Loading...
HomeMy WebLinkAboutINSTALLATION MANUAL (1)OLIVER TECHNOLOGIES, INC page t revision 6/07 FLORIDA INSTALLATION INSTRUCTIONS FOR THE MODEL 1101 "V" SERIES ALL STEEL FOUNDATION SYSTEM MODEL 1101"V" (STEPS 1.15) LONGITUDINAL ONLY., FOLLOW STEPS 1.9 FOR ADDING LATERAL ARM; Follow Steps 10.15 FOR CONCRETE APPLICATIONS: Follow Steps 16-19 ENGINEERS STAMP SCANNED BY St. Lucie County ENGINEERS STAMP SPECIAL CIRCUMSTANCES: If the following conditions occur - STOP! Contact Oliver Technologies at 1-800-284-7437 : a) Pier height exceeds 48" b) Length of home exceeds 76' c) Roof eaves exceed 16" d) Sidewall height exceed 96" e) Location is within 1500 feet of coast INSTALLATION OF GROUND PAN 2. Remove weeds and debris in an approximate two foot square to expose firm soil for each ground pan (C) . 3. Place ground pan (C) directly below chassis I-beam . Press or drive pan firmly into soil until flush with or below soil. SPECIAL NOTE: The longitudinal'Y brace system serves as a pier under the home and should be loaded as any other pier. It is recommended that after leveling piers, and one-third inch (1/3") before home is lowered completely on to piers, complete steps 4 through 9 below then remove jacks. INSTALLATION OF LONGITUDINAL "V" BRACE SYSTEM NOTE: WHEN INSTALLING THE LONGITUDINAL SYSTEM ONLY, A MINIMUM OF 2 SYSTEMS PER FLOOR SECTION IS REQUIRED. SOIL TEST PROBE SHOULD BE USED TO DETERMINE CORRECT TYPE OF ANCHOR PER SOIL CLASSIFICATION. IF PROBE TEST READINGS ARE BETWEEN 175 & 275 A 5 FOOT ANCHOR MUST BE USED. IF PROBE TEST READINGS ARE BETWEEN 276 & 350 A 4 FOOT ANCHOR MAY BE USED. USE GROUND ANCHORS WITH DIAGONAL TIES AND STABILIZER PLATES EVERY 5'4" . VERTICAL TIES ARE ALSO REQUIRED ON HOMES SUPPLIED WITH VERTICAL TIE CONNECTION POINTS (PER FLORIDA REG.) . 4. Select the correct square tube brace (E) length for set - up (pier) height at support location. (The 18" tube is always used as the bottom part of the longitudinal arm). Note: Either tube can be used by itself, cut and drilled to length as long as a 40 to 45 degree angle is maintained. PIER HEIGHT 1.25" ADJUSTABLE (Approx. 45 degrees Max.) Tube Length 1.50" ADJUSTABLE Tube Length 7 3/4" to 25" 22" 18" 24 3/4" to 32 1/4" 32" 18" 33" to 41" 44" 18" 40" to 48" 54" 18" 5. Install (2) of the 1.50" square tubes (E {18" tube) ) into the "U" bracket (J), insert carriage bolt and leave nut loose for final adjustment. 6. Place I-beam connector (F) loosely on the bottom flange of the I-beam. 7. Slide the selected 1.25" tube (E) into a 1.50" tube (E) and attach to I-beam connectors (F) and fasten loosely with bolt and nut. 8. Repeat steps 6 through 7 to create the W" pattern of the square tubes loosely in place. The angle is not to exceed 45 degree and not below 40 degrees. 9. After all bolts are tightened, secure 1.25" and 1.50" tubes using four(4) 114"-14 x 3/4" self -tapping screws in pre -drilled holes. INSTALLATION OF LATERAL TELESCOPING TRANSVERSE ARM SYSTEM THE MODEL 1101 "V" (LONGITUDINAL & LATERAL PROTECTION) ELIMINATES THE NEED FOR MOST STABILIZER PLATES & FRAME TIES. NOTE: THE USE OF THIS SYSTEM REQUIRES VERTICAL TIES SPACED AT 5'4". FOUR FOOT (4') GROUND ANCHOR MAY BE USED EXCEPT WHERE THE HOME MANUFACTURER SPECIFIES DIFFERENT. 10. Install remaining vertical tie -down straps and 4' ground anchors per home manufacturer's instructions. NOTE: Centerline anchors to be sized according to soil torque condition. Any manufacturer's specifications for sidewall anchor loads in excess of 4,000 lbs. require a 5' anchor per Florida Code. 11. NOTE: Each system is required to have a frame tie and stabilizer attached at each lateral arm stabilizing location. This frame tie & stabilizer plate needs to be located within 18" from of center ground pan. 12. Select the correct square tube brace (H) length for set-up lateral transverse at support location. The lengths come in either 60" or 72" lengths. (With the 1.50" tube as the bottom tube, and the 1.25" tube as the inserted tube.) 13. Install the 1.50 transverse brace (H) to the ground pan connector (D) with bolt and nut. 14. Slide 1.25" transverse brace into the 1.50" brace and attach to adjacent I-beam connector ( I ) with bolt and nut. 15. Secure 1.50" transverse arm to 1.25" transverse arm usina four (4) 1/4" - 14 x 3/4" self-taooina screws in pre -drilled holes. OLIVER TECHNOLOGIES, INC. Telephone: 931 796 4555 1-800-284-7437 Fax: 931 796 8611 02/02/2018 File Copy www.olivertechnologies.com page 2 INSTALLATION USING CONCRETE RUNNER 1 FOOTER revision 6107 ,16. A concrete runner, tooter or slab may be used in place of the steel ground pan. a) The concrete shall be minimum 2500 psi mix b) A concrete runner may be either longitudinal or transverse, and must be a minimum of 8" deep with a minimum width of 16 inches longitudinally or 18 inches transverse to allow proper distance between the concrete bolt and the edge of the concrete (see below). c) Footers must have minimum surface area of 441 sq. in. (i.e. 21" square), and must be a minimum of 8" deep. d) If a full slab is used, the depth must be a 4" minimum at system bracket location, all other specifications must be per local jurisdiction. Special inspection of the system bracket installation is not required.. Footers must allow for at least 4" from the concrete bolt to the edge of the concrete. NOTE: The bottom of all footings, pads, slabs and runners must be per local jurisdiction. LONGITUDINAL: (Model 1101 LC "V") 17. When using Part # 1101-W-CPCA (wetset), simply install the bracket in runner/tooter OR When installing in cured concrete use Part # 101-D-CPCA (dryset). The 1101 (dryset) CA bracket is attached to the concrete using (2) 518"x3" concrete wedge bolts (Simpson part # S162300H 5/8" X 3" or Powers equivalent). Place the CA bracket in desired location. Mark bolt hole locations, then using a 5/8" diameter masonry bit, drill a hole to a minimum depth of 3". Make sure all dust and concrete is blown out of the holes. Place wedge bolts into drilled holes, then place 1101 (dry set) CA bracket onto wedge bolts and start wedge bolt nuts. Take a hammer and lightly drive the wedge bolts down by hitting the nut (making sure not to hit the top of threads on bolt). The sleeve of concrete wedge bolt needs to be at or below the top of concrete. Complete by tightening nuts. LATERAL: (Model 1101 TC "V") 18. For wet set (part # 1101-W-TACA) installation simply install the anchor bolt into runner/tooter. For dry set installation (part # 1101-D-TACA) mark bolt hole locations, then using a 5/8" diam. masonry bit, drill a hole to a minimum depth of 3". Make sure all dust and concrete is blown out of the hole. Place wedge bolts (Simpson part #S162300H 5/8" X 3" or Powers equivalent) into (D) concrete dry transverse connector and into drilled hole. If needed, take a hammer and lightly drive the wedge bolts down by hitting the nut (making sure not to hit the top of threads on bolt), then remove the nut. The sleeve of concrete wedge bolt needs to be at or below the too of concrete. 19. When using part # 1101 CVW (wetset) or 1101 CVD (dryset), install per steps 17 & 18. Notes: 1. LENGTH OF HOUSE IS THE ACTUAL BOX SIZE 2. • = STABIUZERR PLATEAND FRAIVIETIE LOCATION (needsto be bated v&n 18uxhes ofcalerofgarid pan orconaue) 3. C� LOCATION OF LONGITUDINAL BRACING ONLY 4. K -=TRANSVERSE&LONGFFUDINALLOC4TlONS REQUIRED NUMBER AND LOCATION.QF MODEL 1101 "V" OR 1101 C "V" ALL WIDTHS; AND LENGTHS UP TO 52' I I Ali �'� ;i� � \I� �11 ■ • • HOMES WITH 5/12 ROOF PITCH REQUIRE: PER FLORIDA REGULATIONS - 6 systems for home lengths up to 52' and 8 systems for homes over 52' and up 80'. One stabilizer plate afffililhe tie required at each lateral bracing system. rprs mail be used in all bons except where ie manufacturers sped ions for sidewall straps in excess of 4,000 lbs. ,1 Transverse arm I beam jl _n I • y roj - 1p1,, se locations require a 5' connector ior Per Florida Codo. ,\H Transverse arm / �� Top (1.25-) 1 bottom (1.5') j' C = GROUND PAN 4 D = GROUND PAN CONNECTOR D Ground \� / F ..^V bracer I beam ( U BRACKETS TRANSVERSE Pan y✓/ i connecters 11 E = TELESCOPING V BRACE bansve se i e„' lc' TUBE ASSEMBLY W/ 1.5 BOT- // \ connectors " / i ,\\ J ground Pan TOM TUBE AND 1.25 TUBE V Bmcket INSERT F = "V' BRACE I -BEAM CONNEC- TORS ASSEMBLY E 'V BracoTub H = TELESCOPING TRANSVERSE Top (1.25-) ARM ASSEMBLY Bottom (1.5-) 1 = TRANSVERSE ARM I -BEAM Ground Pan CONNECTOR J= V PAN BRACKET Model # 1101 "V" Longitude dry concrete bracket part # 1101 D-CPCA Wet bracket part # 1101 W-CPCA not shown iom may be used In all lions except where home ufacturers specifications idewall straps we in !as of 4.000 lbs. These lions require a Wencher. Florida Code. U bracket TubJ l' tsl 02/02/2018 Alternate Hole for it) P�er Assembly Narrower Beam Flange Grad�r-' `Grades-1/2"x 1' ^/' Camage Boll & Nut e'S/l- 1:2' x 2 11, Carnage Boll B Nul I -BEAM CONNECTOR BRACKET Transverse am I beam connector t�\HTransverse an �-..— Top (1.25') bottom (1.5' ) F :'V' bravo I beam connectors J Concrete _�-- -V" Bracket IF;emote ooterf Rumor �I Model # 1101 C "V" OLIVER TECHNOLOGIES, INC. 1-800-284-7437 Model 1101 CVD Model 1101 CV)A not shown page 3 rcviaion 6/07 C = CONCRETE FOOTER/RUNNER D = CONCRETE U BRACKET TRANSVERSE CONNECTOR (connects colds grade 5 -12" x 2 12— carriage bolt & nut) E = TELESCOPING V BRACE TUBE ASSEMBLY W/ 1.5 BOT- TOM TUBE AND 1.25 TUBE INSERT F = "V" BRACE I -BEAM CONNECTORASSEMBLY (connects with grade 5 - 112" x 4" carriage bolt & nut) H =TELESCOPING TRANSVERSE ARM ASSEMBLY 1=TRANSVERSE ARM I -BEAM CONNECTOR (Connects with grade 5 -12" x 212— carriage bolt & nut) J= CONCRETE 'NP' BRACKET (connects with grade 5 -1/2" x 4" carriage bolt & nut) Telephone: 931 796 4555 Fax: 931 796 8811 www.olivertechnologies.com ' 4 VERTICAL VINYL SKIRTING ( components 5 installation i LL S M aACK A'T.TACHEm, wlrN a .�; �nGH J<<46WS Ib AC44T I FLOOR $NAPS 10To Tov B HIoE9 SCRrz uz' ANa PANEL c.rTs V Ten ppt BLOCK swaPo 3-91A4HGS PEE F00T SECuREb P:84C4dF VEMTILATbN TD Tb' ANC,9aTTONI RAILS vw �.,� INCH SCREWS IL-;L" O 4ALL GAME Ls q46 AC_f � ,L O4 gV _ql REmOVtNG ZDP 7. o47 4Ln PI,LLiV� UP ON PANEL! AT'TACtAcb T0GRouk,6 N!'TF 71Kn (3ALMA#'IZE0 NAIL. 19 •OG (IF Salt ISM" 4)L-171) 02/02/2018 MAN•iRAll GRIP SIZE 1:, 21 aoAI _L L^L^_ A. MONMEMAR CYKMW RECESSED 'HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED PLANE ADJO'NING ME TREAD NOSING, OR FINISH SURFACE OF RAMP SLOPE, STALL BE NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES. 'HANDRAIL SHALL BE PROVIDED ON AT LEAST ONE SIDE OF EACH CONONUOUS RUN OF TREADS OF FLIGHT w1M FOUR OR MORE RISERS. • HANDRM ASSEMBUES AND GRADS SHALL BE DESICNEO TO RESIST A LOAD OF 50 PLY APPLIED IN ANY DIRECTION AT ME TOP AND TO TRANSFER MIS LOAD THROUGH THE SUPPORTS TO ME STRUCTURE. ME LLARDS.AVOE M.`OO. ALL. VWTL ryi fOUIVALENi, 2 K 2 BALUS WIN (3) SIMPSUH'S SOS 1/4• x 4-1/2• — W000 SCREWS FOR RIM JUST TO POST CONNECTION. (5) ISO NAILS OR FOUVALENt P T STEP LANDING FLOOR FASTENED TO HOST ROM MEMBERS USING 9MPON'S 1/4• 2 3-1/2• SOS WOOD SMEws OR EOUIV AT 12' O.C. STAGGERED SCREW PATTERN i YAmuyV RISER HEWLt %N BL t !/F n% HE& ME RISER ALL OF MEASURED VERTICALLF EE!".FN LfADNG EDGES OF ME JACENT MEADS. ME CREATEST M';n +OMR "MIN ANY HIGH STNRS 54At1 NOT EXCEED MC SWALLE51 81 NORE 1. ]/, IR YIHWI:Y 'END DEPTH SH"LL BE To 4( LS ME TRFID OEPM SHALL BE RSJRED HORZO TALL, OETFEEN ME t(oMAI PLANES OF ME 1OtEY05t PROJECTION QWCMT TREADS AND AT A RGfI ANQE TO ME TREAD'S LCADRIG IIIIDGE. E S TRCAO CUM TNN4TUN ANv RIOir SIT STNRS SHALL NOt [,,,6 ME . ST BT 4C.0 MAN 3/6 IROA r f RAOFIS OF MRVATURE AT ME LENDING EPR OF MF mr.n e..u. n. .... ..... �. T 5/E• E 6 BOARD RAIL CAP I%fi RI IANUNO GOO NAIL RON—� 0 1 16. OL FLOOR JOATS EACH (S) 16e NAILS M EWIVALENT AT EACH JUST TO PoN JUST CONNECTION. 30• GROUND ANCHOR W/ TIE DOWN STRAP STRAP TO WRAP AROUND P T. 2 A 6 DGHD3' (00 NOT OVER TENSION STRAPS) (EACH SIDES OF LANDING) STAR AND LAMYNO IW,4wADON REDLARLO (1) 2 K 6 P.T. ATTACHED TO POSTS USING (51 16D NAILS OR EWIVALENT AT EACH V3-0• LARDING HEIGHT . 5 STEPS (4W) 2%6 TO (POST CONNECTION. •-OP L...NG •(NNl - I STEPS EAOI P.T, LViT FASI mat uERR; (3) 1/E• Mow SCERS OR m IMES SHALL NOT ALLOW PASSAGE OF A A• DIAMETER SPHERE 2 N 4 TOP k BOTTOM ATTACHED TO TO POSTS VAN (2)E9 WOOD SCREWS ON INSIDE FACE. 1. OPENINGS FOR REWIRED GUARDS ON ME I, ESTAIR TREADS SHALL NOT ALLOW A SIriERE RE h3/9• i0 PASS THROUGH I � 1 ATTACH W/ Yrv. (jSyBWOOD TEBS TSCREW OR EBOTTOM OUV (3) 2 A 12 P.T i ICI 10 P.T 2.6 DSTS "M 3 PER CMKCPOI CONCRETE OPTION. IF STEPS ARE INSTALLED ON ELSP.NG CONCRETE. ME GROUND ANCHORS AND REDOM STRAP CAN BE WITTED. STAIR STRINGERS ME PT. 4 N A POSTS SHALL BE ANCHORED TO ME EMSTRiG CONCRETE SLAB USING SAMPSON'S L-BRACKET OR EGUIVALENT • 41 30 2018 NOTE:CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING A[ I DIPANSIONS AND CONDITIONS PRICR TO CONSTRUCTION, ALI STAIR COMPONENTS TO Z-EEL1%I2H TRFATEQ NUMBER S/ONAL. ' A FASTENERS IN ONTA .T NTH P.T.UMBER TO BE HO) oOff' r "N17FD OR STAINLESS 51EEL l,... Vu:r U urR PI V[In //rvO tRFO•,r0uw NOTE:CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING A[ I DIPANSIONS AND CONDITIONS PRICR TO CONSTRUCTION, ALI STAIR COMPONENTS TO Z-EEL1%I2H TRFATEQ NUMBER S/ONAL. ' A FASTENERS IN ONTA .T NTH P.T.UMBER TO BE HO) oOff' r "N17FD OR STAINLESS 51EEL l,... Vu:r U urR PI V[In //rvO tRFO•,r0uw