HomeMy WebLinkAboutAC PROJECT SUMMERYJob: yr j°t� sof Project Summary SCANNED Date: Sep 20, 2019 Entire House BY By: QUICK CALCS, INC. St. Lucie County 317 ST LUCIE LANE. FORT PIERCE, FL 34946 Phone: 772466.6799 Fax 772-466-6796 Email: OLnCKCALCS®AOL.COM Project• • For. WAL H RE IDENROAEEO AVE GOLDEN HOMES,JOHINC. RECEIVED I OCT 1 4 2019 RCE, FL Notes: ' ST. Lucie County, Permitting Design Information Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 75 °F Inside db Design TD 70 28 OF OF Inside db Design TD 15 °F Daily range M Relative humidity % Moisture difference 650 1 Heating Summary Sensible Cooling Equipment Load Sizing Structure 32151 Btuh Structure 27918 7817 Btuh Btuh Ducts Central vent (0 cfm) 9600 0 Btuh Btuh Ducts Central vent (0 cfm) 0 Btuh Humidification 0 Btuh none Blo(none) er 0 Btuh Piping Equipment load 0 41751 Btuh Btuh Use manufacturer's data n Rate/swing multiplier Equipmerrf sensible load 0.95 33948 Btuh Infiltration Method Simplified Construction quality Average Fireplaces Heallg Co 3065 llri Area (ft� 5 Volume (M 28503 28503 Air changes/hour 0.28 0.15 Equiv. AVF (cfm) 133 71 Heating Equipment Summary Make Trade Model AHRI ref Latent Cooling Equipment Load Sizing Structure 2977 Btuh Ducts 3828 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 6805 Btuh Equipment Total Load (Sen+Lat) 40753 Btuh Req. total capacity at 0.70 SHR 4.0 ton Cooling Equipment Summary Make Trane Trade TRANE Cond 4TTR6049J1 Coil TEM4AOC48S41++TDR AHRI ref 8676081 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER 32550 Btuh Heating input Heating output 12.0 41104 kW Btuh Sensible cooling Latent cooling 13950 Btuh Temperature rise 24 1550 OF cfm Total cooling Actual airflow 46500 1660 Btuh cfm Actual airflow Air flow factor 0.037 cfm/Btuh Air flow factor 0.043 1.00 cfm/Btuh in H2O Static pressure 1.00 in H2O Static Load pressure sensible heat ratio 0.84 Space thermostat Calculations approved byACCA to meet all requirements of Manual J 8th Ed. `VWK 1cIRK Z 0 ep-2P70:43:30 _ 4- wrrgl tspit^ Right-Sufte® Univ rsal2019 19.0.08 RSL108101 CPagel 'MCA ...nets\Wdghtsoft WACtWALSH RES-.10"TON RO.rup CaIc = MJB Front Deor faces: E w�tgh so Right-.10 orksheet Entire House QUICK CALCS, INC. p n u ps-, T7M66_8799 Fos 772-466-6796 Email: OUICKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: 1 2 3 4 5 Raom name FVosed wall Roheight om Room dimensions Room area Entire House 221.0 ft 9.3 It 3064.8 (t' LAUNDRY 23.0 fl 9.3 ft he ticoot ft 9.0 x 14.0 It 126.0 ft' Ty Construction number U-value (etuhfft°-'r7 Or HTM (BtuMftj AM (ft� or penmeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cod Gross WP/S Heat Cool Gross WP1S Heat Cool 6 11 13A-4ocs 2 glazing, dr lone 2 glazing, dr lcn s 2 glazing, drIov-e 2 glazing,:dGlaue_ 13AAccs 2 glazing, dr lcx a 2 gluing, dr lc v e 2 plazinp, dr lave -13A4&s 2 glazing, dr lcx a 1100 13A4acs 2 glazing, cir Iox a 2 glazing, clr lave 2 glazing, dr laa-e 2 plazng _Gr Irnv_e _16X19{Imd � 22A-tph 0.143 0.650 0.650 0.650 _0.650 0.143 0.650 0.650 �_ 0.650 0.143 0.650 ,0,390 0.650 0.650 0.650 0.650 0.650 `0.408 1.356 n n in n _n_ a a a a s s _s_ w w w w w ', - 4,00 18.20 18.20 18.20 _1&20 4.00 18.20 18.20 18.20 4.00 18.20 _70.92 4.20 18.20 18.20 I18.2DSM 18.20 _1.59 38.02 -rig-651 14.99 14.99 14.99 10.68 2,19 33.77 33.77 20.97 219 10.68 _10.34 219 33.77 3377 20.97 20.97 _1.37 0.00 8 9 18 ,40 409 18 36 �72 391 18 -576 0 0 0 __.0 283 0 0 0 T352 18 -2307 142 164 328 728 1134 328 655 _,1310 1410 328 -__223 328 1328 747 1310 1310 -4856 __8403 1261 117 135 770 427 620 608 1216 _1510 771 192 -211 608 621 3242 1510 1610 4191 0 -0 0 0 0 0 0 0 0 0 �--0 0 0 0 0 -0 0 0 0 _0 _0 0 0 0 _ 0 130 0 0-0-0 0 0 0 _0 130 0 0 0 0 0 `521 0 0 0 0 �__0 285 0 _0 144 0 0 0 372 �170 0 t1J I(( -CMG lN--G �--D _20 618 18 48 96 72 `3063 3063 _20 370 0 0 0 0 =3063 721 64 0 0 0 18 �_726 120 0 0 - _ 66 0 0 _123 _ 23 0 0 _ - -260 0 328 � 875 075 F 114 6 c)AED exclusion --- 1224 Ernelope loss/gain 26058 20543 2186 1092 12 a) WiRration b) Room ventilation 4093 0 1175 0 425 0 122 0 13 Iotemal gains: O=PantS (off 230 Appliancestother 0 0 6200 0 0 0 Subtotal (lines 6 to 13) 32151 27918 2512 1214 14 15 Less external load Less transfer Redstntt on Subtotal Duct loads 30% 28% 0 0 0 9600 39600 0 0 0 27817 7817 30% 28% 0 0 983 2894 894 0 0 184 1392 399 392 Total roorn load Air reqred (dm) ui 4151750 15551 35735 0 3890 144 1790 78 +{-r- �liLF�ghFsolEt�' 2019.Sep-2010:43:30 MCP, "' " ""' Rleht-Suite® Unhersal7A19 79.0.08 RSW8101 Page 1 ...neanWrightsag HVAC%WALSH RES-JOHNSTON RD.NP Calc=MJS Front Door faces: E -T# wrelgUNbIf Right-J® Worksheet Enure House QUICK CALCS, INC. FL uoen Phone: 7791M6799 Fes 772-466.6796 Email: OUICKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: o v 1 2 3 4 5 .1 Lwm wE. , ...,...�.,.._.. _ _._._ ..._.._... Room name Exposed wall Room height Room dimensims Room area HALLWAY 5.a ft 9.3 ft heat/cod 9.0 x 5.0 ft 45.0 ft' I KITCHEN 12.0 ft 9.3 ft It 1.0 x 236.0 ft 2360 ft' . Ty Construction number U-value (BIWJft'-°F) Or HTM (BhWft� Area (ft) or perimeter (ft) Load (Btuh) Aiaa (ft!) or perimeter (ft) Load (Btuh) Heat Cad Gross WP/S Heat Cod Gross WP/S Heat Cool 6 11 W, �-.-G 13AAocs 2 glazing, clr love 2 glazing, dr lcae 2 glazing, dr lave 2 glazing, GCloma_A 13A-0acs 2 glazing, dr lose 2 glazing, dr loH a 2 alazim. Clr laze, lflggocs 2 glazing, dr loxe 11D0 13A4ocs 2 glazing, clr lave 2 glazing, dr lave 2 glazing, clr lcNe 2 glazing _cir lave _16X19-0md -219 14.99 14.99 14.99 _10.68 219 33.77 33.77 20.97 219 10.68 _10.34 219 33.77 -33,77 33.77 20.97 _�1.37 0.00 -0 0 0 0 ^0 0 0 0 0 -0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 -0 0 0 0 0-0 0 0 0 0 0 0 0 0 ,_0 A0:143 0.650 0.650 0.650 �0.650 0.143 0.650 0.650 _0.650 0.143 0.650 _0.390 0.143 0.650 0.650 0.650 �0.650 __0.408 1.358 - n n n n _n_ a a a a s s _s_ w w w w w =. - 4.00 18.20 18.20 18.20 __18.20 4.110 18.20 18.20 182(I 4.00 18.20 _10.92 4.00 18.20 18.20 18.20 18.20 =1.59 3I .02 �L--.---CG rRJ ILA--GGG -0 0 0 0 _ o 26 0 -0-0-0 0 0 0 .0 105 0 a 0 0 o o 0 0 0 0 0 __ _o 0 0 0 0 0 o 0 0 0 ___0 0 0 -0 W1 - 1II------��a �--G 47 0 _ 57 0 _211-0-0--0 0 0 0 0 0 _�o 0 0 0 0 375 328 0 0 0 374 458 _�20 0 0 0 0 a _20 0 0 o 0 0�. _223 0 0 0 0 a 112 18 0 0 0 _236 94 0 0 0 0 =236 ZOS 608 0 0 0 _323 0 ��----GG .0 F 45 45 45 5 ._ 62 _�71 190 0 236 12 22A-tph _ ` 8 c) AED excursion -29 -70 Envelope loss/gain 589 301 1533 1065 12 a) RooIffittrrI ver b) Room vemila[ion 93 0 27 0 222 0 64 0 13 Internal gains: Occupants @ 230 AppliancWother 0 0 0 0 0 2600 Subtotal (lines 6 to 13) 681 327 1755 3729 14 15 Less eDdemal load Less transfer RedisMlxtion Subtotal Dud loads 30% 28% 0 0 -681 0 01 0 0 -327 0 0 3034. 28% 0 0 213 1968 588 0 0 102 3631 1073 Total loom load Air required(dm) 0 0 0 0 2556 95 4904 213 _ 4 YiYSFlg�ilso.[>;- 2019-Sep-2010:4 AC�P. RRES. JOH STONLlniwR 2019 Colo 8 J8 Front Page 2 ...nets\Wrightsofl HVAC\WALSH RES. JOFQJSTON RD.Np Colo = MJB Franl Door faces: E w�;°ghs Right-J®Worksheet Entire House QUICK CALCS, INC. 771dARA700 car 772-4e6-6796 Email: OUICKCALCSCa1AOL.COM Job: Date: Sep 20,2019 By: aria 1 2 3 4 5 wucr-CE,r�.,.�+,,,.........._.___.__.____._ Room name Famed wall Room height Room dimensions Room area _ SUN ROOM 36.0 R 9.3 ft heattood 16.1 x 10.0 ft 160.8 ft. GREAT ROOM 13.0 ft 9.3 It h�t/cod 1.0 x 610.0 It 610.0 ft' Ty Construction number num U-value (BtWVftt•F) Or HTM (BtulM Area On or perimeter (ft) Load (Btuh) Am orpenmet)er (it) Lead (Btuh) Heat Cod Gross WP/S Heat Cod Gross WP/S Heat Cod 6 11 13A 4 2 glazing, dr lcwe 2 glazing, dr Icv-e 2 glazing, or b*e 2 glazltg. clr to _ 13A-0ocs 2 glazing, dr Iwte 2 glazing, dr Iov a 2 plazinp tlr Icv-s 2 glazing, dr Icva 11D0 13A-4= 291azing, drla 291ezing, drlcv<e 29bzing, dr Iowa 2 plazinp adr lory Vic_ j6X19-0rrld 22A-iph `0343 0.650 0.650 0.650 _0.650 0.143 0.650 0.650 _0.650 0.143 0.650 n n n n 400 18.20 18.20 18.20 -__219 14.99 14.99 14.99 --93 0 0 0 40 -53 0 0 0 -212 0 0 0 _728 0 0 0 _ 0 300 328 0 - 116 0 0 0 427 0 0 0 0 164 192 _0 -0 0 0 0 _0 -'�0 0 0 0 ^0 � �0 0 0 0 0 � - � 0 0 0 0 -0 l---G -n_ a a a a s s _s_ w w w w w • - 18.20 4.00 18.20 18.20 18.20 4.00 18.20 . 10.92 4.00 18.20 18.20 18.20 1820 _1.59 38.02 _10.68 219 33.77 33.77 20.97 2.19 10.68 _10.34 219 33.77 33.77 33.77 20,97 _1.37 0 0 0 _ 0 93 18 _0 0 0 0 _ 0 75 16 ,0 0 0 0 _ _0 0 0 _0 0 0 0 0 0 0 _0. 0 0 0 0 0 0 0 --0 0 _0 54 0 0 3242 0 = 835 _ 0 II-----GG _ '(iy13A-0ons 0 '0 0 WI _ F _0.390 0.143 0.650 0.650 0.650 0.650 _0.408 1.358 __0 149 0 0 0 54 �160 95 0 0 0 0 =160 380 0 0 0 1983 `254 1369 207 0 0 0 1133 �279 0 121 0 0 95 0 _610 610 25 0 0 0 0 =810 13 100 0 0 1747 0 =96% 494 0.00 160 36 _ --- _ - - 311 920 8 c)AED excursion Envelope loss/gain 4553 2769 3308 5051 12 13 tion a) Infiltration b) Rc ventilatlon Imemal gains: Occupants (a? 230 Appliances/othef 0 667 190 0 0 0 0 69 0 0 0 Subtotal (lines 8 to 13) 5220 2961 3649 5120 14 15 Less external load Less transfer Redsinbution Subtotal Duct leads 30% 28% 0 0 5220 1559 U 0 2961 829 30% 28°/ 0 0 16 3565 1084 0 0 13 5133 1437 Taal room load Air required (cfm) 6778 252 3790 164 4629 172 6570 285 2019-Sep-20 10:43:30 y - . I9Hfsoit" Page 3 ...nelslWd9htsofl HVACIWALSH RES JOHNSTON RD.mp Celc = MJ8 Fronl Door bees: E weigh so t' Right-M Worksheet Entire House QUICK CALCS, INC. NE cnor omorc m voe6 PM , T/2d66-6799 Fax 772-066.6796 Emil: QUICKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: 1 2 3 4 5 Room name Elrposed wall Room Wight Room dirtlensi" Room area LINEN O ft 9.3 R heal/cod 4.0 x 4.0 ft 16.0 ft' PANTRY 0 ft 9.3 ft heat/cool 6.0 x 4.0 ft 24.0 ft' Ty number m ( om F) Or (I3tuNft� Pedmet)er (it) Load (Btuh) Am (et�er (it) penm Load (Btuh) Heal Cool Gross WP/S Heat Cool Gross WP/S He Cod 6 13A4xs 2 glazing, Ur lave 2 glazing, Ur love 2 glazing, Ur Ime 2 glazing, e drlov _ 2 gluon s 2 glazing, dr lave 2 glazing, or low-e 2 plazino Ur lave 13A-0ocs 2 glazing, Ur lave - 0.143 0.650 0.650 0.650 �0.650 0.143 0.650 0.650 0.650 -0.143 0,650 _0.390 0.650 0.650 0.650 0.650 0.650 == 408 1.358 n n n n _n_ a a a a s s -a-_.10.92 w w w w w - 4.00 18.20 18.20 18.20 -18.20 4.20 1820 18.20 18.20 -4.00 18.20 4.00 18.20 18.20 18.20 18.20 =1.56 38.02 '-219 14.99 14.99 14.99 -10.68 219 3219 33.77 20.97 219 10.68 _10.34 219 33.77 33.77 33.77 20,97 =1.37 0.00 0 0 0 0 -0 0 0 0 0 0 0 0 0 -0 0 0 0 0_-0-0-0- -0 0 0 0 ,_____0 0 0 0 0 0 0 `--00 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 0 0 -0 00 �0 0 0 0 0 _._.__0 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 VJ 0 0 0 -0 0 0 0 -_0 0 0 �0 L��-EGG lN--G T-D C= F -0 0 0 -0 0 0 0 0 0. 0 0 0 0 JI D0 2 glazing, Ur Iav-e 2 gluing, 2 glazing, Ur lave 2 glazing, Ur lave 2 plazinp Gr 1pv-e 16MUrrd- 0 0 0 0 0 -0-0- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 --24 0 0 0 0 0 "_24 0 0 0 0 0 �38 0 0 0 0 0 =33 �16 16 =16 0 =25 =22 _ 0 22A-tph -_ -� 2 3 6 c) AED a ssion Envelope loss/gain 25 20 38 30 12 a) Idiltration b) Room verftllatlon 0 0 0 0 0 0 0 0 13 Internal gains: Occupants Q 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 25 20 3S 30 14 15 Less esdemal load Less transfer Redstdlwtlon Subtotal Duct loads 30% 28% 0 0 85 111 33 0 0 41 61 17 30% 28% 0 0 0 38 it 0 0 0 30 8 Total mom load Air required (cfm) 144 5 78 3 49 2 39 2 4j, W1:jM1vA;0 .-. 2019-SeP-2010:43:30 t -""""""... -1 Right -Suite® llniversal 2019 19.0.08 RSU08101 Page 4 AGCA netslWdghtsoft WAC1WALSH RES-JOHNSTON RD.MP CaIc=MJ8 Front Door faces: E }}$ w�i°gli'`soft Right-J®Worksheet Entire House QUICK CALCS, INC. 77246aa799 Fan 7724666796 Email: OUICKCALCSCo1AOL.COM Job: Date: Sep 20, 2019 By: au 1 2 3 4 5 si �wm vu7c, r..nP12R �..,.,-.... .._.._. .._ .__ _. __ Room name RocarlEVOSedwail Room crimeheight Room dnxnsions Room area FOYER 7.0 ft 9.3 ft heat/cool 7.0 x 27.0 ft 189.0 ft' BATH 3 0 ft 9.3 ft heal/cod 120 x 5.0 ft 60.0 ft' Ty Construction number U-value (Btuh/fti'F) Or HTM (Bluh/ft!) Area (ft� or perimeter (11) Load (Btuh) Arm (ft71 a perimeter (ft) Load (Btuh) Heat Cool Gross WP/S Heat Cod Gross WKS Heat Cod g 11 -13p toes' 2 glazing, dow-e r l 2 glazing, clr love 2 glazing, dr lowe 2 glaz rS-clrjo _ 13A4= 2 glazing, dr lowe 2 glazing, dr !owe 2plazinp. of lox_e '13q lots - 2 glazing, or lc we '--6-143 0.6W 0.650 0.650 .-0.650 0,143 0,650 0.650 0.650 ^0- Q650 _0.390 0143 0.650 0.650 0.650 0.650 _0.408 1_358 n n n n _n_ a a a a n s _s_ w w w w w y 4A8 18.20 18.20 18.20 _18.20 4.00 18.20 18.20 18.20 4.00 18.20 _10.92 4.00 18.20 18.20 18.20 1820 _1.59 38.02 -.'219 14.99 14.99 14.99 _10.68 219 33.77 3377 20.97 - 219 10.68 _10.34 219 33.77 33.77 33.77 20.97 _1.37 0.0-0 --0 0 0 0 -0 65 0 36 0 0 0 0 0 29 0 0 0 0 0 0 -0 0 0 0 _0 117 0 655 0 -"0 0 0 0 0 64 0 1216 _ 0 0 0 0 0 0 0 0 ,_r.0 ---0 0 0 0 0 -._0 0 0 0 ______0 -0 0 0 ,_ O 0 0 0 -_0 0 ` o 0 0 0 _T0 0 0 0 0 0 0 0 0 0 0 __0 0 _- 0 "yJ `- 1I---� 0 0 0 0 0 _0 0 0 0 �--D W1 .11 D0 13A-4ocs 2 glazing, or lcw a 2 glazing, or lc a 2 glazing, or lcN a 2 placing _o r lc e_ 16X79-0md-� 22A-toh _0 0 0 0 0 0 =189 189 0 0 0 0 0 ,�189 7 0_ 0 0 0 0 u300 266 0 0 0 0 0_ ,259 0 0 0 0 0 60 60 0 0 0 0 0 � o 0 0 0 0 0 0 -95 0 0 3 0 �__ -0 C� F 0 _ _ -64 6 c)AED excursion 7 Envelope loss/gain 1338 1474 95 75 12 a) hfiftretion b) Room ventilation i 30 300 0 0 0 0 13 internal !Joins: A pplesother 0 0 0 0 0 Subtotal Qines 6 to 13) 1467 1511 95 75 14 15 Less e#m eal load Less transfer Redslrilwtion Subtotal loads Dud loads D 30% 28°e 0 3 1470 439 0 2 1513 424 30% 28% 0 0 22 117 35 0 0 18 93 26 Total mom load Air required (dm) 1909 71 1 1937 84 153 6 119 5 A- \iv 19�-'.1Y5o{* 2019-Sep-2010:43:30 AGOA � " '`" Right -Suite® DniVar$al 201919.0.08 RS1108101 Page 5 ...nets\Wdghtsoft WAGMALSH RES- JOHNSTON RD.NP Calc - MJB Front Door faces: E ----- tsgOft• Right-J® Worksheet Entire House QUICK CALCS, INC. 111..00 Fnr "9dRR.6796 Fmeil: OUICKCALCSOAOL.COM Job: Date: Sep 20, 2019 By: 311 1 2 3 4 5 bI LUUItL . .RT PIERCE, FLW....... ....��___.__.-_.._.___._. Room name Ev'posed wall Room height Room dnlensicns Room ana'1 _ OFFICECLST 0 If 9.3 It heat/cool 120 x 21 It 25.0 ft OFFICE 7.0 If 9.3 It heat/cod x 220.0 ft 220.0 It' Ty Construction number U-lelue (Btu[Vftk-F) Or HTM (9tulvM Area (ft9 or perimeter (ft) Load (Btuh) Axea (ftj or perimeter (ft) Load (6tuh) Heat Cool Gross WP/S Heat Cod Gmss WP/S Heat Cool 6 11 0143 0.650 0.650 0.650 _0.650 0.143 0.650 0.650 ��0.650 0.143 0.650 _0.390 0.143 0.650 0.650 0.850 0.650 _ 0:408 1.358 n In n n _n_ a a a a `s s _s_ w w w W W 7 _ 4.00 18.20 18.20 18.20 _18.20 ADD 18.20 18.20 16.20 ^ 4.00 16.20 _70.92 4.00 18.20 18.20 18.20 18.20 �1.59 38.02 219 14.99 14.99 14.99 --a 0 0 0 - 0 0 0 0 0 0 0 0 0-0-0 0 0 0 0 0 0 65 18 0 ,_0 0 0 0 0 0 _0-0-0 47 0 0 0 0 0 0 0 0 0 13A-0acs 2 glazing, dr lave 2 glazing. dr ow-e 2 glazing, dr loxes 2 glazing, dr-100a_ 13A-4= 2 glazing, dr lave 2 glazing, cir low�e 2 plazinp,c1r Iom =, 13A-0dds 2 glazing, dr lave 11p0 _10.68 219 33.77 33.77 -2.0.97 219 10.68 _10.34 219 33.77 33.77 33.77 20.97 =1.37, 0.00 _0 0 0 0 0 0 0 0 0 0 0 0-0-0-0-0-0- 0 0 0 0 0 0 0 _ 0 0 0 328 28 0 0 0 D 0 608 10 0 0 0 0 0 I_p 0 0 0 0 0 0 0 W F lak400s 2 glazing, dr low-e 2 glazing, dr lavc 2 glazing, dr lave 2 plazinp. Gr tory_e .16X19-0md 22A-tph 0 0 0 0 0 0 0 0 0 0 __24 0 0 0 0 0 0 _�_38 0 0 0 0 0 0 =33 0 0 0 0 0 0 _220 0 0 0 0 ^-_ _ 0 0 0 0 0 ,� 349 268 a 0 0 __ 0 _3010 �-24 24 220 _.220 7 -3 -126 6 c)AED elxursion Emelope loss/gain 38 30 1131 886 12 a) Infiltration b) Room ventilation 0 0 0 0 130 0 37 0 13 Ihtemal gains: occupants ot 230 Appliancesrother 0 0 0 0 900 Subtotal Ounce 6 to 13) 38 30 1261 1823 14Subtotal 15 Less eMertW load Less transfer ReDudctRedistributionRedistribution0 Duct 30% 28% 0 _ a 0 0 _30 0 01 3D'/o 289% 0 0 29 1290 385 0 0 23 1847 517 Total rmm load Air required (dm) 0 g 1676 62 23&1 103 _ 2019-Sep�2010:43:30 AC N Right -Suite® Universal 2019 19.0.08 RS008101 Page 6 ... nets\Wnghtsoft WACIWALSH RES- JOHNSTON RD.nup Calc = MJ8 Front Door faces: E w�ightso Right-JO Worksheet Entire House QUICK CALCS, INC. 0 T PIERCE FL 34946 Phone: 772466-6799 Far 772466-6796 Email: OUCKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: Jv 1 2 3 4 5 W wcie w4E, F R Room name Exposed wail Room height Room areaom areaclimatisians Room WIC 2 0 It 9.3 It heaVcod 11.0 x 4.0 ft 44.0 It' BEDROOM 2 26.0 It 9.3 ft heat/cod 211.0 g=1.0 x 211.0 ft Ty Construction number U-value (ghwit-F) Or HTM (Btuwft� rea AM5 or perimeter (ft) Load (Btuh) AM M orr perimeter (ft) Load (Btuh) Heat Cod Gross WP/S Heat Cod Gross WP/S Heat Cod 6 11 13A;% 2 glazing, dr lc v-e 2 glazing,; clr Iowa 2 glazing, clr love 2 glazvg,_dLlov:e...._ 13A4xs 2 glazing, dr lcx a 2 glazing, dr lcr a 2 plazim dr lory-e 13A-0ocs 2glazing, dr lov-e ,1100 13A4acs 2 glazing, dr lave 2 glazing, dr laves 2 glazing, cir lone 2 glazimi, dr lcvv a .18X190md. 22A-tph "O.f43 0.650 0.650 0.650 .,^0,650 0.143 0.650 0.650 0.650 ^^0.143's 0.650 n n n n _n_ a a a a s _s_ w w w w w = = - 4-00 1&20 11120 18.20 _t&20 4.00 1&20 1&20 1&20 4.00 18.20 .-J0.82 4.00 18.20 18.20 18.20 18.2D 1:59 36.02 -219 14.99 14.99 14.99 0 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 io 0 0 0 __0 ---0 0 0 0 _0 --0 0 0 0 !0 �,10.68 219 33.77 33.77 20.97 - 2.19 10.68 _70.34 219 33.77 33.77 33.77 20.97 =1.37 -0 0 0 0 0 _.._0 0 0 0 0 ___.��0 0 0 0 0 0 0 0 0 0 0 0 0 =70 _0 0 0 0 0 140 0 0 T_36 121 0 0 0 0 0 0 ^, _0 ,_.211 211 100 0 0 _ U 121 0 0 0 0 0 0 0 _211 414 0 0 655 - 484 0 0 0 0 0 0 0 _�335 220 0 0 _7`5 265 D -0 0 0 0 0 0 ;289 0 V,V�-Ca `D 0 0 0 0 0 0 0 0 0 0 _0 0 0 0 0 0 0 0 _0 0 0 0 0 0 T60 0 IW - ,C_ F -0.390 0.143 0.650 0.650 0.650 �0_650 _0.408 1.358 44 �44 28 1065 0.00 44 0 0 -5 89 6 c)AED excursion Envelope loss/gain 70 55 2953 1633 12 a) Infiftretion b) Room ventilation 0 0 0 0 5199 1499 13 Internal gains: Occupants @ 230 Appliancesrdhef 0 0 0 0 0 0 Subtotal Qines 6 to 13) 70 55 3472 1782 14 15 Less eDdernal load Less transfer Redistribution Subtotal Dud loads 30% 28% 0 0 0 70 21 0 0 0 55 15 30°/n 28% 0 0 0 3472 1037 0 0 0 1782 499 Total mom load Air required (dm) 91 I 3 71 3 4508 167 2281 99 2019-Sep-20 10:43:3D ACCP Ri9hlSuiteO Universal 201919.0.08 RS1108101 Page 7 ...nets\Wdghtsoft FMACVWALSH RES JOHNSTON RD.NP Calc = MJB Front Door faces: E Right- JO Worksheet Entire House QUICK CALCS, INC. 0o F.w rivseaams Pm fl- OLIICKCALCS0AOL.COM Job: Date: Sep 20, 2019 By: au 1 2 3 4 5 si LwIM� ,11-".n..c.��.,..,........._. .._.___.___.._.__ Roomnanie Elpmed wall Roan height Room dimensions Roan env _ BEDROOMS LMNG O ft 9.3 It heat/coot 14.0 x 11.0 it 154.0 W MWIC O n 9.3 It heat/cool 10.0 x 9.0 1t 90.0 ft2 Ty Constnraicn number U-value (BtuNftk•t7 Or HTM (Stuh/ft') Arm (ft� or perimeter (it) Load (Btuh) AM (ftl a perimeter (ft) Load (Btuh) Heat Cod Gross WP/S Heat Cod Gross WP/S Heat Call 6 11 13A7413cs 2 glazing, ar bme 2 glazing, clr Iv2v-e 2 glazing, ar low-e 291azing. clr.love, 134400s 291azing, Gr lave 2 glazing, ar lave 2 plaZirlp, ar love_ '13A4&S 2 glazing, ar 10 1100. 13A4= 2 glazing, dr lod-e x 2 glazing, clr loa 2 glazing, clr lows 2 plazinn _ar lave �18X19:Omd 22Mtph 0143`n 0.650 0.650 0.650 �0.650 0.143 0.650 0.650 0- 0.143 0.650 �0.390 0.143 0.650 0.650 0.650 _0_650 n n n -n_ a a a a 5 s _s_ w w w w w = 4:00 18.21 18.21 18.20 11129 4.20 18.Z0 18.20 1420 4.00 18.2D _10.92 4.00 18.20 18.20 18.20 18.20 =.59 219 14.99 14.99 14.99 _10.68 219 33.77 33.77 219 2Z19 10.68 -10.34 219 33.77 33.77 33.77 20.97 _1.37 0.00 0 0 0 0 _0 0 0 0 0' 0 0 0 0 0 0 0 0 0 0 0 0 _0 0 0 0 0 0 0 0 -0 0 0 0 0-0 0 0 0 0 0 0 0 0 0 0 0 -0 0 0 0 D 0 0 _-0 y 0 0 0 0 __0 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 - 0 0 _0 0 0 0 0 0 "0 0 0 -0 0 0 0 0 0 =143 _0 0 0 -0IWI - 0 0 0 0 0 154 1f 4 0 0 0 0 0 154 0 _0 0 0 0 0 0 -244 0 -00 0 0 0 0 0 _211 0 0 0 0 0 0 _9D 90 0 0 0 0 0 _90 0 0 0 0 0 0 �123 0 F 0 ._0.408 1.356 - 38.02 -162 10 6 c)AED excursion Envelope loss/pain 244 49 143 113 12 a) IMittration b) Roomventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 ApplianCes/other 0 0 1800 0 0 0 Subtotal (lidos 6 to 13) 244 1849 143 113 14 15 Less edema] load Lesstransler Redistribution Subtotal Duct loads 30% 28°h 0 10 254 76 0 8 185 520 30% 28% 0 0 28 170 51 0 0 22 135 38 o Totalraxn lad Air regared (rim) 329 12 2376 103 221 e 173 e 2019-Sep-2010:43:30 •"••"""" ""' _'^"-"' RightSulte® LInhR1sa12019 19,0.08 RSW8101 Page 8 .�CCA ...nets\Wdghtsoft HVAC%WALSH RES- JOHNSTON RD.Np Calc = MJB Front Door faces: E w� ghtsvo& Right-J®Worksheet Job: Date: Sep 20, 2019 Enure House By: QUICK CALCS, INC. 770�92e799 car nMSS-6796 Emil: OUICKCALCSistAOL.COM 1 2 3 4 5 Room name ExpoSRoome eight Room height Room dimensions Room area �0 It 8.3 it 4 0 x 9.0 he f coel 36.0 It' MASTER BEDROOM 34.0 ft 9.3 ft heat/cool 1.0 x 283.0 ft 283.0 it' Ty Construction number U-value (BtLdV t'-`F) Or HTM (Btuh/Rl Area M or perimeter (it) Load (Btuh) Area (f11 a Perimeter (it) Load (Btuh) Heat Cod Gross WP/S Heat Cod Gross WP/S Heat Cod 6 11 134-0ocs 2 glazing; clr lorv-e 2 glazin dr Iwv-e 2 glazing, clr Iom-e '.2 glazing„Gr.lorv:e._ 134-00cs 2 glazing, clr Im" 2 glazing, clr lave 2 glazi_m dr lone -13AAocs _ 2 glazing, clr low-e i1D0 _ 13AAocs 2 glazing, dr Io 2 glazing, dr lave 2 glazing, clr lave 2 glazing _dr love _16X19A/nd 22A-tph ^0.143 0.650 0.65D 0.650 �0,650 0.143 0.650 0.650 0.650 0.143 0.650 _0.390 0.143 0.650 0.650 0.650 _0_650 _0.408 i_358 n n n n _n_ a a a a s s _s_ w w w w w - 4=00 18.20 18.20 16.20 _78.20 4.00 18.20 18.20 18.20 4.00 18.20 _10.92 4.00 18.20 16.20 18.20 18.20 _7.59 38 219 14.99 14.99 14.99 _10.68 2.19 33.77 33,77 20.97 2 19 10.68 _10.34 218 33.77 33.77 33.77 20.97 _1.37 0.00 0 0 0 0 0-0-0-0-0 0 0 0 0 0 0 0 0 0 0 0 0 --0 0 0 0 0 0 0 0 - 0 0 0 0 0 0 0 00 177 0 0 18 0 0 0 -169 0 0 0 0 0 0 0 00 0 0 _ �0 92 0 0 0 0__ `283 34 -635 0 0 328 0 347 0 0 270 II-�--ClG 0 0 0 -0 0 0 0 __0 0 0 �0 IN�G 0 0 0 0-0-0 0 0 0 0 0 0 0 0 140 0 48 0 0 _283 0 0 -0 �D l 0 0 0 0 0 = 36 36 _0 0 0 0 0 0 0 0 0 0 _T_ 0 -SZ 0 0 0 0 0 368 0 874 0 0 449 129 3 200 0 1621 0 � 0 F �36 0 49 0 0 283 - .02 6 C)AED excursion 277 Envelope loss/gain 57 45 3945 3102 12 a) Infiltration b) Room ventilation 0 0 0 630 0 1810 0 13 Neural gains: Occupants o 230 Appliancesrottar 0 0 0 0 0 900 Subtotal Qines 6 to 13) 57 45 4574 4183 14 Less e#emal load Less transfer R�stdbution Subtotal6 Dud loads 30% 26% 0 _� 0 0 0 -45 0 0 30% 28% 0 0 458115 1368Total A mom load required (cfm) 0Air _ vV�t9bT5o t-, 20t&Sep-2010:e �= -""•".^"" Right-Suite®lYiiveroa1201919.0.08 RSW6101 Page 9 ,40Ck... nets%WnghtsoB WACIWALSH RES-JOHNSTON RD.mp Calc=MJS Front Doorfaces: E wnghl-NO • Right-M) Worksheet Entire House QUICK CALCS, INC. PIERCE F uana chon, 772d M799 Fax 772466-6796 Email: QNCKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: .1 1 2 3 4 5 S,..U..,E....�....... .._...._..__._._..._._. .._ _. Room name EVMed wall Room height Room arrmereians Room area M HALL 0 ft 9.3 ft heat/cool 4.0 x 4.0 ft 16.0 ft' M BATH 16.0 ft 9.3 ft heat/cool 1560 ft 1.0 x 156.0 ft Ty Construction number U-%slue (Btuh/ft-F) Or HTM (B UIM A> (ft� a perimeter (ft) Load (Stuh) Area (0j or perimeter (ft) Load (Btuh) Heat Cool Gross WP/S Heat Cod Gross WP/S Heat Cod 6 V�jJ--G 13A4acs 2 glazing, dr lowe 2 glaznxy dr love 2 glazing, dr lov-e 2 gIni g,.dr,lov e_ 134-0acs 2 glazing, dr loxes 2 glazing, dr IO 201MMIL dr ]a" 13Agocs 2 glazing, or lowe `-0343 0.650 0.650 0.650 _0.650 0.143 0.650 0.6W _�0.650 0.143 0.650 _0,390 0 650 0.650 0.650 0.650 0.650 _0408 1.358 n n n n _n_ a a a e_ `e s _s_ w w w w w 4-00 18.20 18.20 18.20 -18.201 4.00 18.20 18.20 18.20 4.00 18.20 -10.92 8.20 18.20 18.20 18.20 18.20 _1.59 38.02 -2 19 14.99 14.99 14.99 219 33.77 33.77 20.97 - Me 10.68 _10,34 3.19 33.77 33.77 33.77 20.97 =1.37 0.00 - 0 0 0 0 -00,68 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 149 8 0 0 -0 0 0 0 0 141 0 0 0 0 0 0 0 0 0 0 0 '-565 142 0 0 _0 0 0 0 0 - - 308 117 0 0 0 -0OJ 0 0 0 I--G ILA-.�QG ___ -W --�_a 0 0 0 0 0 0 -0 0 0 _0 0 , 0 ._..._a 0 0 0 0 0 �0 <-D -JJDO 134-0ocs 2 glazing, cir lave 2 glazing, clrlave 2 glazing, cur lave 2 glazmg, cur lave _18X19-0 - _ 22A-tph -0 0 0 0 0 0 __0 0 0 0 0 0 0 0 0 0 �, 0 = 25 00 0 0 0 0 0_ -22 0 0 0 0 0 0 0 0 0 �_ 0 156 0 0 0 0 0 _247, 0 0 0 0 �_0 _213 0 F _ 16 16 16 0 �156 156 18 608 _2 -� 6 elcurs c)AEDion EmMope lass/gain 25 20 1582 581 12 a) RooInfiltration b) am �erdila0on 9 9 0 0 296 0 a6 0 13 Internal gains: Occupants a 230 Appliar,xs/dher 0 0 0 0 0 0 Subtotal Qines 6 to 13) 25 20 1859 666 14 15�=mlwd Less edemal load Less transfer Redistribution Subtotal 30% 28% 0 0 -25 0 0 0 0 -20 0 0 30% 28% 0 0 6 1865 557 0 0 5 671 188 0 0 0 0 90 37 2019-Sep-20 10:43:30 AEFA """"""""" "" ""'"' Right-SuiteD Lhhersal 2019 79.0.08 RSW8101 Page 70 ...nets\Wrightsoft HUAMWALSH RES-JOHNSTON RD.mp Cale=MJS Front Doorfaces: E wrrigMsoR Right -A) Mrksheet Engre House QUICK CALCS, INC. 317 ST LUCIE LANE FORT PIERCE FL 34946 Phone: 772-466-6799 Faz 772466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Sep 20, 2019 By: 1 2 3 4 5 Room name Exoosed wall Ron height Roan Roan dimensions Roan area M TOILET 0 ft 9.3 It heaUcool 4.0 x 5.0 ft 20.0 ft2 BATH 2 - 8.0 it 9.3 ft heat/cad 11.0 x 8.0 ft 88.0 ft2 Ty Constmdicn number U-value (BtWft-°F) Or HTM (Btuwm Area (ft2) cr Perimeter (ft) Load (Btuh) Am M or perimeter (ft) Load (Stuh) Heat Cool Gross WP(S Heat Cod Gmss N/P!S Heat Cod 6 11 U 143 0650 0.650 0 850 _0.650 0.143 0.650 0.650 __0.650 01-- 0650 n n n n en_ a a a a 5 s w w w w w = - 4'W 1820 1820 1820 18.20 4.2 18.2020 18.20 18.20 4.00-219 18.20 1092 4.00 18.20 1620 18.20 11120 1.59 3&02 --219 14.99 14.99 14.99 10.68 - 0 0 0 0 - 0 -0 0 0 0 0 -" 0 0 0 0 0 0'-74 0 0 0 0 0 9 0 0-0-0 65 0 0 0 �'262 0 164 0 - 43 0 135 0 i3A4a 2 glazing,'dr lave 2 glazlrg, dr lode 2 glazing, clr lave 2 glazing. dc,love 13A-0acs 2 glazing, dr low-e 2 glazing, dr lowe 2 glazing, dr to 13A4ocs 2 glazing, cir Iowe - -0 0 0 0 R_,0 0 0 -0 3377 33.,77 77 20.97 10.68 10.34 Z19 33.77 33.77 33.77 20.97, �_'f,37 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 -0 NW,W,/0WNN,��11 Cam_ F 0 0 0 0 0 -0 0 0 __,��0 0 0 --_0...�__.0 0' 0 0 `0 0 -0 11D0 13A-0ccs 2 glazing, clr lave 2 glazing, clr lave 2 glazing, clr lave 2 glazing _clr lave _16X19-0rri4 22A-trh �0,390;s_ 0.143 0.650 0.650 0.650 0.650 =07408 1.358 -0 0 0 0 0 0 20 0 0 0 0 0 0 0 0 0 0 _�.32 0 0 0 0 0 0 0 0 0 T_ 0 �__88 a 0 0 a 0 0 0 0 0 __-___-o ;�>1-40 0 0 0 0 - 0 _.120 20 �_ ,=27 ,�.,_88 =' 88 8 -2 36 6 c)AED excursion Ernelope loss/gain 32 25 869 363 12 a) Rocsan ve b) Room ventilation 0 0 0 0 148 0 43 0 13 Internal gains: Occupants @ 230 Pyplianceslother 0 0 0 0 Subtotal(lines 6to 13) 32 25 1018 405 14 15 Less edema[ load Less tributio Redistribution Dud bads Duct 30% 28% 0 0 32 9 0 0 25 7 30% 28% 0 0 0 1018 304 0 0 0 405 114 Total raxn load Air required (dm) 41 2 32 1 1321 49 519 23 �}+6igi.ot 2019-Sep-20 10:43:30 �-- " Ri9hbSuite® Universal 2019 19.0.08 RSU08101 Page 77 �� ...nets\Wrightsoft HUAC\WALSH RES- JOHNSTON RD.MP Calc = MJ6 Front Door faces: E weigh sofi' Right-J® Worksheet Entire House QUICK CALCS, INC. eo vim.. 1111 maa Finail- DI IICKCALCS0AOL.COM Job: Date: Sep 20, 2019 By: 31fbi 1 2 3 4 5 LLWLL m.rVI11---r�s.To........ ,.�.___.__ __ Room nerne Pad wall Room height Room dlman5lona Room area WIC 3 4.0 ft 8.3 ft heaUcod 11.0 x 4.0 ft 44.0 ft' BEDROOM 3 28.0 ft 9.3 ft hea 1.0 x 211.0 It 211.0 ft' Ty Construction number U-,Jww (Btuh/ftWF) Or HTM (Btuwm Nea (ft') a Perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 13A'-0ocs ' 2 glazing; or low-e 2 glazing, or Iowa 2 glazing, dr lcxe glazing, clrlowe_ 13A-0gcs 2 glazing, or lcxe 2 glazing, clr Iowa 2 glazing, drlova t3A-0ocs0.143 2 glazing, or Iowa 11D0 13A-4= 2 glazing, dr lava 2 glazing, dr lowe 2 glazing, dr Iowa 2 glazing.dr Iowa _16X79.Omd`- 22A-tph � C143 0.650 0.650 0.650 _0.650 0.143 0.650 0.650 �0.650 0.650 0.390 0.143 0.650 0.650 0.650 0.650 -0.408 1.356 n n n n _n_ a a a a s s _s_ w w w w w = - 4A0 18.20 18.20 18.20 y18.20 4.20 18.20 18.20 18.20 4.00 18.20 10.92 4.00 19.20 18.20 18.20 18.20 ____7.59 38.02 vn9 14.99 14.99 14.99 ,_-_10.68 219 33.77 33.77 20.97 i 219 10.68 __10.34 219 33.77 33.77 33.77 20.97 - 1.37 ^0.00 37 0 0 0 _�0 0 0 0 0 �37 0 0 0 ,._,_0 0 0 0 0 --149 0 0 0 0 0 0 0 0 -81 0 0 0 �0 0 0 0 0 121 0 0 0 0 140 0 0 36 121 0 0 0 0 100 0 0 0 w484 0 0 0 0 -- -265 0 0 0 ___6 220 0 0 755 0 0 --0 0 0 0 0 _ 289 _ 0 I�FF---------GGGG ..2 410 0 0 055 0 0 0 'UJ II---w 0 0 0 0 0 0 0 0 0 0 0 0 -0 9 0 -0 �--D ,C,� F 0 0 0 0 0 __0 0 0 0 0 0 49 0_. ,_0 0 0 0 _-0 �70 152 0 0 0 0 0 _�_80 0 0 0 0 0 -fit 211 _211 0 0 0 0 0 0 0 0 0 -330 �_. 1065 - �._211 A -14 44 4 -13 6 c)AED excursion 99 Envelope loss/gain 371 128 2953 1633 12 a) otion Ronn b) Room ventilation 700 200 519 0 149 0 13 Internal gains: Occupants Q 230 Appliances/other 0 0 0 0 0 0 Subtotal Qines 6 to 13) 445 150 3472 1782 14 15 Less eQmial Ind Less transfer Redistribution Subtotal Dud loads 30% 28% U 0 4451 133�42300/* 0 0 1501 28% 0 0 0 3472 1037 0 0 0 1782 499 room load Air required (cfm) SZ8 4508Total 167 99 2019-Sep-2010:43:30 AffERight-Suite® Unhersa12019 19.0.08 RSW8101 Page 12 h ...nets%Wdghtsoft HUAC%WALSH RES. JOHNSTON RD.mP Calc = MJB Front Doorfaces: E ' 1 iE.g � Duct System Summary Job: "Wlrigl��so y • � Date: Sep 20, 2019 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34M Phone: 772466-6799 Fax 772466-6796 Email: OUICKCALCS@AOL.COM Far. WALSH RESIDENCE, DAVE GOLDEN HOMES, INC. JOHNSTON ROAD, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1550 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1550 cfm 215 ft Name Design (Btuh) Htg (cfm) CIg (cfm) Design FIR Diam (in) H x W (In) Duct Matl Actual Ln (ft) Fig.Egv Ln (ft) Trunk BATH 2 h 1321 49 23 1.000 5.0 Ox 0 VIFx 55.6 155.0 st6 BATH 3 h 153 6 5 1.000 4.0 OKI) VIFx 16.6 115.0 st2 BEDROOM 2 h 4508 167 99 1.000 7.0 OKI) VIFx 59.1 155.0 st6 BEDROOM 3 h 4508 167 99 1.000 7.0 Ox0 VIFx 55.6 155.0 st6 BEDROOMS LIVING c 2376 12 103 1.000 7.0 Ox0 VIFx 40.2 135.0 St5 FOYER c 1937 71 84 1.000 6.0 Ox0 VIFx 14.5 115.0 st2 GREAT ROOM c 3285 86 142 1.000 8.0 Ox0 VIFx 22.7 115.0 st1 GREAT ROOM -A c 3285 86 142 1.000 8.0 0x0 VIFx 41.0 135.0 st4 KITCHEN c 2452 47 106 1.000 7.0 Ox0 VIFx 21.4 115.0 st3 KITCHEN -A c 2452 47 106 1.000 7.0 Ox0 VIFx 14.8 115.0 st3 LAUNDRY h 3890 144 78 1.000 6.0 Ox0 VIFx 18.4 115.0 st3 LINEN h 144 5 3 1.000 4.0 Ox0 VIFx 17.0 115.0 st3 M BATH h 2422 90 37 1.000 5.0 Ox 0 VIFx 41.6 135.0 st5 •TOILET h 41 2 1 1.000 4.0 Ox0 VIFx 38.4 135.0 st5 •wlc h 221 8 8 1.000 4.0 0x0 VIFx 37.4 135.0 st5 MASTER BEDROOM C 2680 110 116 1.000 7.0 Ox0 VIFx 43.5 135.0 st4 MASTER BEDROOM-B c 2680 110 116 1.000 7.0 Ox0 VIFx 45.0 135.0 st4 OFFICE c 2364 62 103 1.000 7.0 OxO VIFx 16.6 115.0 st2 PANTRY h 49 2 2 1.000 4.0 Ox0 VIFx 17.3 115.0 st3 SUN ROOM h 3389 126 82 1.000 6.0 OxO VIFx 28.0 115.0 st1 SUN ROOM -A h 3389 126 82 1.000 6.0 OxO VIFx 27.1 115.0 st1 wlc 2 h 91 3 3 1.000 4.0 Ox 0 VIFx 60.4 155.0 st6 WIC h 578 21 8 1.000 4.0 Ox0 VIFx 1 55.4 1 155.0 1 st6 _ RC� :s [A 2014Sep-20 10:43:32 1r,1 ,ID ry RightSuile® Unimmal 2019 19.0.08 RSU08101 Page 1 ACCA... nets\Wrightsoft HVACNWALSH RES-JOHNSTON RD.MP Calc=MJS Front Doorfaces: E Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam pn) H x W (in) Duct Material Trunk st6 Peak AVF 409 232 1.000 925 9.0 0 x 0 VinlFlx sty st5 Peak AVF 520 381 1.000 954 10.0 0 x 0 VinlFlx st2 st2 Peak AVF 659 573 1.000 839 12.0 0 x 0 VinlFlx s1:4 Peak AVF 307 375 1.000 688 10.0 0 x 0 VinlFlx st1 st1 Peak AVF 644 682 1.000 868 12.0 0 x 0 VinlFlx st3 PeakAVF 246 295 1.000 669 9.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR(fpm) Veloc Diam (n) H x W (in) Stud/Joist opening (in) Duct Matl Trunk rb1 Ox0 1550 1550 0 0 0 0 Ox 0 VIFx 2019-Sep-2010:43:32 _ Wfjl9Ht5+DFt^ :• •��--. •T� RighlSuOe® Universa12019 79.0.08 RSW8101 Page 2 ACCA... nets\WdghtsoftHVAC\WALSHRES- JOHNSTON RD.Wup Calc=MJB FrontDootfaces: E