HomeMy WebLinkAboutPLANSDESIGN CRITERIA: APPLICABLE CODES REGULATIONS & STANDARDS 1. THE 2017 FLORIDA BUILDING CODE, SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CH. 23 WOOD. 2. AA ASM 35 & SPECIFICATIONS FOR ALUMINUM STRUCTURES, PART 1-A OF THE ALUMINUM DESIGN MANUEL PREPARED BY THE ALUMINUM ASSOCIATION, INC. WASHINGTON D.C. 2005 ED. 3. ASCE 7-10 & SET 4. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 5. ACI318 CONCRETE REFRENCE MANUAL. WIND LOADS 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1664.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. WIND LOADS PER FBC TABLE 2002.4 (MWFRS) VULT = 150 MPH & EXPOSURE = C FOR 20 X 20 X 0.013" MESH SCREEN HORIZONTAL PRESSURES ON WINDWARD SURFACES = 43 PSF HORIZONTAL PRESSURES ON LEEWARD SURFACES = 34 PSF VERTICAL PRESSURES ON SCREEN SURFACES = 12 PSF VERTICAL PRESSURES ON SOLID SURFACES = 36 PSF FOR 18 X 14 X 0.013" MESH SCREEN, APPLIED FACTOR = .88 FOR ALLOWABLE STRESS DESIGN, APPLIED FACTOR = .6 FOUNDATION DESIGN FOOTING SIZE EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM F'x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. SPECIFICATIONS THE FOLLOWING SPECIFICATIONS ARE APPLICABLE TO THIS PROJECT: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: a. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 - ASTM C 150 ii AGGREGATES - LARGE AGGREGATE 3/4 MAX. - ASTM C 33 iii. AIR ENTRAINING+/- 1 %- ASTM C 260 iv. WATER REDUCING AGENT - ASTM C 494 v. CLEAN PORTABLE WATER vi. OTHER ADMIXTURES NOT PERMITTED b. METAL ACCESSORIES SHALL CONFORM TO: i. REINFORCING BARS - ASTM A615, GRADE 60 v. WELDED WIRE FABRIC - ASTM Al85 c. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. d. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1. 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. e. MOIST CURE OR POLYETHYLENE CURING PERMITTED. T. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. g. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. WHEN PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT 3. WHEN APPLICABLE FOR NEW SLAB ADDITION TO ADJACENT DRILL & EPDXY #5 X 8" REBAR INTO EX. FOUNDATION WITH 1"MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) 48" O.C. TYP. ALL LOCATIONS 4. WHEN APPLICABLE FOR NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH I" MIN. HOLE, EMBED 6" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHERWISE NOTED. ALUMINUM SPECIFICATIONS 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE NOTED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH # 12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING U.C. 5. 1 "X2" & 1"X3" NON STRUCTURAL MEMBERS MAY BE USED INTERCHANGEABLY. FASTENER SPECIFICATIONS 1. FASTENERS ARE REQUIRED TO BE SAE GRADE OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG. SPECIFICATIONS) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, FASTENERS AND SCREENS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1 /4" X 3-1 /2" GAILY. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1 /4" X 2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14 X 2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE # 10 X 1-1 /2" SMS OR TEK SCREW AT 2C O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW' SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. MISCELLANEOUS 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME: IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE 2 x 4 SMB: 2x4'k0.04N'x0.100" UNLESS OTHERWISE INDICATED. RESPONSIBILITIES 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND ENSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW' MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2'k0.044" 2 x 3: 2x3"x0.050" 2 x 4: 2"x4"x0.050" 2 x 5: 2`xS'x0.050" OPEN BACK SECTIONS 1 x 2: 1'k2"x0.044" 1 x 3: 1 "x3"x0.045" SNAP SECTIONS 2 x 2 SNAP: 2x2'k0.045" 2 x 3 SNAP: 2"x3'k0.050" 2 x 4 SNAP: 7'x4"x0.045" SELF MATING (SMB) 2 x 4 SMB: 2x4'k0O44'k0.109' 2 x 5 SMB: 2"x5"x0.050NO. 100" 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SMB: 2'k7"x0.057'k0.120" 2 x 8 SMB: 2'k8"x0.072'k0. 124" 2 x 9 SMB: 2'k9'k0.082"x0.124' 2 x 10 SMB: 2"xl 0N0.09Z'x0.398" DETAIL A SCANNED BY St. Lucie County NpV I TO c®p'y Allp" a�FO'l CO E CCMpL1AN T�° T�°ST. LUCIE CpUN BOcc CDN r co z Q E D C)U p U J O 00 rn J 47 LL Lo .� � L LLI c- N I- m C c- I- G QcO�a�i G Q w Q 2 H U 5 r O u Ui d a w rn f O V M 0) I Z O F U 7 u U U J Z } OQ Z Um W F- LU J LL W a�� K w z U rc LLLIJ U O o ¢ W O 0 -.1� a z 0 0 a DESIGN DATE: 11/13/2019 REVISION 1: DATE REVISION2: DATE PAGE: DRAWN BY: KMM SCALE: NTS 6o WALL HEIGHT PER PLAN +_m I �A mo r____—_---\ Ln 1X3 N x w 0 CDX 2X3 L'- - m 0 o N cn = w W w 4X4X.125 N x CD N 07 n OD C3 DJ 2X3 DJ 1X3 to O gmmz A A O CONTRACTOR: m o o PIONEER SCREEN LLC m z z 0 y m z m PROJECTADDRESS: m MILLER/PAULEY CONSTRUCTION 1651 NW SWEET BAY CIR IV m PALM CITY, FL 1X3 N x w x 0 cn 0 0 D G� W D m m -o FLORIDA ENGINEERING LLC 4161 TAMIAMI TRAIL, UNIT 101 PORT CHARLOTTE, FLORIDA 33952 (941) 391-5980 www.fiengineeringlic.com PROJECT NO. 1931640 CA CERT. #30782 E. GunEirrSoF, P.E. #60102 11/13/2019 FLASHING -x2" FASTEN TO COL. (INTERNAL) W/(2) #IOXLI/2-SMS, FASTEN TO EAVE RAILS ABOVE W/ #10X1-I/2"SMS 24- O,C. AND 6- FROM END. TABLE 'D' NG<m TY Shc. SIOE/SIZE 2 x 3 4/12 2 X 4 5n2 2 X 5 5/12 2 x 6 6/12 2 X 7 7/12 2 x 8 8/14 2 X 9 9/14 2 X 10 9/14 'HORIZONTAL OR SLOPED BEAM PER PLAN NOTCHED 70 RECEIVE COLUMN WITHIN EMS. (EACH SIDE) STY PER TABLE D NOTCH PROFILE MAY VARY TO PERMIT CORRECT IF SMS COLUMN PER PLANS MAINTAIN MIN. OF 5/B•SEPERATION FROM EDGE OF BEAM SMS O.C. TVP. DETAIL "E" - UPRIGHT TO BEAM CONNECTION SCALE: N.T.S. NOTE: IF PAVERS ARE PRESENT, CONCRETE ANCHORS SHALL PENETRATE INTO FOOTING 2-1/4' MIN. (TYR NOTE: WHEN FASTENING TO WOOD USE 1/4' GALV. LAG SCREW IN LIEU OF CONS, ANCHORS AND ENSURE PENETRATION MIN 2-I/4- INTO STRUCTURAL FRAMING BENEATH (TYPS 1/4' DIA. TAPCON SCHEDULE UPRIGHT CITY. TAPCON/ CITY. #12 SMS E/S 2X3 (1) 1/4" TAPCON/ (4) #12 2X4 (2) 1/4" TAPCON/ (4) #12 2X5 (2) 1/4" TAPCON/ (4) #12 2X6 (3) 1/4' TAPCON/ (6) #12 2X7 (3) 1/4' TAPCON/ (6) #12 2X8 (4) 1/4" TAPCON/ (8) #12 2X9 (4) 1/4" TAPCON/ (8) #12 2XIO (5) 1/4" TAPCON/ (10) #12 SCHEDULE BASED ON 2-1/4' MIN. CONCRETE ANCHOR EMBEDMENT 1/8'#'x2"X ANGLE 5032 H-32 ANGLE (2) - 912 SMS INTO COLUMN I/L' MASONRY ANCHOR EACH ANGLE - EACH SIDE COL_ 2-1/4-MIN. CONIC. ANCHOR EMBEDMENT 3000 PSI CONIC. AB/ FTG. x10 WWM SIDE VIEW OR FI OR FIBERMESH MASONRY ANCHOR AT AT EACH ANGLE HO —Iry T (2) #1OX TO BE BEAM INSTALL OF TO CORNEP 3/8' DIA. TAPCON SCHEDULE UPRIGHT QTY. TAPCON/ OTY. #12 SMS EIS 2X3 (D 3/8' TAPCON/ (4) #12 2X4 (2) 3/8" TAPCON/ (4) #12 2X5 (2) 3/8' TAPCON/ (4) #12 2X6 (2) 3/8' TAPCON/ (6) #12 2X7 (2) 3/A' TAPCON/ (6) #12 2X8 (3) 3/8" TAPCON/ (6) #12 2X9 (3) 3/8" TAPCON/ (6) #12 2XIO (4) 3/8' TAPCON/ (8) #12 SCHEDULE BASED ON 2-1/4' MIN. CONCRETE ANCHOR EMBEDMENT -SELF-MATING OR SNAP SECTION TYP- PER PLAN E2- O.B. BASE PLATE-TYP. 1-1/4' MIN GOING, ANCHOR EMBEDMENT •' a 2- MIN. ANCHOR SPACING WHEN GREATER THAN 2x4 UPRIGHT IS USED SEE ° ^ TAPCON SCHEDULE ABOVE 2 - #12 SMS 1/4' LANDON XL (RED HEAD MFG. OR EQUAL) 2 @ IXB BASE 2 @ SLAB (BEYOND) II• Rx2'BASE PLATE ANCHORED ® TO CONE w/ /4- MASONRY ANCHOR 6- MAX EACH SIDE " OF POST AND 24. O.C. MAX 3000 PSI CONIC. " SLAB/ FTG. 6X6-1omo WWM FRONT VIEW OR FIBERMESH DETAIL "B" - 2"W' OR LARGER SELF MATING UPRIGHT TO DECK DETAILS SCALE: N.T.S. (2) #MD' SMS INTO SCREW BOSSES FOR EDGE MEMBER EDGE MEMBER OR PURLIN - DETAIL "D" - ROOF BRACING CONNECTION SCALE: N.T.S. ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL %WA) #10X.75- INTO GIRT OR PURLIN B (2) MAX. ZS INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED (4) FIOZM SMS INTO SCREW BOSSES EDGE MEMBER y A_ OR PURLIN 0.06Z5- 6063-T6 FLAT PLATE w/(W ISMS, MIN, I/2' rN PURIIN D EDGE DISTANCE. E. PLATE MAY BE FASTENED INTERNALLY TO BRACE UPRIGHT, BEAM -SNAP, MEMBER SELF MATING. OR HOLLOW DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: N.T.S. 'ALL MEMBERS PER PLAN PAGE 2'X2"n.063-- DIM, TO MATCH PURLIN 'MEMBERS VARY PER PLAN PAGE 2 SIZE RECEIVING CHANNEL (2) #12 SMS INTERNAL TO HAVE RAIL (3) #12 EACH SIDE INTO PURLIN o zP�a�1H'L FASTEN TOP OF HEADER TO INTERSECTING MEMBER w/(2)#10 SMS w/I" PENETRATION INTO SCREW BOSS OF EAVE RAIL - SEE PLAN MEMBER - TYP. BOTH SIDES OPEN BACK EXTRUSION UPRIGHT v DOOR JAMB PER PLAN FASTEN HEADER 1/(2) #10X3' INTO SCREW BOSS OF HEADER ALTERNATE HEADER CONNECTION WHEN Z-BAR IS USEO-FASTEN Z-BAR TO COL/HEADER AT EACH - CORNER AND IF O/C ALTERNATE BASE PLATE CONNECTION ATTACH MEMBER TO BASE PLATE (INTERNAL)w/(2) #IOXY SMS ATTACH BASE PLATE TO MEMBER w/Q) #10X3- SMS INTO SCREW -� BOSS OF BASE PLATE 4. a UW TAPCON (RED HEAD MFG. OR EOUAU WITHIN 6- OF COLUMN 8 24. O.C: MAX. 1-1/4' PENETRATION INTO UNDERLYING FOOTING DETAIL "F" - DOOR JAMB & HEADER CONNECTION SCALE: N.T.S. (2) #IOxZ' SMS THRU Ix21NTO EAVE RAIL EACH S1DE OF COLUMN DETAIL "G" - SLOPED PURLIN CONNECTION SCALE: N.T.S. 04 #12x1'SMS @ 1- SPACING - ZX2- EDGE BEAM 1 (2) #IOx3'SMS INTO SCREW BOSSES CONNECTING EDGE BEAM TO PURLIN � 1-1/2'x 1/16-PLATE (TOP OR BOTTOM) EX2'FASTENED TO COLUMN w/(2) #IOM-1/2'SMS INTO SCREW BOSSES FOR SMB OR SNAP COLUMN NOTCH COLUMN AS REO'D. COLUMN PER PLAN r J O Lo r M (1� co z Z_N�o_ Q E o LL of O U W -j 0 00 - W Q LL Lr) •F Z N LL Ld a) L a) r—~I-Mc V — I- c'— Z < O Q� Q O� Lo.(- r LL LL ALTERNATE DE"G" SLOPED , - Toll CI PURLIN CONNECTION SCALE: N.T. !e W O K W U U (] (h d1 O Z U LLI NO w a- z O_ U UU U J z } OQ zLU Um D J W LL DI w DO ILI air ��:U w O G w Z YC O K U J J Do Q D- W O a DESIGN DATE: 11/13/2019 ISION is DATE REVISION 2: DATE PAGE: DRAWN BY: KMM SCALE: NTS GIRT FASTENED INTERNALLY AT EACH END wl AIOxIS' EACH SCREW GROOVE. FASTEN TO BEAM W/ 2x2x.125 ANGLE (2) #12 SMS INTO BEAM 8 (2) #I0xl.5 THOU ANGLE INTO GUTTER WHERE NO GIRT 15 PRESENT. ATTACH ANGLE DIRECTLY TO GUTTER -� 2'x2 ANGLE #12 EACH LE sns LEG G BEAM CLOSE BOTTOM OF ° BEAM WHEN TRIMMED .044 RECEIVING CHANNEL, FASTEN .1#12 SMS EACH SIDE OF BEAM GIRT #10 SHE WITHIN 6- OF BEAM 8 24' 0 C. 2x2I,11W ANGLE EA. SIDE OF BEAM w/(D #12 SMS EACH LEG EACH SIDE FOR BEAMS ABOVE 243 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS B INCLUDE 2' GUTTER BRACE AT EACH BEAM LOCATION FOR GUTTER TO FASCIA: (z)5iiz sns (1) #14 @ Ia. 0 C FOR GUTTER BRACE/ STRAP: (2) #I4 EA. STRAP SEE TOP VIEW FOR BEAM OVER 24 -044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER INTERNALLY WIGS #12 SMS ALTERNATELY 2x2MUIF ANGLE BELOW GIRT, (2) #I4 SMS INTO BEAM a (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW JTTER TO #ICx2' IEW 18' O.C. S EW 'x6'MIN. EXISTING) ?AL TOP VIEW DETAIL "H" BEAM TO GUTTER CONNECTION SCALE: N.T.S. .050' GUTTER STIFFNER FASTEN TO FASIA w0 WOOD SCREW FASTEN TO GUTTER W2) #12 SMS — GUTTER GUTTER WHEN BEAM 8 PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM 6 PURLIN I Il8X2'x2' ANGLE B (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (B EAM TO PURLIN) / 118"x2'n2' ANGLE w1(2)#12 SMS INTO EA: MEMBER (BEAM B PURLIN) DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE: N.T.S. (U 4% WOOD SCREWS (2) #12 SMS INTO FASCIA 2x2x1/8'ANGLE wl$SMB GIRT #12 SMS EA. LEG GIRT 0 0 I/8-x2'x4- STRAP STRUCTURAL GUTTER INTO (D #125MS INi08EAM SIDE VIEW (2) #12 SMS GUTTER o o p � o A p F 1 91 ° DI O I 01 pl F o to GIRT le (2) GUTTER BRACES \\\ F FASCIA EACH w/E) OR SMS INTO \\ �'O o 3/16'-5052-H32 GUSSET WOOD SCREWS INTO FASCIA F INTERNAL OR EXTERNAL \ 8-INTO EA. SIDE TYP. 2x2x1/8-ANGLE WGO F BXIOSMB ]ILLUSTRATED) #12 SMS EA. LEG 9 NOTE F INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 3/8- MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-I FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN UT SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8- MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8- OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 TABLE B-1 .M Sim COL. TO BEM GTY SMS/ SIDE OF wL BE>M TO BEAM .0 SML FACE/SIDE 2 x 4 (5) #12 (9)#12 2 x 5 (5) #12 (9) #12 2 x 6 (7) #12 (9)#12 2 x 7 (10) #12 (10) #12 2 x 8 (12) #12 (14) #12 2 x 9 (14) #14 (14) #14 2 x10 (16) #14 (I5) #14 DETAIL "K" GUSSET CONNECTION SCALE: N.T.S. SMB e 1 1 1 1/e'x2'x4'STRAP (2) #12 SMS INTO BEAM GIRT (2) #12 SMS INTO GUTTER STRUCTURAL GUTTER TOP VIEW DETAIL "L" CORNER GUTTER CONNECTION SCALE: N.T.S. 1/8- PLATE ON 450 ANSI OR 1/8'TT#' ANGLE W/I #12 SMS INTO EACH INTERSECTING MEMBER PERIMETEI FRAMING DETAIL "1-2" CABLE CONNECTION AT CORNER SCALE: N.T.S. 1/8'STAINLESS STEEL 400 MIN. BRAIDED CABLE. 600 MAX. EBOLT FOR BILE TENSION 1/8'STAINLESS STEEL BRAIDED CABLE 3000 PSI CONC. 6x6-10x10 WWM OR FIBERMESH N O O W a a ~ C O N N a M C � W .. U r N N ♦I� co J Z Z �_ E U W p U U U LJJ -J 000 W < im LL• in •� Z otf enLLI ~ or) M C W Q 0� a� Q U 0 r co V a m r O z I— U W O a / O < d U ' MIN. SLAB /FOOTING 3/8' OIA x 3' EMBED U V) U CONC.SCREW ANCHOR (TAPCON OR EQUAL) J Z } J 3000 PSI CONC. Z LU O m 6 6-IOxIO LOB MIN. SOB OWN OR FIBERMESH LLI N.I Lu-i 600 MAX. 0-1 J W LL. 0 U • #• W N D_F �zU o s. LIE BE Ul p Z Q J Q DO —1O U cJ fOEL 4' MIN. BLAB � D.. W a ' rv/FOOTING LS'x5.5'ALUM. STRAP Z O w/(2)1/4'OIA, x 2-1/1 0 of MASONRY ANCHOR 0 OIL (TAPCON OR EQUAL)tal DATE: 1DATE19 REVISION::GN REVISION 1: DATE DETAIL "I -I" CABLE CONNECTION „r EON, AT FOUNDATION SCALE: N.T.S. ��� REVISION 2: DATE PAGE: DRAWN BY: KMM SCALE: NTS 3/16" 5052-H32 GUSSET 2" X PURLINS ATTACH TO BEAM WITH MIN (4) #10 X 1 1/2" SMS PLACE WASHER UNDER SCREW IN GUSSET CORNER 1 114" #14 SMS @ 1 1/4" O.0 CORNER POST x NOTES: 1. GUSSET DIMENSION ARE MINIMUM (2) REQ'D (1) EA SIDE OF BEAM - MAYBE INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1-1/4" C/C SPACING 3. GUSSETLENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. RAIL 1"x2" O.B. PATIO SECTION 3" x 3" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) WITH (3) -912 x 3/4" S.M.S. EACH SIDE AS 10WN (3/8" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) LATERAL "K"-BRACING CONNECTION DETAILS K-BRACE GUSSET PLATE PER E-SERIES 3" x 2" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) (3) - #12 x 3/4" S.M.S., EACH SIDE AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) 'ANGLE 1' INTO EACH DICATED BELOW DETAIL #2 i CORNER POST (2) #10 X 1 THRU SCREW SLAB/FOOTING NOTES: SEE PLAN 1. CONNECTION DETAIL AT EAVE RAIL SIMILAR SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 X 2" SMS THRU BRACE INTO BEAM THRU GUSSET PLATE POST BRACE 3/8" 0 CONCRETE ANCHOR (2 PLATES) FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "K"-BRACING CONNECTION DETAILS 1" X 2" O.B. FASTENED TO CORNER POST W/ #12 X 1 1/2"SMS AT 6" FROM TOP & BOTTOM RAILS TYPICALLY @ 24" O.C. , 1/8" X 2" X 2" EXTRUDE ANGLE 5052 ' H-32 ALLOY EA CORNER W/ (2) #14 X 2" -SMS INTO POST &(1)3/8"DIAL CONCRETE SCREWANCHOR INTO - '- CONCRETE 6" SIDE VIEW CORNER K-BRACE DETAIL SCALE: N.T.S. (4) #14 X 3/4" SMS INTO POST 1" X2" BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C: MAX CORNER POST W/ V X 2" @ BACKSIDE 3/8" X LENGTH AS REQUIRED FOR 21/4" EMBED CONCRETE SCREW ANCHOR INTO CONCRETE FRONT VIEW CP- CORNER POST TO CONCRETE DETAIL A-4 SCALE: NITS N O O b W a a 0 ~ O w N m M a „y c � W U r N O Lo J M � r1 M ZZ0 0 — D — U 0Y p U Lu LLB Q -1 J 0) LL Lo ~_ � W L fl1 H M C_ Lu Q .. Q 0 <- U F- O C° O --J � � 0_ LL 0 v c` ) O) I Z O F- U 6" x 5" x 0.050" COLUMN 6063-T6 ALLOY PLATE (ONESIDE)OR STRONGER 2x2%0.093 () U) U BRACE (TYP.) J Z } K-BRACE Z C) 00 W >_�- 2 x 3 x 0.070 CHAIR RAIL of J W LL O 0 O O O GIRT (CHAIR RAIL) W U o Z K-BRACE O Z ¢ -1 O O O,, ¢ a w e d 2x2x0.093 z 00 0 u BRACE(TYP.) (11 TOTAL)-#12 x3/4" S.M.S. AS SHOWN (112" MIN. 1� r1p1j DESIGN DATE: 11/13/2019 SIGN 1: DATE PLATE EDGE DISTANCE & C-C FASTENER SPACING) ``11 LL to DATEaPAGE:DRAWN LATERAL "PC' -BRACING `� � CONNECTION DETAILS R VISION 2: BY: KMMSCALE: NTS A. MACHINE (w%IBOLTS 3/4"DA. WASHERSi THRU CARRIER BEAM & POST BEAM ® CARRIER BEAM `I'X 'MEMBER FOR SCREENING VARIES HORIZONTAL BEAM ON ITS SIDE POST (IF REQUIRED) �2k2k0.125' T' FOR SINGLE RECEIVING CHANNEL HORIZONTAL BEAM OR ANGLE EACH SIDE 4" FOR DOUBLE HORIZONTAL (6)#101 BEAM OR 4'k4" EACH SIDE 6'FOR TRIPLE HORIZONTAL BEAM OR 6X6 OF(6)FO 2R ROWS 2 ROWS OF (6) FOR RECEIOR OR (61 EACH ANGLE EANG CH CARRIER BEAM TO POST DETAIL SCALE: NTS OVER GIRT AND CUT TO FIT BROW GIRT. FASTEN EACH LEG W/ (2) # 12x5/9 SMS STIFFNER CARRIER #10xl-1/2'SMS @24' O.C. MAX CONNECTING TO 1'X2' CARRIER BEAM # 1 Oxl-1 /2' SMS Q 24" O.C. MAX CONNECBNG- ROOF BEAM (SLOPED OR FLAT) (NOTE USE SIMILAR DETAIL FOR NOTCHED UPRIGHT CONNECTION TO CARRIER BEAM NOTE: FOR DOUBLE OR TRIPLE CARRIER BEAM, OUTSIDE WEBS SHALL OVERLAP 4x4 POST OR NOTCH POST S ABOVE FOR 6x6 POST. ALL CASES, CONNECT USING MACHINE BOLTS DECRIBED ABOVE. ROOF BEAM TO CARRIER BEAM CONNECTION DETAIL SCALE: NTS I /8'x2k2' x LENGTH CUT TO FIT ANGLE ROOF BEAM TO C.B. W/ REC. CHANNEL TABLE BEAM SIZE QUANTITY/SIZE LEG TO BEAM E/S QUANIItt/SIZE TO BEAM. INTERNAL 2x4 (4)012 OR(2)IT 16 (8)#12 OR(3)#I6 2x5 (5)#12 OR(3)#16 (10)#12 OR(3)#16 2x6 (5)#12 OR(3)#16 (10) #120R (4) # 16 2x7 (6)#14 OR(4)#16 (12) 914 OR (4) 916 2x8 (7)#14 OR(4)#16 (12)#14 OR(6)#16 2x9 (8)#14 OR(5)#16 (14)#14 OR(6)#16 2.10 (9)#14 OR(6)IT 16 114)#12 OR(7)A16 EACH SIDE OF BEAM FASTENED (2) 1/2' DIA. EXPANSION BOLTS W/ (4) # I N5/8" SMS TO BEAM SEE NOTE #2 THIS PAGE (2) 1/4" TAPCON INTO HOUSE WALL FOR BOLT PLACEMENT 2-1/4" EMBEDMENT MIN. ALTERNATELY RECEIVER CHANNEL MAYBE USED IN _ LIEU OF 1/8" ANGLE EA. SIDE EXISTING HOST STRUCTURE (DESIGNED BY OTHERS) BEAM PER PLAN o 0 0 CLOSE TOP OF SIDE VIEW BEAM WHEN TRIMMED .044 RECEIVING CHANNEL, BEAM TO GUTTER/HOST CONNECTION SCALE: NTS NOTES: 1. 3x3 POST TO HAVE 3/8" RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 2- FROM EDGE OF SLAB AND PROVIDE MINIMUM 2'SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. THREADED ROD REQUIRES 3" MINIMUM EDGE DISTANCE 2. 4x4 POST TO HAVE I /Z RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 3-3/4" FROM EDGE OF SLAB AND PROVIDE MINIMUM 3-3/4'SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. 3. WHERE PAVERS ARE PRESENT ANCHOR LENGTH SHALL BE INCREASED BY THICKNESS OF PAVER NOT TO EXCEED 2-1/Z FOR PAVER THICKNESS MORE THAN 2-1/2'SPECIFICATIONS SHALL BE REQUIRED. PAVERS SHALL BE BONDED TO UNDERLYING CONCRETE FOUNDATION. O CARRIER BEAM 0 ,CHINE BOLTS ISHERSTHRU & POST BEAM (A. M,ACHINE BOLTS W/I3/4' DIA. WASHERS THRU CARRIER BEAM & POST (3)1/4" DIA. MACHINE BOLTS POST w/ 3/4' DIA. WASHERS THRU CARRIER BEAM & POST FRONT VIEW CORNER CARRIER BEAM CONNECTION DETAIL SCALE: NTS BOLTS wD/IW SHE SINE 3-3/4' FROM EDGE OF SLAB/ FTG. TOP VIEW 4'k4" POST (SEE PAGE-2 /S FOR SIZE) �VVV/ •�T� —2k4k0.125 ANGLE 3000 PSI CONC. SUB/FTG. FRONT VIEW 6x6-10x10 WWM OR FIBERMESH NxN' POST CONNECTION DETAIL SCALE: NTS b r J N Lo J rn co Z Z�❑ < E o p U LuJ000rn W Q LLLn.L CDc� M C Z c C /Oy Q < U O C° J r o a L.L.. TOP VIEW z O COLUMN PER PLAN H (3) IDIA. MACHINE U BOLOL TS w/WASHERS � (4)3/9T (LENGTH) ANGLE (I(INTERNAL)U) THRU BOTTOM LEG MLEG OF ANGLE INTO CONIC. O Q Z Um • w LLI WLL. •e• J .. < U) 3000 PSI CONIC. W CL > U SUB/FTG. FRONT VIEW W 0 W Z 6x&IOXIO WWM O Z O OR FIBERMESH 4X4 COLUMN ALT. BASE ATTACHMENT U a F Q J; J m Q DETAIL SCALE: NTS z n o a 0 Im 0 a 11/13/2079 ��®p Q • EVISIONATE: 1. �REVISION 2: PAGE: AWN BY: KMM SCALE: NTS