HomeMy WebLinkAboutPLANSSETUP AND INSTALLATION OF SINGLE WIDE SHED 1. BUILDING IS PLACED IN REQUESTED LOCATION ON SCHEDULE 40 PVC TO ALLOW FOR MOVEMENT TO PLUM OR SQUARE UNIT TO HOUSE, FENCE, PROPERTY LINE, ETC. 2. ONCE UNIT IS SQUARE AND THE HIGH SPOT OF THE GROUND IS ESTABLISHED, THE BUILDING IS BLOCKED ON THE HIGH SPOT AND LEVELED. THE OTHER END OF THE BUILDING IS BROUGHT UP TO LEVEL AND BLOCKED. THEN THE CENTER OF THE BUILDING IS SUPPORTED TO LEVEL, BLOCKED, AND THEN SHIMMED. 3. AFTER THE BUILDING IS LEVEL, MORE BLOCKS ARE ADDED TO ACHIEVE THE CORRECT SPACING (SEE TABLE 3). 4. ANCHOR PLACEMENT IS ESTABLISHED BY THE WIDTH OF THE BUILDING. HOLES ARE DRILLED THRU THE 2"x4" BOTTOM PLATE WITH A 1/2" AUGER BR. 1/2' EYEBOLT OR OPTIONAL 1/2" THREADED ROD (FOR A "HIGH SET") IS SECURED THRU THE HOLE. 5. ANCHORS ARE NOT REQUIRED IN THE BOTTOM PLATE FOR DOORS AND DOORWAYS WITH NO FOOTER (GARAGE DOORS FOR EXAMPLE). HEADER DESIGN TRANSFERS THESE LOADS. 6. IF THE UNIT HAS A FLOOR, EITHER A HOLE IS DUG FOR THE 30" AUGER ANCHOR AND BACKFILLED AND SECURED AS PER THE DETAIL OR A 1/2" HOLE IS DRILLED INTO THE CONCRETE 1-1/2" OFF OF RIM JOIST. THE EYEBOLT IS FASTENED THRU THE BOTTOM PLATE AND A SIMPSON A-24 (OR EQUAL) IS SECURED TO THE CONCRETE WITH A 1/2" WEDGE ANCHOR. 7. IF THE UNIT IS A 'NO FLOOR' OPTION, ANCHOR WITH 1/2"x5" WEDGE ANCHOR THRU THE 2"x4" BOTTOM PLATE. TABLE 1 ANCHORING TO CONCRETE SHED WIDTH UPLIFT (PLF) ANCHOR SPACING 20'-0" 400 3-e 13'-8" 280 3-B" 11'-8" 240 10,-0" 200 160 S-6" 6'-0" 120 3'-C TABLE 2 SKID RuNNER SPACING - SHED WIDTH X1 X2 X3 P-1or V-1C)" 2'-8" 6'-4" - 10'-O" 1"-7" 6'-10" - 8'-0" O'-9" 6'-6- 6.-0. 0'-10" 51" - *VALUES ARE FROM END OF JOIST TO CENTERS OF (2) 4"xe SKI05 ONLY. 8' WIDE SHEDS HAVE (4) SETS OF SKIDS. 1. BUILDING IS PLACED IN REQUESTED LOCATION. THE FIRST SECTION OF THE DOUBLE WIDE IS����>_ PLACED ON THE HIGHEST LOCATION OF GROUND AND IS LEVELED UP. 2. BLOCKS ARE THEN PLACED AT THE END, CENTER, AND OTHER END TO LEVEL ONCE THE BUILDING IS LEVEL, BLOCKS ARE ADDED TO ACHIEVE THE CORRECT SPACING (SEE TABLE 3). 3. THE NEXT SECTION OF THE SHED IS BACKED INTO PLACE AND UNLOADED PARALLEL WITH THE FIRST SECTION. THE TWO SECTIONS ARE CONNECTED AT THE LOWER CORNER WITH (1)j"x4j" BOLT AND NUT. THE SECOND SECTION IS THEN LEVELED AND THE OTHER BOLT HOLES ARE LINED UP AND BOLTED SECURE. THE REST OF THE BLOCKING IS THEN COMPLETED. THIS - - F; PROCEDURE IS REPEATED FOR MULTIPLE SECTION SHEDS UNTIL ALL SECTIONS ARE IN PLACE. CODE INFOR TION CODE VERSION EBc 2B+• Ea^�• Asa-' 4. GROUND ANCHORS ARE THEN ADDED (SEE TABLE 4B). 5. ONCE THE BUILDING IS PROPERLY BLOCKED AND BOLTED TOGETHER, THE SUPPORT BRACING IS REMOVED. MANUFACTURER MMUOR SEED BUILDING TYPE D "usm m 6. ANCHORS ARE NOT REQUIRED IN THE BOTTOM PLATE FOR DOORS AND DOORWAYS WITH NO FOOTER (GARAGE DOORS FOR EXAMPLE). HEADER DESIGN TRANSFERS THESE LOADS. I CONSTRUGTON TYPE Y-B ERE PBOIECnaN NONE TABLE 3A PAD TYPES TYPE PAD DIMENSIONS MAX. LOAD' MATERIAL 1 2"x8"x16" 1778LBS CO CRETE BLOCK QUALITY CEMENT AND SAND MIX II 4"x8"X16" 3500LBS CONCRETE CEMENT BLOCK QUALITY AND SAND MIX III 16"06" 395OLBS ASS PLASTIC PADS IV 8"x8"x16" 190CLBS CONCRETE BLOCK QUALITY CEMENT AND SAND MIX • BASED ON 2000PSF SOIL BEMING CAPACITY (2000PSF IS TYPICAL) i�HOOL OW OR SOUD CONCRETE BLOCKS (B"X9'XIB7 MAY BE STACKED ON PADS FOR HIGH SETS UP TO 48' WITHOUT REINFORCING. 2. ABS PADS REQUIRED ON 11'-8" AND IS-8' WIDE SHEDS ONLY. TABLE 3 SUPPORT FOOTING PAD SPACING FOR RUNNER BLOCKING FOR SINGLE & DOUBLE WIDE SHEDS SHED DESCRIPTION PAD MAXIMUM LOAD AND PAD TYPE SHED WIDTH TYPE LW(PLF) END PAD MAX. SPACING END PAD SIDE RUNNER PAD TYPE INTERIOR PAD SIDE RUNNER PAD TYPE 13'-B" SW/DW 4.15/332 Cr TO 6' 6'-0" 1936113 I, R, III. OR IV 1879L8 I, II, III, OR N 11'-8" SW/DW 6.00/480 0' TO 6" 6'-0. 2558LB I, II, III, OR IV 2555LB I, It. III, OR IV 10'-0" SW/DW 5.00/400 Cr TO 6' 6'-0. 2400LB I, II, III, OR N 2400LB I, II, III, OR N 8'-0" SW 4.00/320 0' TO 6" 6'-0" 2029LB I, II. III, OR IV 2133LB I, II, III, OR IV6'-0" SW 3.00/240 0" TO 6" 6'-0- 1658LB I, II, III, OR IV 1866LB I, U. III, OR N • LOAD W10M OF UPUFT ON RUNNER NOTES 1. PAD SPACING IS END TO CENTER OF PAD. 2. PADS OTHER MAN END PADS SPACING IS CENTER TO CENTER. 3. USE SAME MAXIMUM SPACING MR INTERIOR SPACING. GENERAL NOTES & SPECIFICATIONS FOR AUGER ANCHORS 1. BUILDING ANCHORS SHALL BE "MOBILE HOME" TYPE HP-1 SINGLE HELIX EYE AUGER ANCHOR BY HOME PRIDE OF BRISTOL. VA. OR EQUAL. AVERAGE HOLDING STRENGTH IS NOT LESS THAN 4,900 LBS. 2. ANCHORING SYSTEM TO GROUND PER LOCAL BUILDING CODE (BY DEALER). LOCATE ANCHORS PER TABLE 4A OR 49. 3. THREADED ROD WITH EYEBOLTS SHALL BE PLACED THRU THE BOTTOM PLATE (FLOOR SYSTEM) AND ATTACHED TO ANCHOR. THESE CAN BE EXTENDED WITH THREADED ROD (OR STRAPS WITH EQUAL OR GREATER STRENGTH) FOR ELEVATED PORTIONS OF SHEDS ON LEVELING BLOCKS. TABLE 30" AUGER ANCHOR SPACING 4A - SINGLE WIDE SHED WIDTH LW UPLIFT (PLF) END ANCHOR-- MAX. INTERIOR SPACING... 13'-8" 7.00 43 O-0' TO 3-0" 10'-0" II 208 U-T 10 Sme, 10'..=0" .. e 10,-0" 5.00 174 0'-0" TO 3'-0" 10,-0" 8'-0" 4.00 138 S-v TO N-O' 10'-0" 6'-0" 3.00 104 U-,T TO S-or 10'-0" TABLE B 30" AUGER ANCHOR SPACING - DOUBLE WIDE SHED WIDTH LW UPLIFT (PLF) END ANCHOR- MAX. INTERIOR SPACING••• 20'-0' 10.00 400 V-Cr 10 X-O" 5'-0" • LOAD IMOTH OF UPLIFT ON RUNNER •• LOCATION FROM ENO WALL OF AUGER ANCHOR ••• MAXIMUM SPACING BETWEEN ANCHORS NOTES 1. ANCHOR SPACING IS DESIGNED AS PER ASCE-7. 2. ALL MEASUREMENTS ARE CENTER-TO-CENTQL 3. THE MINIMUM NUMBER OF ANCHORS PER SHED IS (4). (1) ANCHOR PER EACH CORNER. ADDITONAL INTERIOR ANCHORS ARE REQUIRED IF SPACING 15 MORE THAN 10'-0' BETWEEN ANCHORS.. 4. ANCHORS SHALL BE ON S1DE WALLS EXCEPT WHEN THE SHED IS PLACED NM TO AN EXISTING BUILDING; IN WHICH ANCHORS CAN BE PLACED ON THE END WALLS AS CIASE TO THE SIDE AS POSSHIM Jr, SCABNNEL, Tx2" GALVANIZED WASHER St. Lucie` ^n 2"x2" GALVANIZED WASHER WITH 1/2" NUT WITH 1/2" NUTT 1/2" THREADED ROD OPTIONAL MR 'HIGH SET' NOTCH OR COUNTERSINK BOLT 1/2" THREADED ROD : OPTIONAL FOR "HIGH SET" ,f EYES BOLTED TOGETHER WITH 1/2'x2" BOLT & NUT WTH (2)2"x2" GALVANIZED 1/2' COUPLFFi THRU 214" BOTTOM PLATE 2"x4' BOTTOM PLATE NALED 1/2" COUPLER T va _ ,/q� 1/2"x12' FORGED EY®OLT F ♦' WASHERS (2.000LB SHEAR CAPACITY) �ONRETE i MIN. e 1/2WETIGE ANCHOR IONT)CSUB THRU 2'x4' P.T. BOTT)M PLATE TO 2"x6" P.T. BASE " MIN. u x EYES BOLTED TOGETHER WTTi 1/&x2 (SEE TABLE I FOR SPACING) __ �CONCRETE BOLT & NUT WITH (2)2"x2' GALANIf�r R p`1 WASHERS (2.000LB SHEAR CAP a� }�C��A' _ 1/213" (400 LBJ CONCRETE WEDGE ANCHOR (SEE (SEE TABLE I FOR SPACING) SIMPSON A-24 CONCRETE SUB BY OTHERS THROUGH CUP OR EQUAL LOCH_ CODES AND JURISDICTION SLAB BY OTHERS THROUGH LOCAL CODES AND JURISDICTION 30" EARTH AUGER AN G�� �,/V (SEE TABLE 4 FOR SPACI�iG)SHE SHED WITH SKID SHED WITH 'NO FLOOR' OPTION 1 ITF16'•• ``�j`�'` GC' ANCHORED TO CONCRETE ANCHORED TO CONCRETE TO PADiOR�BLOFI�IN� V TIE-DOWN DETAILS NOV zzafff .T I` %.0VF_ I' BASIC "No SPED V-2W EXPOSURE o ENCLOSURE CNaDSm INTERN&- FRESSURE COEFTQENT +/- ole IMPORTANCE FACTOR 1.18 ROOF DEAD LOAD Ims ROOF UVE LOAD 20Ps OR SWIIe FLOOR DEAD LOAD EPS FLOOR UVE UND m Taps - 12ws oPr. 'R' RATING OF WALLS• FLOOR ROOF I N/A MODULES PER BuILOING 1 HURRICANE PROTEOTON USAGE Na HURRICANE SHELTER USAGE ILO muA POOTAGE LESS TR1AY n4 SUET. REVISIONS REV DESCRIPTON DATE BY 1 2alT FBC 11/12/1T MB3 2 1 a/26/Ie I MR Cn W 2 0 W 0 ►? W _J m D 0 0 O'd W _J Z I W 0 C.D ARE NOT PART OF THIS GOVERNED BY LOCAL (EMPT FROM THE FBC ON CODE PER SECTION 3. REFER TO TIE -DOWN DETAILS FOR PROPER INSTAUAT10N REQUIREMENTS TO MEET CODE. 7/13/19 aftleW T Ba1dtP! FlDdda UOense 646( Sheet! D-1 OF PSI APPROVAL 201 f -18 Side Wall Header Schedule (180C) End Wall Header Schedule 80 mst ap r t o A SRe{d} i6ex. Spen N.11b} •• 04 ALUMINUM ROOF SHEATHING Building Width Fasteners w/strap leech end){c} > Size to W W le 1-2k4 6'-0" 0 <-3'x 0.13t' ndls -•- (each end) 2-2'k4 b- % .131' mars •_O• �, Max. Span NJ(b} a''-0'• O{d} 0 3-3'x 0131"nail a. eouet slues era r lo. yraae pmc In Ir uneer t 1 .j ro I n_ 0 1z RUNNERS m w END W TRUSS 2•x4• TRUSS. 0 24" O.C. MAX. x s b. NJ Number ofjack studs required to Gwpod each end. 4'k4'wated B-o. 1 6-3'x 0.131'nails o. Laid eat tT ` a. Tabulated values are for s r 2 grade Spruce rt a each lumber. - tl. No Jack sWd;, but 2xO studs laid gat. '-� r - b. NJ - Number ofjack studs required to support each end. c. Window header for window openings that have more than 50% combined stud wail above �� I✓�� "-'1 and below, otherwise use door header schedule. I. SEX FASRNFR swmulE Fw�ludoas ((' d. See header details far alternate layouts, i.e. 2-2•x4' or rx4• P.T. rs. ses kn r¢a e. The header can be attached to the t ate and thus have the combined strength a �XANDwXRLm4�oIga Mro bow top b 9t CODE INFOR ATION equivalent and use the maximum span stated. CODE vERRON rw 101' °b' ses- AlA gf Wu1 sews li " 5� 3•M- Exmaw i it sxruiHNc j I I - I E w� on cou I I I ' li 12-alz' w ibVo RI I mums ca (RYW rum w (IH•.4• seou 'a sruss—N YEIR 5 YQNn 12• VAX. - WNur Ism HYDROVENT DETAIL SIDE WALL WINDOWS END WALLS WINDOWS & (OPTIONAL) & DOORS DOOR 6' WIDE OR LESS 41e 4"x4" W/2ax4" MANUFWPURDR s W sxEOS BUIMNG TYPE us REO euua rssrx11Tu1 LAYM 70R CONSTRUCTION TYPE Y-B RRE PRO DN NONE FIRE SUPPRESSION SYSTEM NONE OCQIPANGI' sTwaOE ALLOWAaE NUMBER OF STORIES 1 BASIC WINO SPEED VrlelwgH uposuR c ENOUX3 R ENclosm ORFRNAL PRESSURE COEPRO W +/- D.la IVP ANCE Moroi 1.15 .ttwtteuk. ROOF DE LOAD 1O,sT G.F.I. - + NOTES -OPTIONAL ELECTRIC I5 b�icA� ROOF uvlz LMD tsu P aR swa IroWr wb OUTLET U FLOOR Oren LOAD IOMF -ALL WIRING SRAL- BE 14 GAGE 3-WIRE MC UBLE. {pp,=REY;FW SOURCE N II -ENCJSE IN ALL METAL BoxEs. .,. FLooR uvE tr>en su TaPSF- 12rJSF M. DEIGN PRESSURES L FI R• RATING OF WAILS, BOOR ROOF N/A ROOF +27.8 -947 ROOF FRAMING PLAN WIRING DIAGRAM :rx.JJmsmn+ V4u. rlddy rm MODUtEH PER BOILBIM WALLS/DOORS INDOWS +32.5/-29.2 (OPTIONAL) HURRICANE PRpTECIION USAGE No FLPEa9E3)s,WPEN 17 " SuaFawNae.Tx PEnJasA HURRICANE SHFLTER USAGE NO WIR be M YG me WVL W��. IpaTxJls YM! soI PDoTAGE 'r19 Sa3T. OR Loa REVISIONS sees'k. 2-•4• . r '�0 RTu1 REV DESCRIPfON I DATE IBY m ALUMNuM WALL sMm*4c wnaNs i Y W. r MUL 24 sLE HFMFIi CETUL x- oe � i i Le m9aRn oN NsmE � W Omwn eP MT13 2.4 maaaxc i ZO 12/12/17 g ^ Saale: eo Wut F N/A 2if a, nJ 9F M,E ul w = to mar 24• °F' 'Lin, Rnon nuldNe SS-B-180CR7 2.4 SUE MR RNR FFWIaJc z.4 saR Mrz W � I. FdIN¢UttNI FlAVS NS Ipr PMIr Ci iN5 R.41 5£T .Wa Al2 LJ W9UdD BY LM JIt®KTxJI. 3. BUYOINa 5 Flid1 1XE FHL FNFALY LdI50A'AIKKI Aid duos Rn'Rn ro saE W J COD IO1a2L FOR 1011 - A'♦a maw nWUNc N1m ao]9• d ]. FeaER T nE-w/LN�onas FUR RmPw gsruLawN M -T lJ J E+mm).1r STRAP p/`-1. xuLs STANDARD WALL DETAIL- N R°LL INc UENeERs u¢ camNuous FRdI Q : REoln To moo A. ILL RYlwi TRU556, ETL APE LJ i3 aFE. IX�f LI LJ �� OR EPIk WITH DOOR &WINDOW OPTIONS FDIINMIWN 4LL 10 0.CCi IhD 3DPirp Ta ENSllff A whRNuaus laa P.l1tL WI WNL �E 9M Ir¢ O STIGS. As Halm. ARS W' ro W-a• urns • ro u'b• Nor wNnNvals suET MRAL aMk'^ 11q w �s V) U s. sFtvcnmLs aiFx Jw sc. Fv MLL H vs AN eo• MWWW ELEVATION CROSS-SECTION END ELEVATION rb- P.r. Amain Wml - ]/J' P.T. RHIOOD ]/J- aWll RE OS lT OALYA M ar Nar IESS TNAv avow- NWNAL TmaNLss w Ww. a. rm1Da ro s 9pTJrIm oN-s11E or olxms lxRu IJxx TYPICAL ARCH FRAME WITH DOOR In4 w Eauxgea. SEE TARE 2 rw auwmm Jno - Tx - ]/4- P.T. cle w O_ (n O cw¢ T. Mi N1NwWs ANv boas To MRi THE MNIMUM SPEa roNs mPaNa •a U (2)YW LUD MT 3•1 M. D WS 2Y6• IJe MT rs,4 sOR MTELLH I nM nWMW U lJ LJ Pg Ll Ares CTo Lr-0• a•-0• ro Irb- END ELEVATION END ELEVATION '-0• NAx K 51Fa ✓s. 11 II Y] tr-r E-1W v-far 1'-mp - 10'-0• 1'-T a-ue - • a'-P• Y-C - 9'-0• s'-O• a'-19• el• YF I w.lxx wra®wcrp o r • o I 1 I I D g I j LB P.T. 2J• O.c. T19. w11GNF1 123PSF O la• O,G I Tin. W" 3/4- W RYBLWar 1 444• P.T. Arr T am, H24 OR EM'NFNT. sm TARE 2 Ew wM1111Y ANO WR3NE. a 1 I 1 v W aA1M11T1 T FKLfoxa6sIo1.11 eUaE 10N RA➢. UMBERSwWNSNXTMS]amo. m vO Noue socuee g oba 00ESNbeR I Q LLJ = '� (10 _ Q C�7Art % STATE ; �/v` p MouheW T. BaldWin P.E. Z Florida License 64608 WRHOUT DOOR WRH GARAGE DOOR Row JoSn sLE somxE FOR ss J (MY ON c4sxo FLOOR FRAMING PLAN F m Sheet: SSB-1 OF 1