Jamb Connection
Supplement
This document provides a series of connection schedules and basic detailing concepts for the
connection of garage doorjambs to building frames with the use of various fasteners.
DASMA Technical Data Sheet TDS-161 may be used as an alternate to this document.
PM 324620 Rev. P10
SCHEDULEI
3/8" DIAMETER LAG SCREWS
MAXIMUM SPACING OF LAG SCREWS
PER JAMB IN
MAIN SUPPORT MEMBER SPECIES
SYP
SPECIFIC
GAVITY-0.55
DOUGLAS FIR
SPECIFIC
GRAVITY -0.46
SPF
SPECIFIC
GRAVITY -0.42
LOAD PER
JAMB LBIFT NOIE3
100
24
24
24
120
24
24
24
140
24
24
24
160
24
24
24
180
24
24
24
200
24
24
24
220
24
24
24
240
24
24
24
260
24
24
22
280
24
23
20
3o0
24
22
19
320
23
20
16
340
21
19
16
360
20
18
16
38D
19
17
15
400
18
16
14
420
17
15
13
440
16
15
13
460
16
14
12
480
15
13
12
500
14
13
11
520
14
12
11
540
13
12
10
560
13
11
10
58D
12
11
9
60D
12
11
9
620
12
10
9
640
11
10
9
660
11
10
8
680
10
9
e
700
10
9
8
720
10
9
e
740
10
8
7
760
9
8
7
780
9
8
7
800
9
8
7
1. BASED ON 3/8" DIAMETER LAG SCREWS WITH 1-1/2" O.D. WASHERS WITH A 1-9/32"
THREAD PENETRATION INTO SEASONED DRY WOOD SUPPORTING STRUCTURE.
2. PROVIDE QUANTITY OF LAG SCREWS AS REQUIRED TO MAINTAIN MAXIMUM SPACING AS SHOWN IN
TABLE WITH A MINIMUM OF THREE(3) LAG SCREWS PER JAMB. LAG SCREWS AT TOP AND BOTTOM
OF JAMB SHALL BE PLACED A MAXIMUM OF 6" FROM THE END OF HE JAMB.
3. LOAD PER JAMB CALCULATED BY TAKING DESIGN LOAD (PSF) TIMES DOOR WIDTH (FT) DIVIDED BY 2.
EXAMPLE; DESIGN LOAD =30psf
DOOR WIDTH =16ft
LOAD PER JAMB = 30psf x 16(V2 = 2401b/ft
4. CHART IS BASED ON 6'-6" MINIMUM AND 24'-0" MAXIMUM DOOR HEIGHT.
5. DOOR JAMB TO BE 2x4 OR LARGER N0.2 GRADE SPF LUMBER OR BETTER MOUNTED TO SUPPORT STRUCTURE.
IF MOUNTING R DRYWALL, INCREASE TACHIEVENER LENGTH TO REQUIRED
PENETRATION.MUM
S ALLP BE THE SOLE RE ONSIBT RESPONSIBILITY OF
6.D DESIGN OF THE SUPPORT PPORT STRUCTURE OF THE BUILDING DESGNER\\\\51����+I//I//
7. MINIMUM EDGE DISTANCE SHALL BE AND SHALL BE DESIGNED FOR THE 10, CALCULATED LOAD LISTED IN ABOVE TABLE AS MINIMUM FAS ENER SPACING SALLBE 12^,PER
NOTE 3
AND ALL HOLES SHALL BE PRE -DRILLED TO PREVENT SPLTTING.
\\\\\'O�N`CE
�•
8. CALCULATIONS CONFORM TO ANSVAF&PA NDS-2005.
No. 51737 •�
9. LAG SCREWS SHALL CONFORM TO ANSI/ ASME STANDARD B18.2.1.
�'
STATE
ZZ
^._(�
Approved lf�M
John E. Sates, P.E. v�l/tZ
�,C . ;� ,%Q7�
ij�Fss �ORID a6��\��
3121 Fatrgate Dr.
Carrollton, TX 75007
FLPES1737 TXPE56308/F2203
Revision P10
SCHEDULES
3/8" FJ A307 HEADED OR HOOKED ANCHOR BOLTS IN NORMAL WEIGHT CONCRETE
MAXIMUM SPACING OF ANCHOR BOLTS PER JAMB (IN)
LOAD PER
JAMB LB N0TE8
2000 PSI
CONCRETE
2500 PSI
CONCRETE
3000 PSI
CONCRETE
100
24
24
24
120
24
24
24
140
24
24
24
160
24
24
24
180
24
24
24
200
1 24
24
24
220
24
24
24
240
24
24
24
260
24
24
24
280
24
24
24
300
24
24
24
820
24
24
24
340
24
24
24
360
23
24
24
380
22
24
24
400
20
24
24
420
19
24
24
440
19
23
24
460
18
22
24
480
17
21
24
500
16
20
1 24
520
16
20
24
540
15
19
23
560
14
18
22
580
14
18
21
600
13
17
20
620
13
16
20
640
13
16
19
660
12
15
19
680
12
15
18
700
11
14
17
720
11
14
17
740
11
14
16
760
11
13
i6
780
10
13
16
800
10
13
15
\\`` gtA E.
I Isc �77��i
o. 51737 _
'a,
10 ; STATE OF zr
7 Al
1. BASED ON 3/8"O A307 HEADED OR HOOKED (1.69" MIN. HOOK LENGTH) ANCHOR BOLTS WITH A2" O.D. W'ASH �11„\`\
WITH A MINIMUM EMBEDMENT DEPTH OF 3" AND A MINIMUM EDGE DISTANCE OF 3`.
2. PROVIDE QUANTITY OF ANCHOR BOLTS AS REQUIRED TO MAINTAIN MAXIMUM SPACING AS SHOWN IN
TABLE WITH A MINIMUM OF THREE (3) ANCHOR BOLTS PER JAMB. ANCHOR BOLTS AT TOP AND BOTTOM
OF JAMB SHALL BE PLACED A MAXIMUM OF 6" FROM THE END OF THE JAMB.
3. LOAD PER JAMB CALCULATED BYTAKING DESIGN LOAD (PSF) TIMES DOOR WIDTH (FT) DIVIDED BY 2.
EXAMPLE: DESIGN LOAD =30psf
DOOR WIDTH =16ft
LOAD PER JAMB = 30psf x i 6f /2 = 2401b/ft
4. CHART IS BASED ON 6'-6" MINIMUM AND 24'-0" MAXIMUM DOOR HEIGHT.
5. DOOR JAMB TO BE 2x6 NO.2 GRADE SPF LUMBER OR BETTER MOUNTED TO SUPPORT STRUCTURE.
IF MOUNTING OVER DRYWALL, INCREASE FASTNER LENGTH TO ACHIEVE MINIMUM REQUIRED PENETRATION.
6. DESIGN OF THE SUPPORT STRUCTURE SHALL BE THE SOLE RESPONSIBILITY OF THE BUILDING DESIGNER
AND SHALL BE DESIGNED FOR THE JAMB LOAD LISTED IN ABOVE TABLE AS CALCULATED PER NOTE 3.
7. CALCULATIONS CONFORM TO ANSVAF&PA NDS-2005 AND ACI 318-05, APPENDIX D.
John E. Scates, P.E.
3121 Fairgate Dr.
Carrol lton, TX 75007
FL PE 51737 TX PE 56308/F2203
Revision P10
SCHEDULE2
16d COMMON WIRE NAILS AND 16d THREADED HARDENED -STEEL NAILS
MAXIMUM NAIL SPACING PER
JAMB IN
MAIN SUPPORT MEMBER SPECIES
SYP
SPECIFIC
GRAVITY -0.55
DOUGLAS FIR
SPECIFIC
GRAVITY -0.46
SPF
SPECIFIC
GRAVITY -0.42
LOAD PER
JAMB (LB/Fr)nrotaa
100
24
24
19
120
22
20
16
140
19
17
14
160
16
15
12
180
14
13
10
200
13
12
9
220
12
11
8
240
11
10
8
260
10
9
7
280
9
8
7
300
8
8
6
320
8
7
6
340
7
7
n/a
360
7
6
n/a
380
7
6
n/a
400
6
6
n/a
420
6
n1a
n/a
440
6
Wa
n/a
460
Wa
n1a
n/a
480
n1a
Wa
n1a
Boo
Wa
n/a
n1a
520
Wa
n/a
n/a
540
n/a
n1a
n1a
560
n1a
n1a
Wa
580
n1a
n/a
Wa
600
n1a
n/a
n/a
620
n1a
n/a
n/a
640
n/a
n/a
n/a
660
n1a I
n/a
n/a
680
n1a
n/a
n/a
700
n1a
n/a
n/a
720
n1a
n/a
n/a.
740
n1a
n/a
n1a
760
We
n/a
n1a.
780
We
n/a
Wa
800
n1a
Iva
Wa
GEWs� TF� x
i
a
No.51737
STgTE OF ; Q
O
ONR ID
1. BASED ON 16d COMMON WIRE NAILS (0.16Z6-1/21 OR 16d THREADED HARDENED -STEEL NAILS (0.148'4-1/2'
WITH A MINIMUM PENETRATION OF 2" INTO SIDE GRAIN OF MAIN MEMBER.
2. NAILS SHALL BE PROVIDED IN PAIRS AT A MAXIMUM SPACING AS SHOWN IN TABLE WITH A
MINIMUM OF THREE (3) PAIRS OF NAILS PER JAMB. NAILS AT TOP AND BOTTOM
OF JAMB SHALL BE PLACED A MAXIMUM OF 6" FROM THE END OF THE JAMB.
3. LOAD PER JAMB CALCULATED BY TAKING DESIGN LOAD (PSF) TIMES DOOR WIDTH (FT) DIVIDED BY 2.
EXAMPLE: DESIGN LOAD=30psf
DOOR WIDTH =16ft
LOAD PER JAMB = 30psf x 16f112 = 2401b/ft
4. CHART IS BASED ON 6'-6" MINIMUM AND 24'-0" MAXIMUM DOOR HEIGHT.
5. DOOR JAMB TO BE 2x4 OR LARGER NO.2 GRADE SPF LUMBER OR BETTER MOUNTED TO SUPPORT STRUCTURE.
IF MOUNTING OVER DRYWALL, INCREASE FASTNER LENGTH TO ACHIEVE MINIMUM REQUIRED PENETRATION.
6. DESIGN OF THE SUPPORT STRUCTURE SHALL BE THE SOLE RESPONSIBILITY OF THE BUILDING DESIGNER
AND SHALL BE DESIGNED FOR THE JAMB LOAD LISTED IN ABOVE TABLE AS CALCULATED PER NOTE S.
7. EDGE DISTANCES, END DISTANCES AND SPACINGS SHALL BE SUFFICIENT TO PREVENT SPLITTING OF THE WOOD.
B. CALCULATIONS CONFORM TO ANSI/AF&PA NDS-2005.
Aooroved
John E.Scates,P.E, tr
3121 Falrgate Dr.
Carrollton, TX 75007
FL PE 51737 TX PE 56308/F2203
Revision P10
SCHEDULE4
3/8"0 SIMPSON TITEN HD SCREW ANCHORS
MAXIMUM SPACING OF ANCHORS PER JAMB (IN)
LOAD PER
JAMB LB/ NOTE4
2000 PSI
CONCRETEN rE1
4000 PSI
CONCRETENOrs1
2000 PSI GROUT
FILLED CMUNOTE2
100
24
24
24
120
24
24
24
140
24
24
24
ISO
24
24
24
180
24
24
24
200
24
24
24
220
24
24
24
240
24
1 24
24
260
24
24
22
280
24
24
20
Soo
24
24
19
320
24
24
18
340
24
24
16
360
24
24
16
380
24
24
15
400
24
24
14
420
24
24
13
440
24
24
13
460
24
24
12
480
23
23
12
500
22
22
11
520
21
21
11
540
20
20
10
560
19
19
10
680
19
19
9
600
18
18
9
620
17
17
9
640
17
17
9
660
16
16
8
680
16
16
8
700
15
15
8
720
15
15
8
740
15
15
7
760
14
14
7
780
1
14
7
Soo
134
13
7
Esc E AT�s /01
No. W737
STATE OF
i�j�A�••FCORIOP• G\=�N�
1. BASED ON 3/8"0 SIMPSON TITEN HD SCREW ANCHOR WITH A 13W O.D. WASHER INTO NORMAL WEIGHT CONCRETE
WITH A MINIMUM EMBEDMENT DEPTH OF 2.3W AND A MINIMUM EDGE DISTANCE OF 2-W4'.
2. BASED ON 3/6"0 SIMPSON TITEN HD SCREW ANCHOR WITH A 13/4" O.D. WASHER INTO GROUT FILLED CMU WITH A
MINIMUM EMBEDMENT DEPTH OF 23/4', A MINIMUM EDGE DISTANCE OF 4, AND A MINIMUM END DISTANCE OF 4'.
CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM 090 AND GROUT SHALL CONFORM TO ASTM C478.
3. PROVIDE QUANTITY OF SCREW ANCHORS AS REQUIRED TO MAINTAIN MAXIMUM SPACING AS SHOWN IN
TABLE WITH A MINIMUM OF THREE (3) SCREW ANCHORS PER JAMB. SCREW ANCHORS ATTOP AND BOTTOM
OF JAMB SHALL BE PLACED A MAXIMUM OF 6' FROM THE END OF THE JAMB.
4. LOAD PER JAMB CALCULATED BY TAKING DESIGN LOAD (PSF)TIMES DOOR WIDTH (FT) DIVIDED BY 2.
EXAMPLE: DESIGN LOAD =39psf
DOOR WIDTH =1 Oft
LOAD PER JAMB = 30psf x 16f /2 = 2401h/it
5. CHART IS BASED ON T-6" MINIMUM AND 24'-O" MAXIMUM DOOR HEIGHT.
6. DOOR JAMB TO BE 2x6 NO.2 GRADE SPF LUMBER OR BETTER MOUNTED TO SUPPORT STRUCTURE.
IF MOUNTING OVER DRYWALL, INCREASE FASTNER LENGTH TO ACHIEVE MINIMUM REQUIRED PENETRATION.
7. DESIGN OF THE SUPPORT STRUCTURESHALL BE THE SOLE RESPONSIBILITY OF THE BUILDING DESIGNER
AND SHALL BE DESIGNED FOR THE JAMB LOAD LISTED IN ABOVE TABLE AS CALCULATED PER NOTE 4.
8. CALCULATIONS CONFORM TO ANSMF&PA NDS-2005.
9. SCREW ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
John E. Scates, P.E. Ll flv
3121 Fairgate Dr.
Carrollton, TX 75007
FL PE 51737 TX PE 56308/F2203
Revision P10
Wagnc®
paiton
3395 ADDISON DRIVE
*, * OF uZ
q :• STA'�
��0 `• °LOR��p �
filON"
]I11 FMItW1E pR.
CMfltl110N, 5TSU07
PE R PE 31TT/ Ti{ 6]09/iLl]
6'
6'
MINIMLM fO0�pP9 CONCRETE
RE�MAXIMUM DESIGN LOAD
CAPACNTf OF 2065 LOS.
I-=
4'J
1-1/2'J 1-1/2'-I
HD SCREW
4) 3/6' SIMPSON TIEN HD SCREW
4) 3/B' OIA. LAG SCREWS
WASIIER AND
ANCHOR NTH A 1-1/4' WA%IER AND
WITH 1-1/4' 0.0. WA TI
]EPTH OF
A MINIMUM EMBEDMENT DEPTH OF
LAO SCREWS SHALL NAVE A
MOE
2-3/4' AND A MINIMUM EDGE
MINIMUM PFNETNARON OF
DISTANCE OF 4'.
1-9/] r NTO ME MAW
SUPPORT MEMBER.
091 M 20M MWiT FILED CAN
N. MAXIMUM DESIGN Lon
µpp0 SLPPD SUPPORT 3 111RE
ME MAXIMUM DAD
DATE
NAME
CAPACITY OF 2400 LBS
CAPACITY OF 2430 LBS.
D A
5 24 07
1
G IRT
CHECHED
5/24/07
1
MRB
JAMB
CONNECTION SUPPLEMENT
DRAN1N0 PART NO.
REV.
32462O
P1O
DocuSign Envelope ID: F67AF1B8-18BC-4E74E1)40-E5F1585688B1
Jax Apex Technology, Inc.
FBPE CA NO.7547
4745 Sutton Park Court, Suite 402
Jacksonville, FL 32224
Evaluation reports are the opinion of the engineer who prepared the report, based on the findings, and in no
way constitute or imply approval by a local building authority. The engineer, in review of the data
submitted, kinds that, in his opinion, the product, material, system, or method of construction specifically
identified in this report conforms with or is a suitable alternate to that specified in the Florida Building
Code, SUBJECT TO THE LIMITATIONS IN THIS REPORT
Jeffrey P. Arneson, an employee of Jax Apex Technology, Inc. (Apex Technology), is the
authorized evaluating engineer of this report. Apex Technology is the prime professional, as defined
in Florida Rule 61 G-30.002, authorized to sell the engineering services performed by Jeffrey P.
Arneson, and is in no way acting, nor attempting to act, as an approved evaluation entity. Neither
Jeffrey P. Arneson, nor any other employee of Apex Technology, has performed calculations or
testing for the products listed in this report. This evaluation is based solely upon the review, under
the direct supervision of Jeffrey P. Arneson, of testing and/or calculations submitted by the
manufacturer.
The capacities listed in this report are based on the limiting capacities as determined from the
substantiating data. We reviewed the substantiating data to a degree that allowed us to determine
whether or not the work performed is consistent with the intended use of the product, and that the
methods used are in compliance with, or meet the intent of, the Florida Building Code. All test
reports were prepared by an approved testing laboratory.
INAf-
CATEGORY: Doors and Windows
6911W, litiill4o7;ffi/I
Wayne Dalton Corporation
3395 Addison Drive
Pensacola, FL 32514
1. CERTIFICATION OF INDEPENDENCE
Jeffrey P. Arneson, the Florida engineer who prepared this report, and Apex Technology
have no financial interest in the manufacturing, sales, or distribution of the products
included in this report. Jeffrey P. Arneson and Apex Technology comply with all criteria as
stated in Florida Administrative Code Chapter 9N-3.009.
2. PRODUCT NAME
Model 8700 garage doors.
Page 1 of Wayne -Dalton
DocuSign Envelope ID: F67AF1B8.18BC-4E74-8040-ESF1585688B1
3. SCOPE OF EVALUATION
Structural Transverse Wind Loads
4. USES
Model 8700 garage doors are used for residential applications with specified allowable
design pressures.
5. DESCRIPTION
General
Model 8700 garage doors listed in Table 1 of this report are sectional overhead doors and
are constructed of minimum .052" vinyl facer and a minimum .032" vinyl backer. The doors
have a polyurethane insulation sandwiched between the interior and exterior skins and 20
gage end caps. Each section shall have a 1-1/4" x 1-112" x 22 ga continuous internal rails at
the top and bottom of each section. The ends of each rail in the top of each section shall be
reinforced with a 15 gage reinforcing bracket. The sections shall have 20 gage backup
plates at all intermediate hinge locations. The sections are 1-5/8" thick with tongue and
groove joints and shall have a maximum section height of 21 ".
Door Tracks
All door assemblies listed in this report have both vertical and horizontal tracks ranging
from a minimum 16 gage to minimum 15 gage, 33 ksi steel and finished with an ASTM
A525 G-40 galvanized coating. The vertical tracks are attached to the supporting structure
with jamb brackets as specified on the most recent manufacturer's installation
instructions/drawings.
Glazed Sections
Unless noted otherwise, the option code assemblies listed in Table 1 of this report are
available with a minimum of 0.125-inch thick standard SSB glass windows that are installed
in frames and inserted in the top or intermediate section of the door. The glazing is not
impact resistant and does not meet the requirements for wind-borne debris regions. Refer
to the most recent manufacturer's installation instructions/drawings for glass size
limitations.
Wind Load Bracing
All option code assemblies listed in Table 1 of this report are braced on the inside of the
doors with three inch horizontal spanning U-bars. Each U-bar is made of either 18-gage or
20-gage ASTM A653-00 steel with a minimum yield strength of 80 ksi and are finished with
an ASTM A525 minimum G-40 galvanized coating. The gage and quantity of U-bar braces
varies depending on the amount of windload resistance required and the height of the door.
In addition to three-inch horizontal spanning U-bars, some of the option code assemblies
listed in Table 1 of this report are braced with vertical aluminum posts made up of 0.125-
inch thick 6063-T6 aluminum alloy. The post is a telescoping post assembly. The outer
member outside diameter is 1.75" wide x 4.00" long. The inner member outside diameter is
1.47" wide x 3.72" long.
Page 2 of 4 Wayne -Dalton
DocuSign Envelope ID: F67AF1B8-18BC-4E74.8D40-E5F1585688B1
6. INSTALLATION
All option code assemblies listed in this report are to be installed in accordance with the
most recent manufacturer's published installation instructions/drawings and this report.
The most recent manufacturer's installation instructions/drawings shall be strictly adhered
to and a copy of these instructions/drawings shall be available at all times on the job site
during installation.
Design wind load pressures for garage doors shall be determined in accordance with
section 1609 of the 2010 Florida Building Code and shall not exceed the allowable
transverse wind loads shown in the following tables:
Table 1: Model 8700 Garage Door Allowable Transverse Wind Loads
Windload
Specification
Option Code
Maximum Size
Positive
Design
PSF
Negative
Design
PSF
Reinforcement(Yes/No)
Glazing
Available
Width
Height
1000
9'-0"
14'-0"
22.90
26.30
3", 20 gage U-bars
Yes
1001
9'-0"
14'-0"
31.20
35.80
3", 20 gage U-bars
Yes
1002
9'-0"
14'-0"
41.60
46.30
3", 20 gage U-bars
Yes
1020
16-0"
14'-0"
23.00
25.00
3", 18 gage U-bars
Yes
1021
W-0"
14'-0"
30.00
33.50
3", 18 gage U-bars
No
1022
16-0"
8'-0.
43.40
48.40
3", 18 gage U-bars+ (2) Aluminum Posts
Yes
1040
18'-0"
12'-0"
18.50
20.70
3", 18 gage U-bars
Yes
1041
18'-0"
12'-0"
25.90
28.80
3", 18 gage U-bars
No
1042
18'-0"
8'-0"
39.20
43.70
3", 18 gage U-bars + (2) Aluminum Posts
Yes
tK4111-l-YalaITAiILl107_YlC1
For Premium garage doors, Test Report Number ETC-07-976-18894.0 in accordance with
ANSI/DASMA 108-2002 for transverse wind load by ETC Laboratories, 297 Buell Road,
Rochester, N.Y.
Installation drawings and installation instructions prepared by Wayne -Dalton Corporation
for each option code assembly listed in Table 1 of this report.
Z149=17#1ki101=N
Florida Building Code 2010 Edition
Section 1609 Wind Loads
Section 1715.5.3.1 ANSI/DASMA 108
10. REPORT SUMMARY
Upon review of the data submitted by Wayne -Dalton, it is my opinion that the models as
described in this report conform with or are a suitable alternative to the code standards and
sections in the Florida Building Code 2010 edition listed in section 9 of this report.
Page 3 of 4 Wayne -Dalton
DocuSign Envelope ID: F67AF1 B8-18BC-4E74-8D40-E5F158568881
11. LIMITATIONS
Any reference in this report to the manufacturer's "most recent" information is a direct
reference to the most recent information submitted by Wayne -Dalton to the Florida Building
Commission as part of their Florida Product Approval application for the option code
assemblies listed in Table 1 of this report.
This evaluation report and the most recent installation instructions, when required by the
building official, shall be submitted at the time of permit application.
The design of the supporting structural elements shall be the responsibility of the design
professional for the building structure and in accordance with current building codes for the
loads listed in Table 1 of this report.
The doors shall not be located in areas where the transverse wind loads exceed the
allowable loads shown in Table 1 of this report.
The option code assemblies with glazed panel inserts do not meet the impact requirements
for the wind-borne debris regions.
The garage door assemblies listed in Table 1 of this report are not approved for use in the
"High Velocity Hurricane Zone" as defined in the Florida Building Code.
12. IDENTIFICATION
Each Model series covered by this report shall be labeled with the manufacturer's name
and/or trademark for field identification.
no. E85G6
Jax Apex Tecf&logy, Inc.
Jeffrey P. Arneson, P.E.
P.E. No. 58544
February 20, 2012
Page 4 of 4 Wayne -Dalton