Loading...
HomeMy WebLinkAboutMISC EMAILPAUL WELCH INC. Mechanical * Electrical * Civil Engineering 1984 S.W. Biltmore St. Suite#114 Port Saint Lucie, FL 34984 Phone (772) 785 - 9888 Email pwelchinc@aol.com January 22, 2015 Re: Door Replacement 3700 Ave. F Fort Pierce, FL 34947 To Whom It May Concern: SCANNED St. Lucey County Our office has calculated the required design pressure in accordance with ASCE 7-10 for a replacement of the roll up door at the above referenced address. Wind speed: V,d,: 160 mph, V.d: 124 mph Exposure: B Enclosure Type: Enclosed Door Size: 14' Wide X 15.5' High (same size as doors removed). Quantity of Doors: 1 Location: Zone 3 (South Side of Building More than 6' from corners of the of the building) Required Design Pressure (Zone 4): +24.9/ -27.3 PSF Doors to be installed shall be equal to, or exceed the required design pressures as listed above. All installations shall be in accordance with FBC 2010 and manufacturer's installation instructions. Proposed Doors: Roll Up Garage Door by Janus International Corporation Series 3100 FL#12765.4 (+38.8 / - 42.2 PSF). Thank you for your attention to this matter. Subm tted by: PA WELCH INC. rk Paul elch, P.E. 04P Reg. No 29945 Attached: Product Approval Sheets for FL#12765.4