HomeMy WebLinkAboutPLANS. 111IIIIIIt. General Notes A. CONCRETE & FOUNDATION DESIGN: L ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 1/2" NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN.) MEETING APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH. 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, 93 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM. THICKNESS. 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. 8.- THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,- ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO. 67 LESS THAN 3/4". AIR ENTRAINING+/- 1%- ASTM C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTABLE WATER OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY: 1.CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2.ALL MORTAR SHALL BE OF TYPE M OR S. TALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS Y-0" IN HEIGHT. C. ALUMINUM: 1. ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-TS FOR ALLOY WITH A MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WHERE KICK PLATES ARE USED A MINIMUM THICKNESS OF 0.024" SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART I -A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN' OR "PART I-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN' ORTHE ALUMINUM DESIGN MANUAL PREPARED BY THE ALUMINUM ASSOCIATION, INC.WASHINGTON D.C. THE FLORIDA BUILDING CODE 6th EDITION ( CHAPTER 16 STRUCTURAL DESIGN & CHAPTER 20 ALUMINUM). 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN 910 SMS 6" FROM THE ENDS AND 12" ON CENTER, IF USING #12 SPACING MAY BE 24" ON CENTER. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH". DECAL SHALL BE PLACED SO IT IS VISIBLE WHEN PANEL IS INSTALLED. I"X2"X0.045" NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH 1/4" 0 X I-3/4" EMBEDMENT & 24" O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WHEN IN WOOD & #lOX 12" EMBEDMENT SMS OR TEK SCREWS IN ALUMINUM MEMBERS TYPICAL. D. FASTENERS: 1. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE 300 18-8. WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO BE ASTM A 325, PLATED WITH STANDARD FLAT WASHERS AND NUTS. 3. ALL CONCRETE SCREWS SHALL BE, SIMPSON, HILTI, RAWL, TAPCON,REDHEAD, DYNABOLT, PORTECT OR APPROVED EQUAL. 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE HOT DIPPED GALVANIZED. 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF 8X BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.).. 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF THE BOLT OR SCREW. ALL LAG BOLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNING AND UNDER NO CIRCUMSTANCES BY DRIVING WITH A HAMMER z ALL EXPANSION ANCHORS SHALL BE DESIGNED IN ACCORDANCE WITH THE SPECIFIC MANUFACTURERS REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER. FASTENERS SHALL BE A MINIMUM OF SAE GRADE 95 OR BETTER ZINC PLATED. 8. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD, OR OTHERWISE NOTED ON PLANS. 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 CLASS G-185. ❑. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" UNLESS NOTED OTHER WISE. E. REFERENCE STANDARDS: ASTME 119 ASTME 1300 CURRENT ASCE 7 CURRENT ALUMINUM DESIGN MANUAL -AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & 1-B ASTM C94 ASTM C 150 ASTM C33 ASTM C260 ASTM C494 ASTM A615 ASTMA185 FLORIDA BUILDING CODE 6U1 EDITION (CHAPTERS 16,20 & 23). /:XI Il CII&I THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT TO SUPPLEMENT THE MORE COMMON ABBREVIATIONS. 1. TYP -TYPICAL 2. SIM - SIMILAR 3. DON -UNLESS OTHERWISE NOTED 4, CONT -CONTINUOUS 5. VIF - VERIFY IN FIELD G. RESPONSIBILITY: 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS. 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM' ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR- 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER 5. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BY A LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES. H. MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 2. IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE ENCLOSURE SHALL COMPLY WITH RESIDENTIAL SWIMMING BARRIER REQUIREMENTS OF THE FLORIDA BUILDING CODE 6th EDITION R 4501.17IN ITS ENTIRETY. 3. DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY CONTRACTOR 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, ENSURE BONDING AGENT IS USED FIRST. 5. SCREENING MATERIAL SHALL BE 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED ON DRAWING S-2. 6. PLEASE NOTE: 2x2 (typ) DIAGONAL BRACING SHALL BE 2"X2"X0.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-2. DESIGN DATA: 1. ULTIMATE DESIGN WIND SPEED Vult, (3 SECOND GUST): NOMINAL DESIGN WIND SPEED Vasd: 2. RISK CATEGORY: 3. WIND EXPOSURE: 4. WIND LOADS: SCREEN ROOF: N/A SCREEN WALLS: 31 PSF SOLID ROOF (SCREEN WALL): 25 PSF COMPONENTS AND CLADDING LOAD: N/A qp Ago i A �lcENsF F9% NIO. 86663 * • ii- 7t RECEIVED �O� •. STATE OF 4 O C T 2 2 119 Piwn �T: 61I012 6N1!(14y1 P@P Q- _ PROFESSIONALE GI EER SEAL ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 10 MPH 120 MPH Thomas L. Hanson P.E 1 FLORIDA LICENSE: 38654 B Myron Max Neal P.E. FLORIDA LICENSE: 86663 5. FACTOR APPLIED TO SCREEN WIND LOADS FOR 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.88 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN: 0.6 7. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING SLAB AND OR FOOTING MEETS THE REQUIREMENTS TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE. 9. SCREEN ROOF TYPE : N/A 10. SOLID ROOF TYPE: 3"X48"XO.024" ELITE EPS COMPOSITE PANEL ROOF 116 FOAM DENSITY, FLORIDA PRODUCT APPROVAL, FL 7561.R-4. ALUMINUM STRUCTURAL MEMBERS SCANNED2x2:- HOLLOW SECTIONS -----------------2"x2'x0.044" BY 2 x 3- --------------------------------------2„ x 3" x 0.050" 2x4- --------------------------------------- 2"x4"x 0.050" St. (..UCIe County 2 x 5: ---------------------------------------2" x 5" x 0.050" 3 x 3: -----------------------------------3" x 3" x 0.125" OPEN BACK SECTIONS 1 x 2:---------------------- -- 1" x 2" x 0.040" 1 x 3: --------------------------------------1" x 3"x 0.045" Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-W v✓w.tbcplans.com C.O.A.429054 DATE: 10/16/2019 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 _1011_214 SNAP SECTIONS I 1PROJECT ADDRESS: 2 x 2 SMS:----------------------------------2" x z' x o.045" KELLY 2 x 3 SMS: 2 x 4 SMS:-------------------------------- 3 3 SMS:--------------------------------- ---------------------------------2" x 3" x 0.072" I 2" x 4" x 0.045° 3" x 3" x 0.090" �� FORT PALMETTO DR FORT PIERCE, FL 34982 I x SELF MATING (SMB 2 x 4 SMB:---------------------- 2" x 4" x 0.044" x 0.100" 2 x 5 SMB:---------------------- 2" x 5" x 0.050" x 0.118" 2 x 6 SMB----------------------- 2" x 6" x 0.050" x 0.120" 2 x 7 SMB----------------------- 2" x 7" x 0.057" x 0.120" 2 x 8 SMB----- ----------------- 2" x 8" x 0.072" x 0.224" 2 x 9 SMB----------------------- 2" x 9" x 0.072" x 0.224" 2 x 10 SMB-------------------- 2" x 10" x 0.092" x 0.374" TUBE SECTIONS 2 x 2---------------------------------------2„ x 2" x 0.090„ REVIEWED FOR CODE COMPLIANCE ST. L UCIE C� �t3(f9 BOCC (d�b.J1� K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 NOTES S-1 2x7 SMB 2x6 SMB 2x6 SMB ] M M M j p C ] M 7 M n X M x M I 1.k 12'-0" 2'-0" 2-0„ 1L Q REVIEWED FOR CODE COMPLMNCt Si. LUCIE COUNT`' RCCC CENSF'. lC,� P1o.86663 iA®�'•. STAT O .? / �'•n• OV PROFESSIONAL E GINEER SEAL ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E. FLORIDA LICENSE: 38654 Myron Max Neal P.E. FLORIDA LICENSE: 86663 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-w .lbcplans.com C.OA.429054 DATE: 10/16/2019 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 A-6f ftTIADDRESS: KELLY 4807 PALMETTO DR FORT PIERCE, FL 34982 ]ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 FLOOR PLAN S-2 .11ll11111/� 1 (1)45 REBAR CONTINUOUS W/ 25" OVERLAP AT ALL JOINTS ON 3" CHAIRS & CENTERED TYPE II MONOLITHIC SLAB MODERATE SLOPE FTG SLOPE: 2":12" - 3":12" NOTES FOR ALL FOUNDATION TYPES: 1. THE FOUNDATIONS SHOWN ARE BASED ON A MINIMUM SOIL BEARING PRESSURE OF 1,S00 PSF. THE BEARING CAPACITY OF THE SOIL VERIFIED BYA LICENSED CONTRACTOR PRIOR TO ANY POURING OF CONCRETE. 2. THE SLAB/FOUNDATION MUST BE CLEARED OF ALL DEBRIS, AND COMPACTED PRIORTO POURING OF ANY CONCRETE. 3. CONCRETE MEET THE SPECIFICATIONS IN THE S-1 NOTES PAGE. K TYPE 11 MONOLITHIC SLAB FOOTING S_3 . . EXISTING MASONRY WALL GROUTED SOLID @ CONNECTION (4)-3/8" 000NCRETE NOTE:MINIMUM EMBEDMENT OFf SCREW WITH 2-3/4" ANCHORS INTO CONCRETE FOOTINGGiHALL 'I EMBEDMENT (MIN BUG BE 2-3/4" AT ALL POST LOCATIONS. AIIG'='-= DISTANCE=3" SCREW LENGTHS AT POST CONNEETIONS MIN SPACING 2") SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE, , FOOTING WHEN A PAVER DECK IS:PRESBNT. ' i A' (3) -1/4" 0 MACHINE - BOLTS WITH WASHERS (MIN. EDGE DISTANCE = 3/4'; MIN. SPACING= 3/4") OR (4) #14X 3/4" SMS EA. SIDE (4)-3/8" 000NCRETE SCREW WITH 2-3/4" EMBEDMENT (MIN EDGE - DISTANCE =3" MIN SPACING 2") a'd TOP VIEW 3"X3"POST Eia,...C.MAX SEE SHS.2 FOR c-+•-++• Z"xZ"x 0.125" ANGLE(FXTERNAL OR INTERNAL) OR O.f25" RECEIVING CHANNEL "'- 1" } x 2" OPEN BACK ANCHORED TO CONCRETE w/ 1/4" X 3- _ -- 1/2" - MASONRY ANLROR-6" AX EACH SIDE OF POST AND d FRONT VIEW NOTE: CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON3/8" 0 LOT SCREW ANCHORS, OTHER SIZE OR TYPE OF ANCHORS SHALL NOT BE USED. Cr1 T13"POST CONNECTION DETAIL S'3 SCALE: NTS _"X 4"X.125"ANGLE FOR ALL -NON-PLUMB OR SQUARE FASCIA SHALL BE USED WITH SUPER GUTTER. HOSTSTRUCTURE BREAK FORM HEADER OR RECEIVING CHANNEL 910 SMS AT EACH RISER OR PAN OR#10 SMS@ 8" O.C. FOR COMPOSITE PANEL /-SOLID ROOF \#10 SMS @ B" D.C. (MIN) FOR COMPOSITE PANEL - ._ (2) #10 SCREWS PER 12" . - WIDTH CONNECTING 12)410 PAN TO HEADER (BOTTOM OR BACK OF PAN) X 2" SCREWS PER 12" WIDTH CONNECTING HEADER OR CHANNEL TO. FASCIA. • S1 ROOF PANEL TO FASCIA CONNECTION DETAILS S_3 SCALE:NTS Fs- r.` (2)1"XS"X2"WIDTH EXTRUDED' GUTTER BRACKET (THICKNESS SHALL BE 0.125" MIN. @ EACH BEAM W/ (2) #10X3/4" SMS 1" SPA, INTO GUTTER LIP & (2) INTO 1"x2"x 0.045"OPEN BACK CARRIER BEAM OR 2"X2"MEMBER W/ #10X4"SMS 114" 1 (2)012X 2-1/2"@ANGLE & (1)#12X 2-1/2"@24"D.C.� NEOPRENE WASHER B-W.0 /PER PANEL INTO CARRIER BEAMz 00 1/4"0X2-3/4"EMBEDMENT (SLOPED OR 00 MASONRY SCREW 3" FROM HORIZONTAL) I END & @ 24" O.C. G SUPE�GUTTEB 2" X_ END BEAM ATTACHED (SEE SHEET 3-2 FOR SIZE) BEAM i�f ) 2" X 2"X325" (MIN) SMS @ 24" OX. 2" x _" END BEAM ANGLE W/ (4) #14X 3/4, INTO UPRIGHTORPOST ATTACHED TO I"x2"OPEN BEAM &CARRIER BEAM (SEESHEETS-2 BACK W/ (4) #10 X 2" 1"XZ"OPEN BACK FORSIZE- THRU SCREW BOSS CARRIERBEAMW/ I IFPOST3"X3"USE (3) 3/W 0 THRU BOLTS (4) 3/8" 0 (SEE SHEET S-Z FOR SIZE) THRUBOLTS- NOTE: WHEN ATTACHING TO WOOD STRUCTURES, WOOD LAG SCREW IF2"X_"SMB CONNECTION SIMILAR ANCHOR DESIGNS SHALL BE OF IDENTICAL SIZE AND EMBEDMENT AS THAT - TO D. S-3.) OF MASONRY ANCHOR SCREWS. S2 S GUTTER BRACE& BEAM ATTACHMENT DETAIL END BEAM TO HOST STRUCTURE DETAIL S_4 N.T.& S-3 SCALE:NTS REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY' IG OCC No. 86663 %AO�•'. STATE OF/y(1 4( ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson RE FLORIDA LICENSE: 3B654 Myron Max Neal P.E. FLORIDA LICENSE: 86663 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-www.fbcplans.com C.O.A: #29OS4 DATE: 10/16/2019 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 JECT ADDRESS: Y PALMETTO DR PIERCE, FL 34982 ]ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-3 t I