2224 N 53rd St Rehab
HVAC Load Calculations
for
ERM Investment Grp Rehab
2224 N 53rd St
Fort Pierce, FL 34946
St. Lucie Countv
SHGC WARNING:
The window performance values consist of the u-factor for the frame,
and Solar Heat Gain Coefficient (SHGC) for the glass. These values have
a huge impact on the building thermal envelop and may have a significant
Impact on the following:
the size of the HVAC system(s), $$$
• the duct work layout and design, $$
delays with permitting, $$$$
Inspector comments or failed Inspections $$
It is important to us that your project Illy on schedule and if there are
any changes to the design base it may impact any of the bullet paints
above. Ko Enemy Del inn must be contacted immediately at
infono koene vtl i Or (561) 327-7272 to help support any
changes to your project information.
Prepared By:
Karen Oliver
KO Energy Design
1470 N Congress Ave, Suite 106A
West Palm Beach, Florida 33409
561 327-7272
Thursday, September 12, 2019
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
uesigned By:
Project Date:
Client Name:
Client Address:
Client City:
Company Name:
Company Representative:
Company Address:
Company City:
Company Phone:
Company E-Mail Address:
Company Website:
Permit Number(s):
Karen Oliver
Thursday, September 12, 2019
ERM Investment Grp Rehab
2224 N 53rd St
Fort Pierce, FL 34946
KO Energy Design
Karen Oliver
1470 N Congress Ave, Suite 106A
West Palm Beach, Florida 33409
561 327-7272
info@koenergydesign.com
www.koenergydesign.com
Jurisdiction: 661100
Built: 1975
Reference City: ' `— 11,''- `�
West Palm Beach AP, Florida
Building Orientation: Front door faces West
Daily Temperature Range: Medium
Latitude: 26 Degrees
Elevation: 15 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Winter: D ^6 qhj Wet Ruh Ral Hum Reel H �m DW Rulh Difference
Summer: 90 78 59% , 70 n/a
50 /0 75 61
I otai building Supply CF
Square ft. of Room Area:
Volume (831:
1_=11[la Raquireo mciucmg Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
832 CFM Per Square ft.: 0.889
936 Square ft. Per Ton: 519
7,488
12,793 Btuh 12.793 MBH
18.305 Btuh 85 %
3,330 Btuh 15 %
21,634 Btuh 1.80 Tons (Based On Sensible + Latent)
r
hvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may.vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:1...12224 N RAM Sr_nn i .kn
Thursday, September 12, 2019, 2:08 PM
Thursday, September 12, 2019, 2:08 PM
Thursday, September 12, 2019, 2:08 PM
Rhvae
KO Ener
I Description
IA-cb-o. Glazing -Single pane, operable window, clear,
metal frame with break, U-value 1.08, SHGC 0.75
IA-cb-o: Glazing -Single pane, operable window, clear,
metal frame with break, in partition wall, U-value
1.08. SHGC 0.75
11 N: Door -Metal - Polystyrene Core, U-value 0.35
12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
12C-Osw: Part -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
16B-38: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-38 insulation, U-value 0.026
20P-13-c: Floor -Over open crawl space or garage,
Passive, R-13 blanket insulation, carpet covering, U-
value 0.068
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 87, Summer CFM: 45
Ventilation: Winter CFM: 0, Summer CFM: 0
AED_Excursion:
Total Building Load Totals:
Total Bull
Square ft.
Volume (f
Supply CFi
oom Area:
Total Sensible Ga
Total Latent Gain:
Total Cooling Req
Including Ventilation Air:
832
936
7,488
Elite Software Development, Inc.
2224 N 53rd St Rehab
Mud
den
; Let
Sen
Totals
Quan.
Loss
Gain
Gain
Gain
94
2,335
0
6,086
6,086
13.6
368
0
235
235
40
322
0
364
364
612.8
1,282
0
1,200
1,200
221.6 504 0 323 323
936 559 0 1,217 1,217
936 1,464 0 637 637
6,834
3
0
10,062
10,062
600
690
1,290
0
200
3.600
3,800
3,750
666
0
2,448
0
3,114
2,209
1,864
742
2.606
0
0
0
0
Q
. 0
762 _
762
12,793 3,330 18,305 21,634
CFM Per Square ft.:
Square ft. Per Ton:
On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
Your design conditions.
CA ...\2224 N 53rd St-M.) rhA
18,305 Btuh
3,330 Btuh
21,634 Btuh
.raj Mon
85 %
15 %
1.80 Tons
Thursday, September 12, 2019, 2:08 PM
Floor 11 %
Roof 4%
Wall 14%
Glass 21 %
Door 3%
Infiltration 17%
Ductwork 29%
Floor 3% AED Excursion 4%
Roof 6 /o
Wall 7%
Glass 29%
Door 2%
People 6%
Infiltration 12%
Ductwork 14%
Equipment 18%
CA ...\2224 N 53rd St-MJ.rh9
Thursday, September 12, 2019, 2:08 PM
Rhvac-Residential &
KO Energy Design LLC
I Description
1A cb-o. Glazing -Single pane, operable window, clear,
metal frame with break, U-value 1.08, SHGC 0.75
1A-cb-0: Glazing -Single pane, operable window, clear,
metal frame with break, In partition wall, U-value
1.08, SHGC 0.75
11 N: Door -Metal - Polystyrene Core, U-value 0.35
12C-Osw: Wail -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
12C-0sw: Part -Frame, R-13 insulation in x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
1613-38: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-38 insulation, U-value 0.026
20P-13-c: Floor -Over open crawl space or garage,
Passive, R-13 blanket insulation, carpet covering, U-
value 0.068
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 87, Summer CFM: 45
Ventilation: Winter CFM: 0, Summer CFM: 0
AED Excursion: _
System 1 System #1 Load Totals:
Square ft. of Room Area: 832
Volume (w): 936
7,488
Total Sensible Ga
Total Latent Gain:
Total Cooling Req
53rd
,. men - I otal
Juan` • Loss Gaitean Gain Gair
94 2,335 0 6,086 6,088
13.6 368 0 235 235
40 322 0 364 364
612.8 1,282 0 1,200 1,200
221.6
504
0
323
323
936
559
0
1,217
1,217
936
1.464
0
637
637
3
6,834
0
10,062
10,062
600
690
1,290
0
200
3,600
3,800
3.750
666
0
2,448
0
3,114
2,209
1,864
742
2,606
0
0
0
0
0
0
762
762
12,793 3,330 18,305 21,634
CFM Per Square IL 0.889
Square ft. Per Ton: 519
12.793 MBH
85 %
15 %
1.80 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
Air:
Including Ventilation Air:
CA ...\2224 N 53rd St-MJ.rh9
12,793 Btuh
18,305 Btuh
3,330 Btuh
21,634 Btuh
i nursday, September 12, 2019, 2:08 PM
Rhvac - Residential & Light Commercial HVAC Loads "
W Enerpv Design LLC
i Elite Software Development, Inc.
LZtQ�33411
2224 N 53rd
St Rehab
S stem 1 Room Load Summa
P P a
Htg :=Min ,Run Run
Room '
'- Area f 'Sens Htg Duct Dud
'Name
- '' CI 9 "`'Clg Mtm
rAcf
No "_ gF„ Btuh ' CF.M Size Vel
---Zone 1--
Sens at Clg,
Btuh_. <_ Btuh, CFM '
- 'Sys
:-: CFM
1 Living Room 348 4,340 56 2-8 412
2 Kitchen & Dining 212 2,532
6,322 1,138 288
288
33 1-9 482
3 Bedroom 1 163 2,651 34 1-8 443
4,686 659 213
213
4 Bath 50 618 8 1-4 260
5_ Bedroom 2 163
3,399 395 155
498 77 23
155
23
2,651. 34_ 1-8 443
Dud Latent
3,399, 395 155
155
System 1 total _
y 936 12,74 166.
666
System 1 Main Trunk Size: 14 in.
18,305 3,330 832
832
Velocity: 779 ft./min
Loss per 100 ft.: 0.088 in.wg
Coolihc System Summary
Cooling Sensible/Latent Sensible
Tons
"'Latent
Total
S lit Btuh
Net Required: 1.80 85% / 15% 18,305
Actual:
Btuh
"-Si h
197 ° °
75 /° / 25 /°
Eauiomerit Data 17 700
3,330
5,900
21,634
23,600
HPahng Syc}pm
Type:
Electric Resistance
Model:
C
oolin_n g�ctem
Standard Air Conditioner
ASPT29B14A"
Indoor Model:
GSX160241 F`
Brand:
ASPT29B14A'
Efficiency: 0%
GSX16
Sound: 0
16 SEER
Capacity: 27,000 Btuh
Sensible Capacity:
0
23,600 Btuh
n/a
Latent Capacity: n/a
17,700 Btuh
AHRI Reference No.: n/a
5,900 Btuh
201384201
This system's equipment was selected in
accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 47F, SIDB:
18,305
75F, SIRH: 50%, WIDB: 70F, Sen. gain:
Btuh, Lat. gain: 3,330 Btuh, Sen. loss: 12,793 Btuh, Entering clg. coil DB: 75F, Entering cig. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg.
coil TD: 20F, Htg. coil TD: 70F, Req. cig. airflow: 832 CFM, Req, htg, airflow: 166 CFM
CA ...12224 N 53rd St-MJ.rh9
Thursday, September 12, 2019. 2:08 PM
Field Verification Requirement
Project Information
Project title:
Designed by:
2224 N 53rd St Rehab
Project date:
Karen Oliver
Thursday, September 12, 2019
Client name:
ERM Investment Grp Rehab
Client address:
2224 N 53rd St
Client city:
Fort Pierce, FL 34946
Company name:
KO Energy Design
Company phone:
561 327-7272
Field Verification Requirement
All inputs/defaults/building characteristics used for the ACCA Manual J Version 8
calculations must be verified by the HVAC contractor in the field and/or must be verified by the builder/owner verifying that
what is being built is consistent with the builder's/owners project components in this report. Test and balance reports if
performed are to reflect Manual J system actual CFM for each individual unit. K.O. Energy Design must be notified in writing
of any said changes.
Equipment Selection
Equipment selected below was carefully chosen to meet or exceed the FL Energy Efficiency Code. Alternate equivalent
equipment selection shall also meet the attached Energy Code Requirements. Any change in SEER or size of equipment will
require approval and plan revision. K.O. Energy Design must be notified in writing of any said changes.
Manual D Duct Sizing
Duct sizing has been carefully engineered at the stated s.p. Any deviance in duct sizing could impact the performance and
efficiency of selected equipment. Any change or alteration in duct sizing will require approval and possible plan revision.
K.O. Energy Design must be notified in writing of any said changes. Duct sealing Air Distribution System Test to be
performed and made available for Rough Duct Inspection, if required.