind Aron High Wind do� y
Any pen vl000po norrruha Am" viant" fuaryo
T t' 1• • • y t•
I
B NW Expo .
apuvlcfdn
Mansard or Steep Slope Fastening Pattern
6-Nail Fastening Pattern
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R8
Celtf)?G ofAutherhotion 995a3 6'o EDITION (2017) FBC NON-HVHZ EVALUATION FL70674-R33
Owens Coming Asphalt Roof shingles Revision 8: 10/09/2017
Page 4 of 8
6.2.8 Minimum Nailing—Devonshireo:
n
MIS` exposure
Fiposici6nde5.573pu1g 9ealud les81 M
UhiLaddn del sdlador
Dianciare 6-Nail Fastening Pattern
\ 'I RINITY ! ERD
-------------------
Nails
e _r
:a
Tmt"5 otsd Asphaft Roof Ctment
Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing — Duration®, TruDeNnitionO Duration, Duration® Premium Cool & TruDefinition"
Duration Designer Color Collection:
4-W Fastening Pattern
T ee.x®e,mma...,amn
Standard Fastening Pattern
o-rvao rascenmg raaern
Faate"M SPopn GHndxr Tnxn 21:12
btnmOrm•eMwtlm�
e�0.ryµe
1
rw r W�mbP•xmaq r+n""r
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R8
Cerdficote o/Authorimtbn 89SOS 6'"EDITION (2017)FBC NON-HVHI EVALUATION FL10674-R13
Owens Coming Asphalt Roof Shingles Revision 8: 10/09/2017
Page 5 of 9
6.2.1 Minimum Nailing—TruOefinition OakridgeO, Oakridge®:
4 Nail Pattam
Espana con 4 divas
1. r
or
SSWExppsum
?a➢,a4e'mh6vf6pdg
Naffs 66A}'Esposom
Cuvos F.grisrrldnde`66/BP,4g
Standard Fastening Pattern
\! I RININ i ERD
6Nall Pmam
Esqueina con 6davos
s'
r
4—t�
fr 12'
# tail
Ir+: ,
6SW ExImum
C6im
5Sir Expwm
E+r *Wddn do E6/0pdg.
Emosktln de 66J6pdg.
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing— WeatherGuard® HP:
a
6-Nail Fastening Pattern
oft VKDW
Xti.. nj S
d��iiri4drn
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-Ra
Certijkote oJAuthamorion 09503 6rx EDITION (2017) FBC NON-HVHZ EVALUATION FL10674R13
Owens Coming Asphalt Roof shingles Revision 8:10/09/2017
Page 6 of 8
'QRINITY j ERD
6_3 Hio & Ridge Shingles:
63.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard HP Hip and Ridge Shingles
and ProEdge Hip & Ridge Shingles shall comply with the Owens Corning current published instructions,
using four (4) nails per shingle. Installation of DuraRidge^ Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the use of hand -sealing for
wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing— Berkshiree Hip & Ridge and High Ridge:
f—. � tl Md
6.3.4 Minimum Nailing — WeatherGuard® HP Hip and Ridge:
P"
Exterior Research and Design, U.C.
CWWWte ofAvthorfmdon 99503 eEDITION (2017)F0C NON-HVH2 EVALUATION
..Owens Coming Asphalt Roof Shingles
Evaluation Report 037940.02.12-R8
FL10674-R13
Revision 8:10109/2017
Page 7 of 8
6.3.5 Minimum Nailing - ProEdge Hip & Ridge Shingles:
Pmvaiting
Wand- Direction suinn su p
�' e•Exposure
•• riiji#
A Into Ph'
�GEf3� 'I
"3?i�e Fxatemn wRh
' Roca Cmumt •
-OFF` ap'".,,
TRINITY t ERD
Standard .--11•�
Fastening
Pattem {
T+1 r� �� I•-T
12• + Sedans
7'h 8, F� r
6.3.6 Minimum Nailing—DuraRidgeTM Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named CIA entity for information on which plants produce products covered by Florida Rule 9N-3 CIA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625; (631) 546-2458; Kanchi.Agrawala-Dokania@ul.com
- END OF EVALUATION REPORT -