EVALUATION REPORT FLORIDA BUILDING CODE, C EDITION (2017)
Manufacturer: TAMKO BUILDING PRODUCTS 220 West 4°i Street Issued September 25, 2017
-- -- --- — - -- Joplin; MO 64801
(417)624-6644
Manufacturing Plants: Joplin, MO
Phillipsburg, KS
Frederick MD
Dallas, TX R E t,q I EW F D FOR
Tuscaloosa, AL CODE 4.sb1"���'`!- DANCE
Quality Assurance: UL LLC (OUA9625) �., �}- p p�abgl' �l t� ®p,�
v 0 . 16l�ICIE Ce.iUNTY
SCOPE
y;'ct-'ti,9
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1504.1.1, 1507.2.5, 1507.2.7.1, 1523.6:5.1
Properties: Physical properties, Wind Resistance, Wind Driven Rain
Entity
Report No.
Standard
Year
PRI Construction Materials Technologies (TST5878)
TAP-043-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-051-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-054-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-114-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-117-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-130-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-131-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-165-02-01
TAS 100
1995
PRI Constmchon Materials Technologies (TST5878)
TAP-280-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-303-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5876)
TAP-307-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-314-02-01 Rev 2
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-315-02-01
ASTM D 6381
2008(2013)a1
PRI Construction Materiels Technologies (TST5878)
TAP-317-02-01
TAS 100
1995
UL LLC (TST9628)
02NK9507
ASTM D 3161
2016
UL LLC (TST9628)
04NK24366
ASTM D 3462
2010A
UL LLC (TST9628)
05NK28006
ASTM D 6381
2008(2013)el
UL 2390
UL LLC (iST9828)
06NK03898
ASTM D 7158
ASTM D 3161
2011
2016
UL LLC (TST9628)
08CA59132
ASTM D 3462
ASTM D 3161
2010A
2016
UL LLC (TST9628)
09NK07896
ASTM D 3161
2016
UL LLC (TST9628)
10CA50498
ASTM D 3462
ASTM D 3462
2010A
2010A
UL LLC (TST9628)
IOCA64882
ASTM D 3161
2016
UL LLC (TST9628)
11 NK14014
ASTM D 3161
2016
UL LLC (TST9628)
12CA24551
ASTM D 3462
ASTM D 3161
2010A
2016
UL LLC (TST9628)
4786110543
ASTM D 6381
2008(2013)e1
UL LLC (TST9628)
4787043752
ASTM D 3161
2016
UL LLC (TST9628)
4787148748
ASTM D 7158
2011
ASTM D 3161
2016
CREEK Technical Services LLC (ANEi1669)
TBP15001.3
ASTM D 3462
Calculations
2010A
2017
TBP15001.4
FL78355-R4
Page 1 of 11
This evaluation report Is provided for State of Florida product approval under Rule 61G20-3.
The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality
assurance changes throughout the duration for which
this report is valid.
This evalue6on report does not express nor imply warranty, Installation, recommended use, or other product
attributes that are not
specifically addressed herein,
• A CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION
Elite GlassSeal®
12-1/4' If 36', ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick, Joplin &
asphalt shingle with fiberglass mat waled on both sides with asphalt and surfaced with
Tuscaloosa)
ceramic granules complying with ASTM D 3462.
Glass -Seal
12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick &
asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa)
ceramic granules complying with ASTM D 3462.
Glass -Seal
12-1/4' x 36", ASTM D 7158, Class H self-sealing, 3-tab asphalt shingle with fiberglass
(Joplin)
mat coated on both sides with asphalt and surfaced with ceramic granules complying
with ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Heritage®
(Dallas, Frederick,
13-1/4" If 39-318", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Joplin, Phillipsburg &
complying with ASTM D 3462.
Tuscaloosa)
Heritage® Premium
(Dallas, Frederick,
13-1/4' x 39-3/8, ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Phillipsburg &
complying with ASTM D 3462.
Tuscaloosa)
Heritage® Premium
12' x 36", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Frederick)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage® Vintage®
17-1/2' x 40", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Phillipsburg)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage® Woodgate
(Dallas & Frederick)
13-1/4' x 39-3/8, ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
reinforced, laminated architectural asphalt shingle surfaced vrith mineral granules
complying with ASTM D 3462.
Heritage®Woodgate
(Frederick)
12' x 36-3/8', ASTM D 3161, Class F fiberglass reinforced, laminated architectural
asphalt shingle surfaced with mineral granules complying with ASTM D 3462. Shingles
shall be used in the non-HVHZ only.
Hip and Ridge Shingles
12-1/4' x 12", ASTM D 3161. Class F fiberglass reinforced, hip and ridge asphalt
(Frederick & Joplin)
shingle surfaced with mineral granules complying with ASTM D 3462.
Vintage® Hip and Ridge
12" x 12', ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle
(Phillipsburg)
surfaced with mineral granules complying with ASTM D 3462.
TBPI5001A FL18355-R4 Page 2 or 11
This evaluation report is provided for State of Florida praducl approval antler Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
ruCREEK
TECHNICAL SERVICES, LLC
INSTALLATION
Elite GlassSeal® Basic Wind Speed (VmJ:
(Frederick, Joplin & Basic Wind Speed (V„e)
Tuscalcosa) Deck (HVHZ):
8
Glass -Seal —
(Frederick, Joplin (Non-
HVHZ) & Tuscaloosa) Deck (Non-HVHZ):
Underlayment
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ)
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new —construction;- -Min.-15/32—in. .plywood- .existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturers application instructions when installing
shingles at slopes greater than 21:12,
Installed with 5-1/8 inch exposure in accordance with RAS
115 and manufacturers published installation instructions.
Shingles shall be attached using T Nail Pattern" detailed
below.
Installed with 5-1/8-inch exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either'4 Nail
Pattern or "6 Nail Pattern" detailed below.
W
Figure 1. Elite Glass -Seal & Glass -Sea]
4 Nail Fattem (Non-HVHZ only)
7/8"
i-1/8"
Figure 2. Elite Glass -Seat & Glass -Seal
6 Nail Pattern
TBP15001A FL18355-R4 Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Heritage@
Basic Wind Speed (Volt):
(Dallas, Frederick, Joplin,
Basic Wind Speed (Vero):
Phillipsburg & Tuscaloosa)
Deck (HVHZ):
8
Heritage® Premium
(Dallas, Frederick
—8Phillipsburg & Tuscaloosa)--
Deck,(Non-HVHZ):
Heritage@ Woodgate
(Dallas &Frederick)
Underlayment
Min. slope:
Installation (HVHZ):
Installation (Nan-HVHZ):
U
6-1
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in—pplywood or wood plank for --
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBG requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturers application instructions when installing
shingles at slopes greater than 21:12.
Installed with 5-6/8 in. exposure in accordance with RAS
115 and manufacturers published installation instructions.
Shingles shall be attached using '6 Nail Pattern" detailed
below.
Installed with 5-5/8 in. exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either '4 Nail
Patlem' or "6 Nail Pattem" detailed below.
NAIL ZON E
BOND
EXPOSU RE 5-5/9'
1 r' h-- 12-1 /2" —►I'— 12-3/8" -+12-1 /2'r - I --1 "
Figure 3. Heritage@, Heritage@ Premium, and Heritage@ Woodgate (Dallas)
4 Nail Pattern (non-HVHZ only)
ZONE
BOND
EXPOSURE 5-6V
Figure 4. Heritage@ & Heritage@ Premium
6 Nail Pattern
TBP15001A
This evaluation report Is provided for State c
Technical Services, LLC of any product char
This evaluation report does not express nor
specRcally addressed herein.
1`1-18355�R4 Page 4 of I I
ct approval under Rule 61G20-3. The manufacturer shall notify CREEK
assurance changes throughout the duration for which this report is valid.
, installation, recommended use, or other product athibutes that are not
N
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
NAIL ZONE/
ASTENERS4 COMMON BOND
fi-VB° EXPOSURE 55 Sir
1=-� �i-1n:�a-1n+►Iri.a/a^�i-1nr►Ir7.1n>'r� �1^
Figure S. Heritage®Woodgate
6 Nail Pattern
I! I ! ®Common Band
I FASTENERS !'
l} e t
�R ZR : IS
39.3f8" I —
Figure 6. Heritage®, Heritage® Premium, 8 Heritage® Woodgate
Alternate 6 Nail Pattern
PAINT
7-7/8°
6-1/8°
ACCEPTABLE
FASTENER LOCATION
DO NOT FASTEN
'ALONG EDGE OF
COMMON BOND
ZONE
-%,..� PREFERRED
FASTENER
LOCATION
Figure 7. Heritage® (Tuscaloosa)
Expanded Nail Zone
Nail patterns from Figures 3, 4, and 6 may be placed in the nail zone as described above
TSP1500IA FL18355-R4 Page 5 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply miranly, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Heritage® Premium Basic Wind Speed (V,):
(Frederick) Basic Wind Speed (V„,)
Deck (HVHZ):
Deck (Non-HVHZ):
Undedayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ)
TAMKO BUILDING PRODUCT:
Asphalt Shingle:
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed -min. 15/32-lmppplywood-orwood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12. .
Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattem" detailed below.
NAIL ZONFJ
COMMONBOND
5°
1° �11"-►�-- 12°�--1°
Figure 8. HeritageS Premium (Frederick)
4 Nail Pattern (non-HVHZ only)
FASTENERS
5°
Figure 9. Heritage@ Premium (Frederick)
6 Nail Pattern
ZONE/
11ON BONG
1 ur'lbuul.4 FL18355-R4 Page 6 of it
This evaluation report 1s provided for State of Flonda product approval under Rule 51G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product allnbutm that are not
specifically addressed herein.
CREEK
TECHNICAL SERvicFs, LLC
Heritage® Woodgate Basic Wind Speed (V„ il):
(Frederick) Basic Wind Speed (V, )
Deck (Non-HVHZ):
Undedayment
Min. slope:
Installation (Non-HVHZ)
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturers application instructions -when installing
shingles at slopes greater than 21:12.
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either'4 Nail
Pattem" or "6 Nail Pattem' delailed below.
5-1}" 1 EXPOSURES
1'=rl �- 11"-.►�12-3/8"� 11" --� �-1"
Figure 10. Heritage®Woodgate (Frederick)
4 Nail Pattern (non-HVHZ only)
NAILZONE/
FASTENERS COMMON BOND
t T
S-1/2" EXPOSURE 5'
1"'� � 9.1/2"-►1'•3�9.?/8"�3 "I' 9.1n" � 1_ '"
Figure 11. Heritage0 Woodgate (Frederick)
6 Nail Pattern
FL18355-R4
7 of 11
I ms evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
"CREEK::
k�
S
®,
1
_
TECHNICAL SFRv1CFs. LLC
Heritage® Vintage®' - Basic Wind Speed (Vwl)- ILL
f ` -
(Phillipsburg) . Basic Wind Speed (Val): Me
Deck (HVFIZ) , In
So
nii
,.Deck (Non-HVHZ):In
k
ne
Li d-' d
yment
Min. slope:', _, 2:1
the
,.
shi
installation (HVHZ) Ins
an,
Installation .(Non-HVHZ): Ins
rec
. ins
Pa
I v
41
fI .�
e.
(
I
Figure 12. Herite
5 Nall Pattern {no
y. iate:m •.
- -
Figure 13., Heiita
6 Nail Pa
TBP15001A FLIB355
' TAMKO BUILDING PRODUCTS
Asphalt Shingles
194 mph-'
'
150 mph,--,
cordanoe with FBC requirements;
Ily sheathed Min 19132-ini. plywood oiwood plank for
:.
construction Min. -15/32 In.- ply'i o - existing
iruction' -
cordancewithFBCregwremenb
ly sheathBAtmin 15132 m-plywood o[wootl planKfor-'—""
^`;� "`—^ � -�-
wristructiorr'Mm 7/16 in:OSB existing construction.,
cordance with FBC requirements
and in accordance Will FB(Jrequimrrmntis. Refer to
nanufacWreCs application instructions when installing -
Iles at slopes greater than 21 12
Iled with 5 in exposure in accordance with RAS 115-
manufacturers 'published installation's Instructions.`
,
31es shall be"attached using 6 Nait PaUem detailed-
V
Iled with. 5�-in exposure,' inaccordance with FBC
rements and manufacturers published installation,
lctions Shingles shall lie attached using either 5 Nall;'
im or'6 Nail Pattern detailed below -
°"
xoxn
{
s
v,
erR110
r�—WiY.—PI
y''
Vintage®
-
•HVHZonly)_
., NMI-
,
-.
—t{W
Vintage®
am
4 Pape B of l l
`
_ This evaluation, report is provided for State of Florida product approval under.R
Terhnical'Serrices, LLC of any product rhenges or quality assurance changes
` This evaluation report does not express nor Imply warranty, installation, recom
specifically addressed herein.
or
am not
CREEK
TECHNICAL SERVICES, LLC
Hip & Ridge Basic Wind Speed (VmJ:
(Frederick & Joplin) Basic Wind Speed (V„e)
Deck (HVHZ):
Deck (Nan-HVHZ):
Underlayment:
Min. slope:
Installation:
TBP15001A
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min715/32"in-plywo6d or wood -plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements.
Installed with 5-118 inch exposure in accordance with the
FBC and manufacturer's published installation instructions.
The direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
X—M]
\�1�rr► � ��r�y
Figure I
�Fastener .��tener
I `5-M" F „
Figure �N4 Figure3
Figure 14. Hip & Ridge (Frederick & Joplin)
Technical Services, LLC of any product
This evaluation report does not express
specifically addressed herein.
FL18355-R4 Page 9 of it
ct approval under Rule 61G20-3. The manufacturer shall notify CREEK
assurance changes throughout the duration for which this report is valid.
installation, recommended use, or other product attributes that are not
RAM CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Vintage® Hip & Ridge Basic Wind Speed (V,,ll): Max. 194 mph
(Phillipsburg) Basic Wind Speed (V„e): Max. 150 mph
Deck (HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
Deck (Non-HVHZ):
In accordance with FBC requirements;
—
—Solidly sheathed min. 15132 in. plywood or woad plank for
new construction; Min. 7/16 in. OSB existing construction.
Undedayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements.
Installation:
Installed with 5 inch exposure in accordance with the FBC
and manufacturer's published installation instructions. The
direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
Figure 1
Fastener
5r
,JFastener
Figure 2
y `
1 ••
��- Fastener
5-1 /2"
/4u Figure 3
Figure 15. Vintage® Hip & Ridge (Phillipsburg)
I nis evaluation report IS provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product etinbutes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
LIMITATIONS
TAMKO BUILDING PRODUCTS
Asphalt Shingles
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 ft in the HVHZ.
4) Classification to ASTM D 7158 applies to exposure B & C with a building mean roof height of 60-ft or less,
--5)—Deck-substrates shall"be cclean, dry, and free From any irregulantlen and dehris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underiayment application.
6) Shingles shall be installed starting at the eave in horizontal layers such that the laps shad water from the
deck.
7) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 611320-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6N Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
�`•`,`QG?�'PG E N
ti.
No 74021
*
STATE OF
�:�'c`•'•'P4 G P,: �•�Zachary R. Priest, P.E.
, Florida Registration No. Organization 21
n No. ANE11669
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor Will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R Priest, P.E. does not have, not will acquire, a financial interest in any other entity involved in the approval process of the
product
TBP15001.4
END OF REPORT
FL18355-R4
11 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.