HomeMy WebLinkAboutHVAC LOAD ANALYSISMosquito Control HVAC Load Analysis for St. Lucie County 3150 Will Fee Road Fort Pierce, Florida SCANNEL, By St. Lucie Count, COMMERCIAL HVAC LOADS SVOUO',*, ems° ENS,'r.•�9�re * No 60982 r o Prepared By. Eric J. Svoboda. PE Fort Pierce Engineering, Inc 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Monday, December 08, 2014 u - -- - Chvac - Ftill Commercial HVAC.Loads Calculation,Program Buildigg Summary Loads Building peaks in August at 4pm. Elite Software Development, Inc. Mosquito Control Page 2_ Net Roof 2,956 8,779 19.95 0 11.257 11.257 Wall 2,110 6,615 15.03 0 4,645 4,645 Glass 270 7,395 1680 0 18.645 18.645 Floor Slab 238 4,869 11 06 0 0 0 Skin Loads 27,659 62.84 0 34.547 34.547 Lighting 5,912 0 0.00 0 20,173 20,173 Equipment 2.956 0 0,00 0 10.086 10.086 People 19 0 0.00 3,781 4.727 8.508 Partition 350 333 0.76 0 333 333 Cool. Pret. 0 0 0.00 0 0 0 Heal. Pret. 0 0 0.00 0 0 0 Cool. Vent. 450 0 0.00 16,176 9,891 26,067 Heal. Vent. 450 16,024 36.40 0 0 0 Cool.lnfil. 0 0 0.00 0 0 0 Heat.lnfil. 0 0 0.00 0 0 0 Draw-Thru Fan 0 0 0.00 0 782 782 Blow-Thru Fan 0 0 0.00 0 0 0 Reserve Cap. 0 0 0.00 0 0 0 Reheat Cap. 0 0 0.00 0 0 0 Supply Duct 0 0 0.00 0 0 0 Return Duct 0 0 0,00 0 0 0 Misc. Supply 0 0 0.00 0 0 0 Misc. Return 0 0 000 0 0 0 %Net Gain 11 20 4 62 18 55 000 34 38 20 07 10 04 847 0 33 000 0 00 2594 0 00 0 00 000 0 78 0 00 0 00 000 0 00 000 000 0 00 Building Totals 44.015 100.00 19,957 80.538 100,496 10000 e �0 iqr Sen, :,� >,�,�/o�ot, a IM ,r, Lat w�� ° ,Sen �; ,, ,_ Met: 0 LeNet .Mhy J i d i f.•%M tYl �1 l.pfl'4 ✓I,Yl.�� Summa�' k ="' ':' Loss-t�L-oss Gain '4 Gairi Gain Gain Ventilation 16,024 3640 16,176 9.891 26.067 25 04 Infiltration 0 000 0 0 0 000 Pretreated Air 0 0.00 0 0 0 000 Zone Loads 27,991 63.60 3.781 69,865 73,646 73 28 Plenum Loads 0 0.00 0 0 0 000 Fan & Duct Loads 0 0.00 0 782 782 0 78 Building Totals 44,015 100.00 19,957 80,538 100,496 100 00 'Check Figures ---- i Total Building Supply Air (based on a 20° TD): 3,269 CFM Total Building Vent Air (13.77% of Supply): 450 CFM Total Conditioned Air Space: 2.956 Sq.ft Supply Air Per Unit Area: 1.1057 CFM/Sq.ft Area Per Cooling Capacity: 353.0 Sq.ft/Ton Cooling Capacity Per Area 0.0028 Tons/Sq.fl Heating Capacity Per Area: 14.89 Btuh/Sq.ft Total Heating Required With Outside Air 44,015 Btuh Total Cooling Required With Outside Air: 8,37 Tons Z t \Mosquito Control Heat Load.CHV Monday. December 08. 2014. 04.04 PM C6vac - FuIPCommercial HVAC,Loads Calculation Program j Elite Software Development, Inc. Mosquito Control Nu1HF --- — ---- -- Page.3 [Air Handler #1 - AHU_1_ - Summary_ Loads Zn �. �No Description Zone Peak yTlme dr Area Htg Loss Sen Gain Laf Gain People x � Htg CFM C,Ig=CFM ;S Exh Volume# `CFM/Sgft1°-'CFM/Sgft WE-xh` Htg.O.A. Req_CFM Acf:CFMActCFM CIg.O.A. Req.CFM 1 Office 10 324 3.565 6,470 432 Direct Direct 3pm August 2 165 297 0 45 45 2,592 0.51 0.92 0 45 30 2 Office 11 644 7,891 23,879 859 Direct Direct 4pm August 4 366 1,097 0 89 89 5,152 0 57 1.70 0 100 111 3 Office 9 120 356 1,907 160 Direct Direct 3pm August 1 17 88 0 17 tr 960 0.14 0.73 0 5 9 Zone Peak Totals: 1.088 11,813 32,256 1,451 Total Zones: 3 7 547 1,482 0 150 150 Unique Zones: 3 8,704 0.50 1 36 0 150 150 • Z:\. \Mosquito Control Heal load.CHV Monday, December 08. 2014 04 04 PM Chvac - Full, ommercial HVAC Loads•Calculation Program Elite Software Development, Inc. Mosquito Control Page 4 Air Handler #1 - A_HU 1 - Total Load Summary Air Handler Description: AHU 1 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0 14 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.96 --- This system occurs 1 time(s) in the building -- Air System Peak Time 4pm in August Outdoor Conditions: Clg: 95' DB, 78' WB. 118.35 grains, Hlg! 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75' D8 Summer. Ventilation controls outside air, ----- Winter. Ventilation controls outside air Zone Space sensible loss: 11,813 Bluh Infiltration sensible loss: 0 Bluh 0 CFM Outside Air sensible loss. 5,341 Btuh 150 CFM Supply Duct sensible loss. 0 Btuh Return Duct sensible loss: 0 Btuh Keturn Plenum sensible loss:. 0 Btuh Total System sensible loss: Heating Supply Air 11,813 / (999 X 1.08 X 20) = 547 CFM Winter Vent Outside Air (27.4% of supply) = 150 CFM Zone space sensible gain: 32.210 Bluh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 355 Bluh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: Cooling Supply Air: 32,565 / (.999 X 1.1 X 20) = 1,482 CFM Summer Vent Outside Air (10.1% of supply) = 150 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain 0 Bluh Outside air sensible gain 3.297 Btuh 150 CFM Blow-thru fan sensible gain. 0 Bluh Total sensible gain on return side of coil. Total sensible gain on au handling system: Zone space latent gain: 1.451 Btuh Infiltration latent gain: 0 Bluh Outside air latent gain 5,392 Bluh Total latent gain on air handling system: Total system sensible and latent gain: Total Air Handler Supply Air (based on a 20° TD): 1.482 CFM Total Air Handler Vent. Air (10.12% of Supply). 150 CFM Total Conditioned Air Space: 1,088 Sq.ft Supply Air Per Unit Area: 1.3617 CFM/Sq.ft Area Per Cooling Capacity: 305.7 Sq.ft/Ton Cooling Capacity Per Area. 00033 Tons/Sq.ft Heating Capacity Per Area. 15.77 Btuh/Sq.ft Total Heating Required With Outside Au. 17,154 Bluh Total Cooling Required With Outside Air 3 56 Tons 17,154 Btuh 32,565 Btuh 3,297 Btuh 35.862 Btuh 6,843 Btuh 42.704 Btuh Z 1 \Mosquito Control Heat Load CHV Monday, December 08, 2014 04 04 PM Chvac - Fulh Commercial HVAC�•Loads Calculation Program' '., I. Elite Software Development, Inc. Mosquito Control - Page 6 Air Handler #2 - AHU 2 - Total Load Summary Au Handler Description. AHU 2 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.09 HP Fan Input: 0% motor and fan efficiency with 0 in water across the fan Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building -- Air System Peak Time: 3pm in August. ,Outdoor Conditions: Clg: 95° DB, 78' WB, 117.61 grains, Htg: 42' DB Indoor Conditions Clg: 75' DB, 50% RH. Htg 75' DB Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 9am is different 'from the total system peak time, hence the air system CFM was computed using a zone sensible load of 21.604 Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air Zone Space sensible loss: 9,321 Btuh Infiltration sensible loss. 0 Btuh Outside Air sensible loss: 5.341 Btuh Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: Healing Supply Air 9,321 / (.999 X 1.08 X 20) _ Winter Vent Outside Air (34.7% of supply) _ Zone space sensible gain: 20,850 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 238 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil Cooling Supply Air: 21.842 / (.999 X 1 1 X 20) _ Summer Vent Outside Air (15.1 % of supply) _ Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Bluth Outside air sensible gain: 3.297 Btuh Blow-thru fan sensible gain: 0 Bluth Total sensible gain on return side of coil: Total sensible gain on air handling system. 0 CFM 150 CFM 432 CFM 150 CFM 994 CFM 150 CFM 150 CFM Zone space latent gain: 1,273 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 5,392 Btuh Total latent gain on air handling system: Total system sensible and latent gain: Check Figures Total Air Handler Supply Air (based on a 20° TD): 994 Total Air Handler Vent. Air (15.10% of Supply): 150 Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area. Total Heating Required With Outside Air. Total Cooling Required With Outside Au'. CFM CFM 955 Sq.ft 1.0405 CFM/Sq.ft 3691 Sq.ft/Ton 0.0027 Tons/Sq.ft 15.35 Bluh/Sq,ft 14,662 Btuh 2.59 Tons 14.662 Btuh 21,088 Btuh 3,297 Btuh 24,385 Btuh 6.665 Btuh 31,050 Stuh Z 1 1Mosquito Control Heat Load.CHV Monday. December 08, 2014 04 04 PM Chvac - Full' Commercial HVACLoads,Calculation Program i - Air Handler #3 - AHU 3 -_ Summary Loads Zn Qescn,ptlon. 1-. Area A tg Coss • Sen Gail 'No Zone Peak Time People Htg,CFM CIg:CFh 11 Office 117 471 1,983 3pm August 1 22 90 936 019 0.77 12 Office 6 160 570 2,638 3pm August 1 26 120 1.280 0.17 0:75 13 Office 7 192 1,513 3.495 4pm August 1 70 159 I 1,536 0.37 0.83 14 Electrical Room 120 1,755 2,354 7pm August 0 81 107 960 0.68 0.89 15 Men 48 453 881 5pm August 0 21 40 384 0.44 0,83 16 Women 48 453 881 5pm August 0 21 40 384 0.44 0,83 17 Office 8 104 1.273 3,248 4pm August 1 59 148 832 0.57 1.42 18 Hall 124 368 1,971 3pm August 1 17 90 992 0.14 0.72 Zone Peak Totals: 913 6,858 17,450 Total Zones: 8 5 318 793 Unique Zones: 8 7.304 0.35 0.87 EliteiSoftware Development, Inc.: Mosquito Control _,__Page 7 Htg 0. A. Clg.O.A. Lat Gain S.Exh Req.CFM Req.CFM )A Exh ACt.CFM ._ Act,CFM 156 Direct Direct 0 19 19 0 10 17 213 Direct Direct 0 26 26 0 12 23 256 Direct Direct 0 32 32 0 33 30 0 Direct Direct 0 20 20 0 38 20 64 Direct Direct 0 8 8 0 10 6 64 Direct Direct 0 8 8 0 10 8 139 Direct Direct 0 17 17 0 28 28 165 Direct Direct 0 20 20 0 8 17 1.057 0 150 150 0 150 150 Z'1 Wosquilo Control Heat Load CHV Monday. December 08. 2014 04 04 PM rChvac -FUII Commercial HVAC-Loads Calculation Program Elite Software Development, Inc. Mosquito Control Page 8 Air Handler_#3 - AH_U 3 - Total Load_ Summary Air Handler Description: AHU 3 Constant Volume - Proportion Supply Air Fan Draw-Thru with program estimated horsepower of 0.07 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio 0.94 --- This system occurs 1 time(s) In the building --- Air System Peak Time: 4pm in August. -Outdoor Conditions: Clg: 95' DB. 78" WB, 118.35 grains. Htg: 42' DB Indoor Conditions: Clg 75' DB, 50% RH. Htg75' DB _ Summer Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Zone Space sensible loss: 6,858 Bluth .Infiltration sensible loss: 0 Bluth 0 CFM Outside Air sensible loss. 5,341 Btuh 150 CFM Supply Duct sensible loss: 0 Bluth Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: Heating Supply Air: 6,858 / (.999 X 1.08 X 20) _ Winter Vent Outside Air (47.2% of supply) = Zone space sensible gain: 17,247 Bluth Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 190 Btuh Supply duct sensible gain 0 Btuh Reserve sensible gain 0 Btuh Total sensible gain on supply side of coil: Cooling Supply Air: 17,437 / (.999 X 1.1 X 20) _ Summer Vent Outside Air (18.9% of supply) = Return duct sensible gain: 0 Bluth Return plenum sensible gain. 0 Btuh Outside air sensible gain: 3,297 Stuh Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: Total sensible gain on air handling system: Zone space latent gain: 1,057 Btuh Infiltration latent gain. 0 Bluth Outside air latent gain: 5.392 Btuh Total latent gain on air handling system: Total system sensible and latent gain: 6eck;Figures Total Air Handler Supply Air (based on a 20 TD) Total Air Handler Vent. Air (18,91% of Supply): Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area: Total Heating Required With Outside Air: Total Cooling Required With Outside Air 318 CFM 150 CFM 793 CFM 150 CFM 150 CFM 793 CFM 150 CFM 913 Sq.ft 0.8689 CFM/Sq.ft 403.0 Sq.fl/Ton 0.0025 Tons/Sq.ft 13.36 Bluh/Sq.ft 12,199 Btuh 2.27 Tons 12.199 Btuh 17.437 Btuh 3,297 Bluth 20,734 Btuh 6,449 Stun 27,183 Btuh Z \ \Mosquito Control Heat Load CHV Monday, December 08, 2014 04 04 PM