HomeMy WebLinkAboutSET-UP - INSTALL PLANSMODULE TYPE, DIMENSIONS & WEIGHT
,NUMBER OF MODULES = 25 MODULES
MODULE TYPE =. LG 320 N1C-A5 (320W) MODULES
WEIGHT = 39.68 LBS / 18.0 KG.
MODULE DIMENSIONS = 66.38" x 40.0" = 18.44 SF
UNIT WEIGHT OF ARRAY = 2.15 PSF
3/4" PVC CONDUIT RUN
(N) SOLADECK
N
m s
s
4f I
00
M
CO
N
Lo
GENERAL INSTALLATION PLAN NOTES:
(N) AC DISCONNECT
T uci
1) ROOF ATTACHMENTS SYP RAFTERS SHALL BE INSTALL
(N) PV METER (IF REQUIRED)
SHOWN IN SHEET S-02 AND AS FOLLOWS FOR EACH WIND ZONE:
(E) UTILITY METER
(N) ENPHASE IQ COMBINER
WIND ZONE 1: 4'-0" O.C.
BOX
(E) MAIN DISTRIBUTION PANEL
WIND ZONE 2: 2'-0" O.C.
WIND ZONE 3: 2'-0" O.C.
SEE SHEET S-02 FOR SUPPORTING CALCULATIONS.
CB PVM
2) EXISTING RESIDENTIAL BUILDING IS AN ASPHALT SHINGLE
ACD MDP
ROOF WITH MEAN ROOF HEIGHT IS 15 FT AND SYP 2X4 WOOD
-LUC
ST.LUCIE COUNTY
ROOF RAFTERS SPACED 24" O.C. EXISTING ROOF SLOPE FOR
—PLAN REVIEW I _
SOLAR SYSTEM RETROFIT IS 22.6 DEGREES. CONTRACTOR TO
FIELD VERIFY AND SHALL REPORT TO THE ENGINEER IF ANY
DISCREPANCIES EXIST BETWEEN PLANS AND IN FIELD
BLDG:
CONDITIONS
DATE:
I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN
ELEC �A�^�,,J���//��,
C�46�1�I
COMPLIANCE WITH FBC: RESIDENTIAL 2017, CHAPTER 3. BUILDING
DATE:'.42iarvy
//
41-011
STRUCTURE WILL SAFELY ACCOMMODATE CALCULATION WIND
PLUMB:
I
LATERAL AND UPLIFT FORCES, AND EQUIPMENT DEAD LOADS. '
(74) PV ATTACHMENT @ 24" & 48"
O.C.
(N) (25) ENPHASE IQ7-60-2-US
MICROINVERTERS
24" SETBACK AS PER
COUNTY REQUIREMENTS
621-711
LG 320 N1C-A5 (N) IRONRIDGE XR 10 RAIL (TYP.) J
(320W) MODULES
ROOF PLAN & MODULES COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
S-01 SCALE: 1/8" = 1'-0"
ROOF#1
TILT - 22.6"
AZIM. -180"
ON
ARRAY & ROOF AREA
CALCIS (ROOF #1)
ARRAY AREA = 405.68 SQ. FT.
-St ROOF FACE AREA = 802.53 SQ. FT. ♦♦@�
405.68 / 802.53 = 50.554% OF ROOF `♦t
-..,t FACE AREA COVERED BY ARRAY
DESCRIPTION (ROOF #1) = *r
9 ROOF TYPE ASPHALT SHINGLE
ROOF TILT -22.6" r�,
ROOF AZIMUTH - 180" _TI �Q •,
—� ROOF #2 RAFTERS SIZE - Z X4" @ 24" O.C.
4 -0 TILT-22.6' 0
AZIM.-180' ARRAY & ROOF AREA z
mW CALC'S (ROOF #2)
ARRAY AREA = 55.32 SQ. FT.
ROOF FACE AREA = 263.79 SQ. FT.
55.32 / 263.79 = 20.97% OF ROOF D
FACE AREA COVERED BY ARRAY /u
4'-011
DESCRIPTION (ROOF #2) Ij
ROOF TYPE -ASPHALT SHINGLE
1 ROOF TILT -22.6"
O ROOF AZIMUTH - 180'
RAFTERS SIZE - 2"X4" @ 24" O.C.
2 -0,
SCANNED
O LEGEND BY
UM - UTILITY METER St. Lucie COUnfi
1
JB -JUNCTION BOX
-011 INv -INVERTER
Aco -AC DISCONNECT
WIND ZONE 3(TYP.) pM - PRODUCTION METER
WIND ZONE 2(TYP.) Mop - MAIN DISTRIBUTION PANEL
HD3 WIND ZONE 1(TYP.)
O ❑ -VENT, ATTIC FAN (ROOF OBSTRUCTION)
ada"d 5 ea O - PV ROOF ATTACHMENT
S30IS
S30 � -RAFTERS
1N0 - CONDUIT
'b;i2i 71omiDS 'NIA � S CB -COMBINER BOX
Castillp
ElImpfffemn-
DLSw MFD TO FSRMIT*
CASTILLO ENGINEERING
SERVICES, LLC
wpx2.!T
Z25 W. STATE ROAD 434.
SUITE 111
LONGWOOD, FL 32779
ML (Q7) 26"zsM
ERMCPAIES E. CPSTILLO-FL M 525.
REVISIONS
DESCRIPTION
DATE
REV
PROJECT INSTALLER
Ott .1
TOP
N 52
t AT P �4
Ptt,NAI. �.♦♦♦
W
U
v
W Q Co
QU oLL
Z z ui
Qo �Qf
U� Jw
g W Qa
O
LoLL
SHEET NAME
ROOF PLAN &
MODULES
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
S-01
Symbols:
��^� Sheetwhere
Section .............. section is located
Detail ID Letter
Elevation........... Sheetwhere
x-xx section is located
Detail ID Letter
Detail ................ x
x_ Sheetwhere
section is located
Detail ID Letter
Detail ......... — —~Area to be enlarged
(Enlarged Planlanjx"
Sheet where
section is located
Keyed Notes .......... 1 Keyed note designation
on applicable sheet
Ground Terminal....- O
Grounding Point/rod....
Solar Panel ......... or 00 Module with Source
Circuit number
Combiner Box.......... CB
DC Disconnect.......... DCD
Main Distribution MDP
Panel ......................
Fuse ......................
Overcurrent Breaker .. �.—
Inverter ....................
Transformer .............
Automatic ............... ATs
Transfer Switch
Abbreviations:
AC
Alternating Current
APPROX
Approximate
AWG
American Wire Gauge
CB
Combiner Box
DC
Direct Current
DCD
Direct Current Disconnect
DISC
Disconnect
(E)
Existing
EL
Elevation
EQ
Equal
JB
Junction Box
MCB
Main Combiner Box
MFR
Manufacturer
MIN
Minimum
MISC
Miscellaneous
(N)
New
OCPD
OverCurrent Protection Device
POCC
Point Of Common Coupling
PV
Photovoltaic
SF
Squarefoot/feet
STC
Standard Test Conditions
TBD
To Be Determined
TYP
Typical
VIF
Verify In Field
WP
Weather Proof
System Description
This system is a grid -tied, PV system, with PV generation consisting of
25 LIS 320 N1C-A5 (320W) MODULES with a combined STC rated do output power of
8,000 W. The modules are connected into 25 ENPHASE IQ7-60-2-US
MICROINVERTERS. The inverter has electronic maximum power point tracking to
maximize energy captured by the PV modules. The inverter also has an internal
ground fault detection and interruption device that is set to disconnect the array in the
event that a ground fault that exceeds one ampere should occur. The inverter has DC
and AC disconnect integrated system and labels are provided as required by the
National Electric Code
PV Modules .......
Microinverters—* O
Junction Point of
Box Utility
Connection
Utility Meter
When the sun is shining, power from the PV array is fed into the inverter, where
it is converted from DC to AC. The inverter output is then used to contribute to the
power requirements of the occupancy. If PV power meets the requirements of the
loads of the occupancy, any remaining PV power is sold back to the utility. When
utility power is available, but PV power is not available, building loads are supplied by
the utility.
The inverter meets the requirements of IEEE 1547 and UL 1741. This means that
if it detects a loss of utility power, it will automatically disconnect from the utility.
When utility voltage is restored, the inverter automatically reconnects to the utility
grid after verifying utility voltage and frequency stability.
On a day with average Florida sunshine, this system outputs 34.15 kWh per day
on site.
COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
Castillo (�
Engineering
o 510H10 10 PI&MITf
CASTILLO ENGINEERING
SERVICES, LLC
WA 421%5
2525 W. STATE ROAD 434.
SUITE 111
LONGWOOD, FL 32TJa
ME (4 nab 2515
ERMOC MSEL Muo.RPEUM
REVISIONS
DESCRIPTION
DATE
REV
PROJECT INSTALLER
SIBn3Iu..M
CAST .,
�\CE��S,� O
No 2H 0
JT
NAL
U�
v
0 W Q J
Q U o "-
1- z z W
QLLJ
0 'W
U cn _ w
W Qa
Q� oW
0)o
to LL
SHEETNAME
SYMBOLS &
SYSTEM
DESCRIPTION
SHEET SIZE
ANSI B::1
11" X 17"
SHEET NUMBER
A-01
MODULE TYPE, DIMENSIONS & WEIGHT
NUMBER OF MODULES = 25 MODULES
MODULE TYPE = LG 320 N1C-A5 (320W) MODULES
WEIGHT = 39.68 LBS / 18.0 KG.
MODULE DIMENSIONS = 66.38" x 40.0" = 18.44 SF
UNIT WEIGHT OF ARRAY = 2.15 PSF
3/4" PVC CONDUIT RUN
(N) SOLADECK
(N) AC DISCONNECT
(N) PV METER (IF REQUIRED)
(N) ENPHASE IQ COMBINER
BOX
� N \
CV
Q
In
P
w s
s
4.� O
4 -0"
50 �
M (74) PV ATTACHMENT @ 24" & 48"
O.C.
(N) (25) ENPHASE IQ7-60-2-US
MICROINVERTERS
ACD
24" SETBACK AS PER
COUNTY REQUIREMENTS
62'-711
LG 320 N1C-A5 (N) IRONRIDGE XR 10 RAIL (TYP.)
(320W) MODULES
ROOF PLAN & MODULES COPYRIGHTED BY CASTILLO
S-01 I SCALE: 1/8" =1'-0" ENGINEERING SERVICES, LLC
ROOF #1
TILT - 22.6°
AZIM.-180°
1w
GENERAL INSTALLATION PLAN NOTES:
1) ROOF ATTACHMENTS SYP RAFTERS SHALL BE INSTALLED AS
SHOWN IN SHEET S-02 AND AS FOLLOWS FOR EACH WIND ZONE:
(E) UTILITY METER
WIND ZONE 1: 4'-0" O.C.
(E) MAIN DISTRIBUTION PANEL WIND ZONE 2: 2'-0" O.C.
WIND ZONE 3: 2'-0" O.C.
SEE SHEET S-02 FOR SUPPORTING CALCULATIONS.
2) EXISTING RESIDENTIAL BUILDING IS AN ASPHALT SHINGLE
ROOF WITH MEAN ROOF HEIGHT IS 15 FT AND SYP 2X4 WOOD
ROOF RAFTERS SPACED 24" O.C. EXISTING ROOF SLOPE FOR
SOLAR SYSTEM RETROFIT IS 22.6 DEGREES. CONTRACTOR TO
FIELD VERIFY AND SHALL REPORT TO THE ENGINEER IF ANY
DISCREPANCIES EXIST BETWEEN PLANS AND IN FIELD
CONDITIONS
I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN
COMPLIANCE WITH FBC: RESIDENTIAL 2017, CHAPTER 3. BUILDING
4'-011
STRUCTURE WILL SAFELY ACCOMMODATE CALCULATION WIND
LATERAL AND UPLIFT FORCES, AND EQUIPMENT DEAD LOADS.
ARRAY & ROOF AREA
-d' CALC'S (ROOF #1)
ARRAY AREA = 405.68 SQ. FT.
->,
:..;:.
ROOF FACE AREA = 802.53 SQ. FT. Q�
405.68 / 802.53 = 50.554% OF ROOF
FACE AREA COVERED BY ARRAY
DESCRIPTION (ROOF #1)
-9 ROOF TYPE -ASPHALT SHINGLE rn ZO
114,
ROOF TILT-22.6°.
ROOF AZIMUTH - 180° -TI
ROOF #2 RAFTERS SIZE - 2"X4" @ 24" O.C. 0
-�
4'-0"
TILT-22.6°
AZIM. - 180° ARRAY & ROOF AREA z
CALC'S (ROOF #2)
ARRAY AREA = 55.32 SQ. FT.
ROOF FACE AREA = 263.79 SQ. FT.
D
55.32 / 263.79 = 20.97% OF ROOF
FACE AREA COVERED BY ARRAY /U
4'-O"
DESCRIPTION (ROOF #2)
ROOF TYPE -ASPHALT SHINGLE
ROOF TILT - 22.6°
" O ROOF AZIMUTH - 180°
RAFTERS SIZE - 2"X4" @ 24" O.C.
11,
WIND ZONE 3(TYP.)
WIND ZONE 2(TYP.)
WIND ZONE 1(TYP.)
LEGEND
Q - UTILITY METER
JB -JUNCTION BOX
INV I -INVERTER
ACD -AC DISCONNECT
PM - PRODUCTION METER
MDP - MAIN DISTRIBUTION PANEL
O ❑ -VENT, ATTIC FAN (ROOF OBSTRUCTION)
O - PV ROOF ATTACHMENT
— -RAFTERS
CONDUIT
CB - COMBINER BOX
Castillo
Engineering
CE 51GNE0 TO Pl4MIT•'
CASTILLO ENGINEERING
SERVICES, LLC
conttseaas
M5 W. STATE ROAD 434.
SURE 111
LONGWOOD. FL 32]➢9
TEL:(407)Z89 76
ERMCCMiES E. CA UO-FL PE 525M
REVISIONS
DESCRIPTION
DATE
REV
—3
PROJECT INSTALLER
�S...• sR O
S a6
NO 52
5 0
TqT
.16�y ee
00
O m
10� W Q CO
QU pLL
z W Z W
Q 0 X of
LU UQ J W
i W as
Q F-
o C�_
°) O
LID LL
SHEET NAME
ROOF PLAN &
MODULES
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
S-01
2
S-02
SOLAR MODULE
SEE (2/S-02) FOR
ENLARGED VIEW
I
(N) GROUNDING
END/MID CLAMP
(N) IRONRIDGE XR 10
RAIL
QBLOCK, CLASSY
A360.1 CASTAL, MIL
(E) ASPHALT
SHINGLE ROOF TYP.
(N) IRONRIDGE XR 10
RAIL
(E) 2" X 4" RAFTERS @ 24" O.C.
1 I_ QMSC: CLASSIC COMPOSITION MOUNT
S-02
QMSC: CLASSIC COMPOSITION MOUNT
(ENLARGED SECTION VIEW)
SCALE:NTS
SCALE - 1" = V-0"
(N) CAP SCREW, HEX
HEAD, 5/16-18x1" UNC-2A,
18-8 SS
(E) ROOF SHEATHING
(E) 2" X 4" RAFTERS @ 24" O.C.
(1) 5/16"DIA. X 3"MIN.
EMBEDMENT LAG SCREW
AT EACH ATTACHMENT POINT
INTO EXISTING FRAMING
COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
120
1 115: 130
( 1 Vtl 'ax uaMta atSiP, } M Rat "
Y3M on!M]
ft (19) abar far Bosse, <
is
rraad
1
�4x
GSM -
w1W0
z2 tfa fot ramnti a.i m, [ 169
_
' 3 IpSnJs;SSA soutil "S'w MSWe the t -.
..
INt totam abll mt tb taut vM sp Itea s
•W ..
t at ea m
. .4 . rgyritNiebtesiln,
prob5111q,M laeeOSnti Sn.56 Yes
(Annuil E'<teeanie ao4sDility a 0¢1N
Int >m aucl k
4
FIGURE
Wind Speed Ult(mph)
EY61010
Risk Category.
offifiIIIIIIIIIIII_
Wind Speed ASD(mph)
130 IN
Exposure Category
tCw
Mean Roof Height (ft) -1111191-51111
Roof Slope (degrees)
5757
Module Area (sq ft)
20
Kzt
1
Height Adjustment Factor,A
1 1.21
Roof Zone
_ Pnet(30)_;__
1
16
27
2
16
44:6
3
16
67
P_net=B q_ztP_(net(30))
Roof Zone
-.. Poet '
1
19.36
-32t67
2
1 19.36
E 3.966
3
1 19.36
-81D7
226
Maximum Uplift per
-fastener-Wind Zone 1
3594
Per American Wood Council -
NDS Max Withdraw Load for
476
5/16" LAG with 2.5"
Embedment
"Roof attarhements w 2rails at L4jftO/C
Maximum Uplift per
"fastener Wind Zone 2
296.8
PerAmerican Wood Council -
NDSMax Withdraw Load for
476
5/16" LAG with 25"
Embedment
`Roof attachements w 2 rails at: I I ft O/C
Maximum Uplift per
`fastener Wind Zone 3
445.9
Per American Wood Cound I -
NDS Max Withdraw load for
476
5116" LAG with 2.5"
Embedment
'Roof attachements w 2 rails at: L2 f ft O/C
Castillo
Engineering
DESIGNED TO PtRMITO
CASTILLO ENGINEERING
SERVICES, LLC
CONtl265 5
2925 W. STATE ROAD 434,
SUITE 111
LONGWOOD. FL =79
lEL(L07J28 TS
Efl OC1iATESE GMMO-FLPES2.
REVISIONS
DESCRIPTION
DATE
REV
PROJECT INSTALLER
OCT 1 9
`tt11111A1►p/dI
s
No 5 590
st
T E
W
U �
v
LLI Q
Q U W LL.
F Z LLI
Z
Q X of
Q LLI Q IL
Q o w
O) 0
Lf) LL
SHEET NAME
STRUCTURAL
ATTACHMENT
DETAILS
SHEET SIZE
ANSI B
11" X 17"
SHEETNUMBER
S-02
Q CABLE
SOLADECK
IV, NEMA 3R
LISTED
(N) 125A ENPHASE IQ COMBINER 3
(X-IQ-AMt-240-3) [WITH UPTO (4)
2-POLE BREAKERS AND ENVOY
COMMUNICATION GATEWAY]
I
I
I
I
I
I
I
L
(2) #10 AWG TH WN-2 f Red
(2) #10 AWG THWN-2 - Black
EGC #10 THWN-2
IN 3/4" PVC OR EMT CONDUIT
RUN
ELECTRICAL LINE DIAGRAM
E-01 I SCALE: NTS
(N) PV METER
(IF REQUIRED)
000
0 0
(3) #8 AWG THWN-2
(1) #10 AWG THWN-2 GND
IN 3/4" PVC OR EMT CONDUIT
RUN
SOLAR ARRAY (8.0 KW -DC STD) TOTAL
25 LG 320 N1GA5 (320W) MODULES
47" (01) STRING OF 13 MODULES
(01) STRING OF 12 MODULES
NOTE:
SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE
REQUIREMENTS OF THE NEC 2014, AND THOSE SET FORTH BY THE
FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING MAXIMUM
NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OF MODULES PER
STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER AND MODEL
NUMBER, INVERTER MANUFACTURER AND MODEL NUMBER, AS
APPLICABLE.
ENPHASE IQ7-60-2-US
MICROINVERTERS
PV MODULES
HOT TAP USING POLARIS TAPS OR
INSULATION PIERCING
(N) AC DISCONNECT:
24OV, 60AMP, FUSED
NEMA 3R, UL LISTED
WITH 40A FUSES
(3) #8 AWG TH WN-2
IN 3/4" PVC OR EMT CONDUIT
RUN
TO UTILITY GRID
OBI-DIRECTIONAL
UTILITY240V
1-PHASE, E. 240V
(E) MAIN DISTRIBUTION
PANEL, 250A RATED, 240V.
(E) MAIN BREAKER
200A/2P, 240V.
EXISTING GROUNDING
ELECTRODE SYSTEM
COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
Castillo r(k
Engineering
OESIGNEP TO PEWIT.
CASTILLO ENGINEERING
SERVICES, LLC
m 90m
2925 W. STATE ROAD 4M,
SUITE 111
WNGWOOD, FL 32A9
rEL: (4oi1 zeN
EftMCCRPTES E. fA$iILLO - FL PE 52550
REVISIONS
DESCRIPTION
DATE
REV
PROJECT INSTALLER
OCT
CAS? 4Al
®O j9nat •�,
NO 2590
9.
TE O
� S, R l ••'�
p� / .N
ROJECT 909110
W
U rn
V
LLI Q _J
Q U o LL.
Z W Q U
Q X 0_
QW ¢a
o Q O�
rnU
LL
SHEET NAME
ELECTRICAL
LINE DIAGRAM
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
E-01
AC CONDUCTOR AMPACITY CALCULATIONS:
FROM ROOF TOP SOLADECK TO LOAD CENTER
MDDDLE MANUFACTURER
LG
_
MODULE MODEL _
LG NEON2 32OW
INVERTER MANUFACTURER.. _
ENPHABE
INVERTER MODEL _
ENPHABE IQ 7
MODULES/BRANCH CIRCUIT 1 _
13
MODULEB/BRANCH CIRCUIT 2. _
12
TOTAL ARRAY POWER' (TGWU _ _
8.013
SYSTEM. AO1 VOLTAGE
24CV 1-PHASE
OESIGN TEMPERATURE
M IN. AMBIENT TEMP. 'F
32
MAX. AMBIENT TEMP.'F
1.17
CALCULATED MAX. VOC
0 N 44
CALCULATED MIN VMP
0 26_
CONDUIT FILL
NUMBER, OF CONDUITS
_
1
AMPAGITY' CALDU LTIONS'
AC CONDUCTOR AMPACITY CALCULATIONS:
FROM AC COMBINER BOX TO MSP
_ MODULEPROPERTIES,
VDc
_ 40.E1I_
ISO
10'.19.._
VMPP
33.3
IMP
9.62
TO VDD
-0.27%/'C_
ITO VMP
1'_-0.3796/'C
PMP
320.❑
NCCT
1 45'C_
INVERTER I PROPERTIES"
OUTPUT VOLTAGE
'240 L-L 1-PH
MAX INPUT DC VOLTAGE
48 NOC
OPERATING RANGE
IS- 45VDC
MPPT VOLTAGE RANGE
27 - 37'VDC_ _
START VOLTAGE
22 VDC
MAX INPUT POWER
_350 WOO___
CONTINUOUS AC POWER
240 VA
1.25 X
913'C
AMBIENT
TEMP
CONDUIT
FILL
DERATED
MAXIMUM CIRCUIT
CIRCUIT
MAX AMPS
AWG
MAX AMPS
AMPACITY
TEMP OF
DERATE
FILL
DERATE
AMPACITY
BREAKER
CIRCUIT
13.0
I. 6.3
#10
40
130 _._
0.76
4
0.8
24.32
�.
20_A
CIRCUIT 2
12.0
1 S.a
#1 O
40
ISO
0.76
4
0.S
24.32
20 A
AC CEP.G.T,R
25.0
31.3
#a
55
95
3
1
S2-B
_ A
PA..L OUTPUT
D.96
40
M AXIMUN CIRCUIT VOLTAGE DROP 1 2%
VOLTAGE DROP CALCULATIOMB
CIRCUIT
AWG
CIRCULAR
MILLS
I
V
MAX
LENGTH.
CIRCUIT 1
# 10
103B13
13.0
240
1 4,9. FEET
CIRCUIT 2
# 1 ❑
113380
121.13
24D
1 e)1 F_E7T
COMBINER PANEL OUTPUT
#B'.
16510
25.0
240
1 23 FEET
NOTES
TEMP DERATE BASED ON NEC TABLE 310.15(8)(2)(A)
CONDUIT FILL DERATE BASED ON NEC TABLE 31. 0.1 5(8)(31(A)
MAXIMUM VOC CALCULATED USING MODULE MANUFACTURE TEMPERATURE COEFFICIENTS PER NEC 690.7(A)
UNLESS. OTHER WISE SPECIFIED, ALL WIRING MUST BE THHN OR THWN-2 COPPER
ALL WIRE SIZES LISTED ARE THE MINIMUM ALLOWABLE
I IN ANY CELL INDICATES THAT THE SYSTEM IS SAFE AND COMPLIES WITH NEC REQUIREMENTS
IN ANY CELINDICATES A POTENTIALLY UNSAFE CONDITION
- INFORMATIL ON INPUT BY SYSTEM DESIGNER
INFORMATON OBTAINED FROM MANUFACTURER DATASHEETS
COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
ELECTRICAL NOTES
1. ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND
LABELED FOR ITS APPLICATION.
2. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
DEGREE C WET ENVIRONMENT. THE TERMINALS ARE RATED FOR
75 DEGREES "C".
3. THE WIRES ARE SIZED ACCORDING TO NEC 110.14".
4. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS
SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS
POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
5. WORKING CLEARANCES AROUND ALL NEW AND EXISTING
ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
6. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.
CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
SUPPORTS, FITTINGS AND ACESSORIES TO FULFILL APPLICABLE
CODES AND STANDARDS.
7. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS
ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM
ACCORDINGLY.
8. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND
READILY VISIBLE.
9. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
MANUFACTURER'S INSTRUCTION.
10. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY -IN LUG.
11. THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE.
12. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL
PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE
ENTRANCE.
13. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
14. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
15. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE
310.10 (D).
16. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE
FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
ENPHASE IQ7-60-2-US MICROINVERTER
Input Data (DC)
Recommended Input Power (STC)
235-35OW +
Maximum Input DC Voltage
48V
Peak Power Tracking Voltage
27V-37V
Operating Range
16V-48V
Min. / Max. Start Voltage
22V / 48V
Max DC Short Circuit Current
15A
Output Data (AC)
Maximum Output Power
240W
Nominal Output Current
1.OA
Nominal Voltage / Range
240V/211-264V
Nominal Frequency/ Range
60 Hz
Extended Frequency / Range
47-68 Hz
Power Factor at rated power
1.0
Maximum unit per 20A Branch Circuit
16 (240 VAC)
Castillo
Engineering
DESIGNED TO PERMIT'
CASTILLO ENGINEERING
SERVICES, LLC
coA#..
2925 W. STATE ROAD 434,
SURE 111
LONGWOOD, FL 32779
TEL(4N).9-.75
BGnocNAlEs E cnsn uo - N vl[ ssssD
REVISIONS
DESCRIPTION
DATE
REV
PROJECTINSTALLER
OCT 17 2019
4i6'N1°Mw
01l1 IABIIBiP
01� Sig 'Newt!,•• 1/`
' \CE/y
1t•• 0 52590
13
• >}
ATE F
0
AN R
PRO EE •• J� L •\ `%
'fill I00
W
U rn
O IT
LU Q (Y)
QU iE 0 LLLL.
Z Z W Q U
Q XW
U to LLI
J EL
Q o of
rn O
LL
SHEET NAME
WIRING
CALCULATIONS
SHEET SIZE
ANSI B
111E X 1711
SHEET NUMBER
E-02
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: NEC 690.17(E), CB
LABEL LOCATION:
CONDUIT, COMBINER BOX
(PER CODE: NEC690.31(G)(3)(4) & NEC 690.13(G)(4)
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(4))
ADHESIVE FASTENED SIGNS:
• THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT
WHERE IT IS INSTALLED.
• WHERE REQUIRED ELSEWHERE IN THIS CODE; ALL FIELD
APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD
COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].
• ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF
PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER
RESISTANT [IFC 605.11.1.31
(PER CODE: NEC690.54)
WARNING
VVERTER OUTPUT CONNECTION DO NC
2ELOCATE THIS OVERCURRENT nFVTCF
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(7))
[Not required if panelboard is rated not less than sum of ampere ratings
of all overourrent devices supplying ft]
LABEL LOCATION:
COMBINER BOX
(PER CODE: NEC690.52)
LABEL LOCATION:
AC DISCONNECT, DC DISCONNECT, POINT OF
INTERCONNECTION
(PER CODE: NEC690.56(C))
01
ime
COPYRIGHTED BY CASTILLO
ENGINEERING SERVICES, LLC
Castillo
Engineering
DESIONEP TO P[¢MITs
CASTILLO ENGINEERING
SERVICES, LLC
CV28%5
Z25 W. STATE ROAD 434,
SURE111
LONGWOOD, FL 32779
TFl:(48712e 76
FAMOCRATFSEG MW-RPEQ2
REVISIONS
DESCRIPTION
DATE
REV
PROJECTI STAL R
``o`a��eeleuBeBp
•.�' 1riN. ✓�
5�.0 e
N
2 0
Yt
T T OF Z
B11 Itle
Of
W
U 't
W Q J
Q U of LL
Z w Q LLT
LL
Q 0 X of
UU) Jw
gw Qa
Q� ory
0)O
LOW
SHEET NAME
SYSTEM
LABELING
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
E-03
® LG
Life`s Good
LG NeON°2
THE
1 C-A5
PANEL OF THE FUTURE AVAILAB LE=TODAY
_---The LG NeONO 2 has seen many improvements from longe-rwarranties and higher efficiency to strongerframes and better
wind loadin This panel is ideal for homes seeking a visually pleasing solar panel and for where future system expansions
are considered e.g:: to incorporate battery storage in years to come.
The LG NeON®&Is with their double sided. cells and CELLO technology absorb light from the from: and the bark of the
- module. This technology sets anew standard for innovation and was recognised with the 2015Photovoltaic Innovation
Award atthe intersolarindustry Eventin Germany. LG also won the 20161ntersolaraward for ournew NeON BiFaciairange.
--- Great Visual APP Appearance
`
�J LG NeONO 2panels have been designed with appearance:
in mind Their black ceU% black: frames and thinnerwire
bl isbars give an aesthetic* pleasing uniform black
appearance. Your home deserves the LG NeOW 2
��- More Power per Square Metre
LG NeONO 2§ 320W are a similar physiml Sim to marry
conventional 270W panels.Thls means with the LG
NeONO 232OW you get 18.51%mom electricity per
square metre than a 270W panel- So you cart install
mom kW of solar on your roof with the LG NeONO 2.
�ad�maae�K«ea
!' fl � anA U/amnw
Cvofvaoom
2C 6121SD:Cfi1J30-1/-;OL1J03
ffC 61]01(5ffiM¢tCmosmnTest)
MC62716(AmnahaTest)
IMW kFire Wong
GEC
iPmduRWamaray
15Yemsr Ill2019
OutputVJaaniyNPmaT.
' p lnaearsesez)Arreriny�ossrPa,o.aayr�lM�lmefix6,rssyea�s
Tem erasure Characcensbc,
INOCT -
4533T
IVPt
1 4L27Wc
(IM -
- I om3
Current —Vole characteristic, at various imediarm levels characteristics a various imadiarm levels
is _
vdta m
eurrera-Voldne characteristic, a[variousoxll TemaardNl6
15 Years Product Warranty (Parts &Labour) �
The LG product warranty is 5 years longer than many
competitors Standard 10 years and covers 15 years. Y
The Warranty is provided by LG Electronics Australia
and New Zealand. The warranty includes replacement
labour and transport
•_ ,4,6si� Improved 25-Year Performance Warranty
The initial degradation of the module has been improved
from 3%to -20/, in the 1 styear and the annual rate of
degradation has fallen from-0.7%lyear to -0.5%/year
thereafter. This brings an 86%waranted output after 25
years, compared to 80.2%for many standard panels.
wwwagenergy.co.nz
Temper M)
la Elx a Au5m6aftylad
temC
LG finlar BomC556TYp
3 wb2)830 D38 EasternC NSW 2]66
Pk(02)88054038
Ofes Good FM lsolarsalss@Iie=o
Web1q«ie,y.
151C(swWaNT rmida�on$Imtama 1000W/m'.M T leratwe25'SAM I.i
TheraneP�eprxerau[mrt"smeawredaM determired b, W Fectmn¢at 1.s a ab dsaetiart
Electrical Pmoerdes (NOCT-i
MMWeType
_.. 330W _.
_.._
�Mawmwp Parer Pnw CM _.
236
MPP VoInge VmppM
T
(MPPCa I.Iip(A) _
7.76
I Open ChvdtVologeVoctle _
37.9
IShortGwitGmentlsc (A)
as
'xoe'r(xmemaopeau�9enlrm�ss�F6�aaa� eouwim�.amu.,nm�Pem.ezo-4.,aa�e 1 rare
Dimensions (mm)
F I I
z�
WEl.N.Irc Prodietspedrwdwrsarewhject mdwye r
SalarBusiness Oirision v 5.1;5's m. L:
TVM&tilQmgWestvnTme(11F, Da[rol(1018 �Y
128,Y Eam,Yemgde��oglL /L�
5Qd4Nmsxtrte Copyright 02018 W ett0 m
—t,.M91^baVpuvness Aanghtzre.e
Castillo
Engineering
Gf510NE0 TO Ptt MIT•
CASTILLO ENGINEERING
SERVICES, LLC
COAT
2925 W. STATE ROAD 434,
SUITE 111
LONGWOOD, R 32779
rEL'.t4U)avB zsr5
ERMOLPATE6 Ef 1-1-0-FL PE 525W
REVISIONS
DESCRIPTION
DATE
REV
PR
I L
�amA"TcsPoMyAn
�`,oeteeeaee ss
•a • �1196g
�i O o�
No
52590
T}
TE
W
U �
v
W Q th
Q
U oLL
Z
LLl Q U
Q
2 X Of
Q
LU Q
Q
O Cr
O)O
Ln LL
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
111I X 17"
SHEET NUMBER
DS-01
Data Sheet
Enphase Microinverters
Region: US
Enphase
1Q 7 and IQ 7+
Microinverters
UL
To learn more about Enphase offerings, visft enphase.com
The high-powered smart grid -ready
Enphase IQ 7 Micro' and Enphase IQ 7+ Micro -
dramatically simplify the installation process while
achieving the highest system efficiency.
Part of the Enphase IQ System, the IQ 7 and
IQ 7+ Microinverters integrate seamlessly with
the Enphase IQ Envoy-, Enphase Q Aggregator"',
Enphase IQ Battery'", and the Enphase Enlighten"`
monitoring and'analysis software.
IQ Series Microinverters extend the reliability
standards set forth by previous generations and
undergo over a million hours of power -on testing,
enabling Enphase to provide an industry -leading
warranty of up to 25 years.
Easy to Install
• Lightweight and simple
Faster installation with improved, lighter two -wire cabling
Built-in rapid shutdown compliant (NEC 2014 & 2017)
Productive and Reliable
Optimized for high powered 60-cell and 72-cell• modules
More than a million hours of testing
Class II double -insulated enclosure
UL listed
Smart Grid Ready
Complies with advanced grid support, voltage and
frequency ride -through requirements
Remotely updates to respond to changing
grid requirements
Configurable for varying grid profiles
Meets CA Rule 21 (UL 1741-SA)
*The IQ 7+ Micro is required to support 72-cell modules.
ENPHASE.
Enphase IQ 7 and IQ 7+ Microinverters
Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules
Min/Mac start voltage 22V/48V 22 V/60V
DC port
Communication, - Power Line Communication (PLC) -- - -J
Monitoring Enlighten Manager and MyEnlighten monitoring options.
Both options require installation of an Enphase IQ Envoy.
CA
FCC Part 15 Class B, ICES-0003 Class B.
This product is OL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and
NEC-2017 section 690.12 and C211-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC
.and OC conductors, when Installed according manufacturer's Instructions.
1. No enforced DC/AC ratio. See the compatibility calculator at hunss/fin olM P com/en-uStsunnnrt/mod le-comvat bility.
2. Nominal voltage range can be extended beyond nominal if required by the utility.
S. limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
To learn more about Enphase offerings, visit enphase.com v ENPHASE.
02018 Enphase Energy All rights reserved All trademarks a brands used are the property of Enphase Energy, Inc
2018-02-08
Castillo rr(�
Engineering t.r�
DESIGNED r0 pE¢MIi¢
O
CASTILLO ENGINEERING
SERVICES, LLC
o xsesxs
2925 W. STATE ROAD 439,
SURE 111
LONGWOOD. FL 32779
1e11400 zessre
EHmeCFAiEeEGSTILw-FL PE 626M1
REVISIONS
DESCRIPTION
DATE
REV
PR C
I TAL
, -
SiAnaturG 'N '
No F ••
Sp Sgo
SAT
s• <O
OF Q
1 ID P .• 1��
PRI
U �
1-0 W
U
Q CO
of
Q
LL
Z LLI
0
ZZ Ld
U
Q
X Q'
U cn
g W
J w
Qa
Q
cop
tr0 LL
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
DS-02
Data Sheet
Enphase Networking
Enphase
IQ Combiner 3
(X-IQ-AM1-240-3)
U�
LISTED
To learn more about Enphase offerings, visit enphase.com
The Enphase IQ Combiner 3' with Enphase
IQ Envoy' consolidates interconnection
equipment into a single enclosure and
streamlines PV and storage installations by
providing a consistent, pre -wired solution for
residential applications. It offers up to four
2-pole input circuits and Eaton BR series
busbar assembly.
Smart
• Includes lQ Envoy for communication
and control
• Flexible networking supports Wi-Fi,
Ethernet, or cellular
Optional AC receptacle available for PLC
bridge
• Provides production metering and optional
consumption monitoring
Simple
• Reduced size from previous combiner
• Centered mounting brackets support single
stud mounting
• Supports back and side conduit entry
• Up to four 2-pole branch circuits for 240 VAC
plug-in breakers (not included)
• 80 Atotal PV or storage branch circuits
Reliable
• Durable NRTL-certified NEMAtype
311 enclosure
• Five-year warranty
UL listed
Oa ENPHASE.
Enphase IQ Combiner 3
ACCESSORIES and REPLACEMENT PARTS (not Included, order separately)
jEnphase Mobile Connect"
(CELLMODEM-03(4G/ 12year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60
CELLMODEM01(3G/5-year data plan) microinverters.(Available in the US,Canada, Mexico, Puerto Rico, and the USVirgin Islands,
-
_CELLMODEMMl(4G based LTE-M/5-year data plan) where there is adequate cellular serviceinthe installation area.)
Consumption Monitoring' CT
CT-200-SPLIT Split core current transformers enable whole home consumption metering (+/-2.5%).
EPLC-01
Power line carrier (communication bridge pair), quantity 2
XA PLUGd26-3.
Accessory receptacle for Power Line Carrier In IQ. Combiner 3 (required for EPLC-01)
XA-ENV-PCBA-3
Replacement IQ Envoy printed circuit board (PCB) for Combiner 3
ELECTRICAL SPECIFICATIONS
System voltage 120/240 VAC, 60 Hz
Eaton BR series busbar rating 125 A'
Max. continuous current rating (output to grid) 65A
Max.fuse/cimuitrating(output) 90A
Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG) breakers only (not included)
Max. total branch circuit breaker rating (input)
80A of distributed generation/ 90A with IQ Envoy breaker included
jPmduction Metering CT -
200 Asolid core pre -installed and wired to IQ Envoy
MECHANICALDATA
_
IDimen'slons (WxHZD)
49.5 x 375 x 16.8 cm (19. ' x 14.75" x 6:63'). Height is 21:06' (53 5 cm with mounung tifackets).9
Weight
7.5 kg (16.5lbs)
Ambient temperature range
-40'Cto+46-C(40°to 115-F)
Cooling
Natural convection, plus heat shield
Enclosure environmental rating
Outdoor, NRTLcertified, NEMA type 3R, polycarbonate construction
Wire sizes
• 20AW50Abreakerinputs: 14to 4 AWG copper conductors
• 60 A breaker branch input: 4to 1/0 AWG copper conductors
• Main lug combined output: to to 2/0 AWG copper conductors
• Neutral and ground: 14to 110 copper conductors
Always follow local code requirements for conductor sizing.
INTERNET CONNECTION OPTIONS
Integrated Wi-PI - - 802.14b/g/n - -- - - -
Ethernet Optional,802.3, Cat5E(or Cat 6) UTP Ethernet cable (not included)
.Compliance, Combiner, UL 1741
CAN/CSA C22.2 No. 1071
47 CFR, Part 15, Class B; ICES 003
Production metenngrAN51 C12 20 accuracy class 0.5 (PV production)
Compliance, IQ Envoy UL 60601-1/CANCSA 22-2 No. 61010-1
• Consumption monitoring is required for Enphase Storage Systems.
To learn more about Enphase offerings, visit enphase.com
02018 Enphase Energy. All rights reserved All trademarksor brands in this document are registered bytheirrespectiveownec ENPHASE.
2018-09-13
CastlHortitik
Engineering
DESIGNED TO PERMIT'
CASTILLO ENGINEERING
SERVICES, LLC
COA#?BN5
2925 W. STATE ROAD 43Q
SUITE 111
LONGWOOD, FL 32Tr9
TEL 1407f 18M575
RIA EOCGAT aEG NUO. K PE 625O
REVISIONS
DESCRIPTION
DATE
REV
PROJECT
NO
R
W
U rn
IT
W Q (71)
Q U o LL.
Z W
W Z
Q Q X of
QW Qa
Q o of
°y U
In LIL
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
1111 X 17"
SHEET NUMBER
DS-03
A0k IRONRIDGE
Built for solar's toughest roofs.
Roof Mount System
IronRidge builds the strongest roof mounting system in solar. Every component has been tested to the limit
and proven in extreme environments.
Our rigorous approach has led to unique structural features, such as curved rails and reinforced (lashings, and
is also why our products are fully certified, code compliant and backed by a 20-year warranty.
Strength Tested
All components evaluated for superior
structural performance.
Class A Fire Rating
Certified to maintain the fire resistance
rating of the existing roof.
Integrated Grounding
UL 2703 system eliminates separate
module grounding components.
PE Certified
Pre -stamped engineering letters
available in most states.
Design Software
Online tool generates a complete bill of
materials in minutes.
20 Year Warranty
Twice the protection offered by
competitors.
XR10 Rail i XR100 Rail
—^�
A low -profile mounting rat The ultimate residential
for regions with light snov solar mounting rail.
• 6'spanningcapability 8'spanningcapability
• Moderate load capabili Heavy load capability
• Clear and black finish Clear and black finish
Clamps & Grounding O
UFOs Stopper Sleeves
iz�
Universal Fastening Objects
bond modules to rails.
• Fully assembled & lubed
• Single, universal size
• Clear and black finish
Attachments O
FlashFoot2
� r L
Snap onto the UFO to turn
into a bonded end clamp.
• Bonds modules to rails
• Sized to match modules
• Clear and black finish
Slotted L-Feet
XR1000 Rail
A heavyweight mounting
rail for commercial projects.
• 12'spanning capability
• Extreme load capability
• Clear anodized finish
Grounding Lugs
Connect arrays to
equipment ground.
• Low profile
• Single tool installation
• Mounts in any direction
Bonding Hardware
Banded Splices
All rails use internal splices
for seamless connections.
• Self -drilling screws
• Varying versions for rails
• Forms secure bonding
Microinverter Kits
Mount MIS or POs to XR
Rails.
• Bonds devices to rails
• Kit comes assembled
• Listed to UL 2703
Flush Standoffs
Flash and mount XR Rails
Drop -in design for rapid rail
Bond and attach XR Rails
Raise Flush Mount System
with superior waterproofing.
attachment.
to roof attachments.
to various heights.
• Twist -on Cap eases install
• Secure rail connections
• T & Square Bolt options
• Works with vent Flashing
• Wind -driven rain tested
• Slot for vertical adjusting
. Nut uses 7/16" socket
• 4" and 7" lengths
• Mill and black finish
• Clear and black finish
• Assembled and lubricated
• Ships assembled
Resources
Ty . Design Assistant
Go from rough layout to fully
--F engineered system. For free.
Go to IronRidge.com/design
,�„ NABCEP Certified Training
s I Earn free continuing education credits,
NABCEP; while learning more about our systems.
Go to IronRidge.com/training
Castillo
Engineering
YESIo 1010 V...'T•
CASTILLO ENGINEERING
SERVICES, LLC
W .26_
2925 W. STATE ROAD 434,
SUITE 111
LONGWOOD. FL 32779
TEL:(ao M.
ERMO MR SE.0 SPLLO-FL PE Q6W
REVISIONS
DESCRIPTION
DATE
REV
WdJEZIT
ifSTZ94
IB
n/o
2590
T
O
OF
QiQ:
•
P
e���tPI rt
t,G`'\"V
00
U �
0
w
g
Q
U
J
o LL
I---
LLLI
Z LU
Q
9
X �
Q
LU
Q DL
Q
0O Of
mo
u7 LL
SHEETNAME
DATA SHEET
SHEET SIZE
ANSI B
11" X 1711
SHEET NUMBER
DS-04
Classic Composition Mount I QMSC
Elevated Water Seal Technology®
AVAILABLE IN MILL, CLEAR ANODIZED,
AND BRONZE ANODIZED FINISHES.
SCALE I:3
No
DESCRIPTION Ott.
1 FLASHING, ITX ITX.D50",5D5ZMILL I
2 OBLOCK. CLASSIC. A360 CAST AL MILL I
3
HANGER BOLT. PLAIN CENTER. 5/167 x 6, IBA SS
I
4
WASHER. SEALING, 5/16'ID X 3/4"OD, EPDM BONDED SS
1
5
NUT, HEX, 5/16-18, UNC-28. 188 SS
2
6
WASHER, FIAT, 19/64-IDx 7/6'OD x 1/8'EPDM
1
7
WASHER. FENDER, 5/16'IDX I"OD, IBA SS
1
8
WASHER, SPOT -LOCK, 5/16'ID, I8-8SS
1
QMSC: CLASSIC COMPOSITION
MOUNT
A DAm Iimmns 7
iu TooxorrcNsouxac 1YNpAIICLOdV1 nle
r�w.aowws e.Is srAlE:u wmn:I.Ie sxsTlal
Lag pull-out (withdrawal) capacities (lbs) in typical lumber:
Lag Bolt Specifications
Spclr Galdy
St6'cla8 Para-VratldGah
S�1B'Nafl per t-Bvea]depal
D"De F", EGEOI
50
T96
266
Dwglas Fv, SOW,
.48
705
245
ENOTTSml SpmrM,lDdo.M1. PMe(MSR1650f&hlgh.)
.46
705
205
NOT. FIT
.43
606
212
HaTu Rr(NDdh)
.48
705
235
_ _
Swdhem Pme
.55
92l
3G?
spice. Pura. Fh
}2
615
205
spruce. PDM,Fo(E oft milRDl pal aM Nghergradea d MR and M E)
.W
M
266
sources: Amerlan Wood council, Nos 2W5,Table I I I A 1122A
Notes:
1)11toread must be embedded in a rafter or other structural roofinember.
2) See NDSTable 1153C for required edge distances
BI723-7
Quick Mount Mt
RESPECT THE ROOF
Jan-2017, Rev 8
Classic Composition Mounting Instructions
Installation Tools Required: tape measure, roofing bar, chalk line, stud finder, caulking gun, sealant compatlblewlth roofing materials,
drill with 7132" long -style bit, drill or impact gun with 1/2" deep socket.
WARNING: Quick Mount PV products are NOT designed for and should NOT be used to anchor fall protection equipment.
locate, choose, and mark centers of afters to be
mounted. Select the courses of shingles where
mounts will be placed.
Using drill with 7/32" bit, drill pilot hole Into roof
and after, taking care to drill square to the roof.
Do not use mount as a drill guide. Drill should be
long style bit aka'aircaft extension bit to drill a
3" deep hole Into rafter.
Carefully liftcompositlon roofshinglewith roofing
barjust above placement of mount Remove nails
as required. See "Proper flashing Placement' on
next page
Insert Flashing between 1st and 2nd course. Slide
up so top edge of Flashing is at least 3W higher
than the drip edge of the Sid course and lower
Flashing edge Is above the drip edge of 1st course.
Mark center for drilling.
Clean off any sawdust, and fill hole with sealant Slide flashing Into position. Prepare hanger bolt
compatible with roofing materials. with hex nut and sealing washer. Insert Into hole
and drive hanger bolt until caloric stops rotating
easily. Do NOT over torque.
IrLsert EPDM rubber washer over hanger bolt into Using the arck. kit hardware, secure the mddng
block (L-foot) to the mount using torque specs from
Tacking manufacturer. Ifaddng manufacturer does
not specify torque setting, tighten to 13 fL4bz
Bill 723-7
Jan-2017,Rev8
Castillo
Engineering
DESIGNED TO PIRMIT•
CASTILLO ENGINEERING
SERVICES, LLC
mna2""s
2925 W. STATE ROAD 434,
SURE111
LONGWOOD. FL 3V79
To, (407J 2832575
FRNACMIES E.GSIILLO-FLPE52590
REVISIONS
DESCRIPOON
DATE
REV
PROJECTINSTALLER
T
,oR.rp
Will
igCaal•
/V o S� % ,
90
ST
T
♦`
L D Q ♦01)
U rn
V
LL.I ¢
J
Q U o LL
Z
W
W Z q
Q 0 7C 01'
U J
Q 0 LLay
rnp
LL
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
DS-05