HomeMy WebLinkAboutREGULATOR PAPPERWORKBulletin LP-7: R122H
Type R122H First -Stage Regulator
Introduction
The Type R122H is an Underwriters Laboratories listed
regulator designed for Two -Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks. The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
20 Year Recommended Replacement Life —The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both internally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps — Built-in 118 inch NPT gauge
taps orificed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easy testing.
• Durability — A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation — A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation — The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the tightest installations.
FISHER'
March 2010
SCANNtU
BY
St. Lucie Count,
Figure 1. Type R122H First -Stage Regulator
Superior Overpressure Protection —The
combination of a high capacity relief valve and large
vent provide overpressure protection that exceeds
UL standards. When used in conjunction with a
R622 or R652, the two -stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
• Corrosion -Resistant —Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
spring and retainer and a corrosion resistant relief
valve seat.
• Positive Draining Spring Case— When installed
properly with the spring case vent pointed down,
the design allows moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
�www.FISHERregulators.com/lpl
EMERSON,
Process Management
Bulletin LP-7: R122H
Table 1. Ordering Information
TYPENUMBER
CAPACITY BTUMR
PROPANE01
CONNETItCTIONS
INLEOUTLET
NOMINAL OUTLET SETTING
R122H-AAJ
1,100,000
114Jnch x 1124110 NPT
10 psig (0,69 bar)
1. Cos" is based on 30 PSIG (2,07 bar) Intel i mmsure and 20%droop.
V418 w
W=-
Figure 2. Type R122H Dimensions: INCHES
(MM)
LP -Gas Equipment
Emerson Process Management
Regulator Technologies, Inc.
USA -Headquarters
McKinney, Texas 75069-1872 USA
Telephone: 1 (800) 5585853
Telephone: 1 (972) 5483574
For further information visit Y .fishenegulators.cumlfp
The Emerson logo is a trademark am service Mali of Emerson Electric Co. M olhef marks are the popedy of thew prosper a Menem FhOer Is a mink owed try Ftmer Commis, Inc, a
business of Emerson Process Management
The Contents of this Pgbedation are presented far informational purposes only. ad wile every effort has been made W ensae weir amtacy, they are not to be construed as wanames o
guarmaees, express or Implied, regarGng the podurb a services described harem Or their use a applicOlultty. We reserve me M;M to modify or M MM,o the designs a sped8ramns ofwm
Motives at arty Inns unmet notice.
Emerson Process Management does no assume msponseltiryrorthe selection, use or mainonance of any product Responsibility for proper selection, use and rrommot ce of any Emerson
Process Management product remove solely vMh the puroln er.
♦#4
EMERSON.
oEmerson Process Managernem RegUlator Temrlpbgles, Inc, 20M. 2010, M Mortis Ra50ned Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Comp ., .
• Protel
Scree
June 2010
• U;i t' n�nit�f
• Inlet and Outlet Pressure Gauge Taps
Figure 1. Type R622 Pressure Reducing Regulator
Introduction
Type R622 direct -operated, spring -loaded regulators
provide economical pressure reducing control in
a variety of residential, commercial, and industrial
telief
leight
applications. These regulators can be used with
natural, manufactured, or propane gases and have the
same inlet and outlet pressure capabilities.
® www.fisherregulators.com
%
�0
EMERSOM
Process Management
Bulletin 71.1:R622
Body Size and End Connection Style(1)
112 NPT inlet and outlet
Maximum Allowable Inlet Pressure(11
Operating: 125 psig (8,6 bar)
Emergency: 125 psig (8,6 bar)
Except 1.8 to 2.2-inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4,1 bar)
Maximum Allowable Outlet (Casing) Pressure(1)
Operating to Avoid Internal Part Damage:
3 psid (0,21 bar d) above outlet pressure setting
Emergency: 20 psi (1,4 bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
118-inch (3,2 mm) orifice
Flow Coefficients
Wide -Open CB for Relief Sizing: 12.5
Wide -Open C for Relief Sizing: 0.36
Cl: 35
IEC Sizing Coefficients
XT: 0.78
FD: 0.82
FL: 0.89
Flow Capacities
See Table 2
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Table 1. Outlet Pressure Ranges
Pressure Registration
Internal
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22-inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20-inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200% over setpoint
from 20-inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
314 NPT with removable screen
Temperature Capabilitiestl)
-200 to 1607 (-290 to 71 eC)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case, Diaphragm Plate, and
Orifice: Aluminum
Diaphragm, Disk, and O-ring: Nitrile (NBR)
Adjusting Screw and Pushpost: Delrin®
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc -plated steel
Machine Screw, Spring Seat,
and Lever: Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer,
Lever Pin, and Vent Screen: Stainless steel
he exceeaed.
Specifications
The Specifications section lists specifications forType R622
Pressure Reducing Regulators. As it originally comes
from the factory, specifications for a given regulator
are stamped on the spring case nameplate.
OUTLET PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WIRE DIAMETER
INCHES (nnnl)
SPRING FREE LENGTH,
INCHES (mm)
1.e to 2.2-inches w.c. (4 to 5 mbar)
T14453T0012
Purple
0.051 (1,30)
3AD (86.4)
5 to 7-Inches w.c. (12 to 17 mbar)
T14398TOD12
Grange
0.062 (1,58)
3.40 (66,4)
6.5 to 94nches w.C(161022 mbar)
T14399TDO12
YellrnV
0.067(1,70)
3.61(91,7)
9 to 134mGhes w.a. (2210 32 mbar)
T14400T0012
Silver
0.072 (1,83)
4.10 (104)
13 to 204nches w.c. (3210 50 mbar)
T14401T6012
Gray
0.080 (2,03)
3.60 (91,4)
16 to 35-tncheS W.0 (40 to 87 mbar)
T14402T00t2
Pin%
0.093 (2.36)
3.52 (89,4)
1 to 2.2 psig (69 to 152 mbar)
T144D3T0012
Light Blue
0.105 (2.67)
3.66 (93,0)