Our office has calculated the required design pressure in accordance with ASCE 7-10 for
a replacement of the roll up door at the above referenced address.
Wind speed: V,d,: 160 mph, V.d: 124 mph
Exposure: B
Enclosure Type: Enclosed
Door Size: 14' Wide X 15.5' High (same size as doors removed).
Quantity of Doors: 1
Location: Zone 3 (South Side of Building More than 6' from corners of the
of the building)
Required Design Pressure (Zone 4): +24.9/ -27.3 PSF
Doors to be installed shall be equal to, or exceed the required design pressures as listed
above. All installations shall be in accordance with FBC 2010 and manufacturer's
installation instructions.
Proposed Doors: Roll Up Garage Door by Janus International Corporation
Series 3100 FL#12765.4 (+38.8 / - 42.2 PSF).
Thank you for your attention to this matter.
Subm tted by:
PA WELCH INC. rk
Paul elch, P.E. 04P
Reg. No 29945
Attached: Product Approval Sheets for FL#12765.4