STRUCTURAL STEEL OBSE__ _ ATIONS REPORT
Report Number: HB161005.0074
Service Date: 09/06/16
Report Date: 09/09/16
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Gherry Street
Chattanooga, TN 37402
lrerracon
607 NW Commodity Cv
Port St Lucie, FL 34986-2250
Family Dollar
10M 1 Lennard Road
Port St. Lucie, FL 34952
SCANNED
BY
St. Lucie Countv
Project Number. ,HB161005
Services Requested By: Garrett @ Hutton Construction
Connection Type/Description: Structural steel metal building bolting
Visual Observation Elevation(s)/Location(s): Roof rake parapet walls framing bolting, roof purlins framing & bolting
Type of Observation: Structural steel
Referenced Documents: Official construction documents, Mesco Building Solutions, metal building manufacturer submittal
drawings, page E3 of 15, E4 of 15.
Observation Results:
Based on our visual observations, the connections observed at the referenced locations appeared to be the proper size, type, in
the proper location and placed in general accordance with the identified referenced documents.
Exceptions: 3rd re -inspection
Comments: Deficiencies noted in report number 42 dated 4-27-2016 have been corrected.
L
Services:
Terracon Rep.: Louis, Perini
Reported Too Client
Contractor: Hutton Construction
Report Distribution:
(1) Hunan Construction, Inc.,
(1) Platinum Construction, Inc,
yalmond(aUtton.construction
i3mes(?Platinumcoustruction.0m
(1) St. Lucie County, cicioj@sducieco.org
(1) Velcun Group, Inc,
emcstov(dvelwngroup.com
(1) Velcan Group, Inc,
taudyrAa elcunmurp.com
Reviewed By:
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This
indicated above and shall not be reproduced except in full without the Written consent of our company. Test re
the actual samples tested at theloration(s) referenced and are not necessarily indicative of the properties of of
Cr0019, 10.1613; Rev2 Page I of I
SEP 1 6 RECD
�s02-0/2 7
FL RegisfSHYrar
on No. 44082
t is exclusfor the use of the client
transmitteein are only applicable to
pparentiy or identical materials.
STRUCTURAL STEEL OBSI , _ ATIONS REPORT
Report Number: HB161005.0042
Service Date: 04/25/16
Report Date: 04/27/16
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
Ire racon
607 NW Commodity Cv
Port St Lucie, FL 34986-2250
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB161005
Services Requested By: Kevin O'Steen with Hutton Construction
Reinforcing Steel Type:
Observation Location(s):
SCANNED
BY
St. Lucie County
Observation Results:
Based on our observations, the reinforcing steel placement at the above -referenced locations DID NOT APPEAR to be
completed in general accordance with the identified project drawings. Please see the Exceptions for a discussion of non-
conforming items.
Referenced Drawings: Official construction documents, Metal building drawings section A on page 5
• Exceptions:
• Parapet rake walls steel framing top channel connections missing bolts at plated connections, 2 bolts required at each
connection, (6) six locations missing bolts and fastened together with tech screws.
FBC 107.4 Amended Construction Document required by (DOR) designer of record of metal building before re -
inspection.
• Roof framing purlins concealed at time of inspection, 100% of roof standing seam panels installed, unable to verify
roof panel clip connection to roof framing members holding down metal roof panels, roof insulation 100% complete,
unable to verify from below roof clip connection to roof framing system.
• Main roof framing support W-shape beams supported by columns missing bolts in various locations.
• North, South, East, West metal building comers structural steel columns to wall girt connections missing bolts.
Comments: In progress / ongoing.
RECEIVED
SEP 14 2016
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
(1) Hutton Construction, Inc.,
(1) Platinum Construction, Inc,
galmonl(,c Itoncooewcrion
ia111es P1aVnumCnnsMcfion.org
(1) St. Lucie Cowry, cicioj@rtlucieco.org
(1) Velcon Group, Inc, Reviewed By:
emestovpvelcongmw.cam
(I) Velcon Group, Inc,
rnndvr(u}vcicong=p.com
FL
The tests were performed in general accordance with -applicable ASTM, AASHTO, or DOT test methods. This report is
indicated above and shall not be reproduced except in full without the written consent of our company. Test results trar
the actual samples tested at the locallon(s) referenced and are not necessarily Indicative of the properties of other appr
CNa13, 1041 13, Rc..v Pagc I of 1
ation No. 44082
ely for the use of the client
herein are only applicable to
milar or identical materials.
STRUCTURAL STEEL OW) VATIONS REPORT
Report 1-113161005.0042 I rerracon
Service Date: 04/25/16 607 NW Commodity Cv
Report Date: 04/27/16 Port St Lucie, FL 34986-2250
772-343-9787 Reg No: 6870
Client Project
Hutton Construction, Inc. Family Dollar
Attn: Nancy Bunch 10331 Lennard Road
732 Cherry Street Port St. Lucie, FL 34952
Chattanooga, TN 37402
Project Number: HB161005
Botts
Services:
Rake
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
(1) Hutton ConsWction. Inc.,
(1) Platinum Construction; Inc,
xalmond9hunon.constmction
lamcsAPlafin=Cons ction.orx
(1)St. Lucie County, cieioj@stluciew.org
(1) Velcon Croup, Inc,
cmesm avciconAMP.Mat
(1) Velcon Group, Inc,
randyravelcongmup.com
Reviewed By:
Bolts
FL
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclu:
Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitte
the actual samples tested at the location(s) referenced and are not necessarily indicati4e of the properties of other apparently
Page 1 of 1
tNo. 44082
r the use of the client
a are only applicable to
or Identical materials.
STRUCTURAL STEEL OBS, NATIONS REPORT
Report HB161005.0042
Service Date: 04/26/16
Report Date: 64/27/16
Client
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
at
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
(1) Hutton Construction, Inc.,
(1) Platinum Construction, Inc,
galmonclRbutton.constmction
jamcsAPIatinumConstmction.org
(1) St. Lucie County, cicioj@stlucieco.org
(1) Velcon Group, Inc,
emestovCmVelcongmup.com
(1) Velcon Group, Inc,
iandvr9velcongroup.com
1 rerracon
607 NW Commodity C
Port St Lucie, FL 34986-22f
772-343-9787 Reg No: 68i
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
Number: HB161005
(Photo No.) I Bolts Missing / Roof Parapet Rake Framing
Reviewed By:
FL Reeishrion No. 44082
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclus ely for the use of the client
Indicated above and shall not be reproduced except In full without the written consent of our company. Test results t ansmitte stein are only applicable to
the actual samples tested at the locatlon(s) referenced and are not necessarily Indicative of the properties of other apparently liar or Identical materials.
Page 1 of 1
STRUCTURAL STEEL OBC-i A,VATIONS REPORT
Report H13161005.0042
Service Date: 04/25/16
Report Date: 04/27/16
Client
Hutton Construction, Inc.
Attn:Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
(Photo No.) Bolts Missing / Roof Parapet rake Framing
��.+.ffA [II[il[[annm c 1 C
'T- :IStI[IfCrt[n[numnn o
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
lterracon
607 NW Commodity Cv
Port St Lucie, FL 34986-22.50
772-343-9787 Rea No:6870
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB161005
_seuln)r m[inumu�mm[Ir;r-, I -
-, P ¢�
IP
(1) Hutton Construction, Ina, (I) Platinum Coasuuction, lac,
galmond64M1utton.cunstrucnon lamespPletinutnConstruction.org
(1) St. Luce County, dd0j@sduciwo.org (1) Velcon Group lag Reviewed By:
emestovCWvelcongroup.rnm
(1) Velmn Group, Inc,
M1Ch111
O'COnI O[
mndyr(ijvclmngmuo-con,
FLRegisionNo.44082
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclus
for the use of theclient
Indicated above and shall not tie reproduced except in full without the written consent of our company. Test results transmitterein
are only applicable to
the actual samples tested at the Iocation(s) referenced and are not necessarily Indicative of the propertles of other apparentlyar
or Identical materials.
Page 1 of 1
STRUCTURAL STEEL OBE :_ YATIONS REPORT
Report HB161005:0042 I rerracon
Service Date: 04/25/16 607 NW CommodityCv
Report Date: 04/27/16 Port St Lucie, FL 34986-2250
772-343-9787 Reg No: 6870
Client Project
Hutton Construction, Inc. Family Dollar
Attn:Nancy Bunch 10331 Lennard Road
732 Cherry Street Port St. Lucie, FL 34952
Chattanooga, TN 37402
Project Number: HB161005
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
(1) Hutton Construction, Inc.,
(1) Platinum Construction, Inc,
01mond(aihunun.constmction
lames(a)PlatinumCooshuclion.om
(1) SL Lucie county, cicioj@nlucieco.org
(1) Veleon Group, Inc, Reviewed By:
emesuw rAvelcommp.com
(1) Velcun Group, Inc,
rendyrRvelconmup.com
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is
indicated above and shall not be reproduced except in full without the written consent of our company. Test results trar
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other appe
Page 1 of 1
ration No. 44092
rely for the use of the client
herein are only applicable to
imiter or Identical materials.
STRUCTURAL STEEL OBSI_--, . 'ATIONS REPORT ��������
Report Number. HB161Q05.0071
Service Date: 018/24/16 607 NW Commodity Cv
Report Date: 09/02/16 Port St Lucie, FL 34986-2250
772-343-9187 Reg No: 6870
Client Project SCANNILL
Hutton Construction, Inc. Family Dollar BY
Attn: Nancy Bunch 10331 Lennard Road
7.32 Cherry Street Port St. Lucie, FL 34952 �¢• Lucie C011ntt
Chattanooga, TN 37402
ProiectNumber' IM161005
Services Requested By: Garrett Almond
Connection Type/Description: Roof Panel Fasteners / Dry In
Visual Observation Ele,vation(s)/Location(s): Metal standing seam crimp roof panels
Type of Observation: Structural steel metal building
Referenced Documents: Official construction documents
Observation Results:
Based on our visual observations, the connections observed at the referenced locations appeared to be the proper
size, type, in the proper location and placed in general accordance with the identified referenced documents.
Exceptions: NA
Comments: NA
Services:
Terracon Rep.: Louis, Perini
Reported To:
Contractor: Hutton
Report Distribution:
(1) Hutton Construction, Inc.,
ualmond b4gon.conmuction
(1) St. Lucie County, cicioj@stlucimo.org
(1) Velcon Croup, Inc,
renayr(alvelcon¢row-cm
(1) Platinum Construction, Inc,
jinuo(a)PlatinumComouction.orz
(1) Velcon Croup, Inc,
..stovQvelconmup.cotn
Reviewed By:
FL
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclu:
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitte
the actual samples tested at the location(s) referenced and are not necessarily Indicative of the properties of other apparently
Cr11019, 10-I&D, Rev2 Page I of I
SEP 1 6 RECD
No.44082
the use of the client
are. only applicable to
r identical materials.
STRUCTURAL STEEL OBE; MATIONS REPORT
Report HB161005.0071
Service Date: 08/24/16
Report Date: 09/02/16
Client
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
r
a
Photo No.1 Roof panels fasteners dry in
1 rerracon
601 NIN Commodity CV
Port St Lucie, FL 34986-2250
772-343-9787 Reg No: 6870
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
HB161005
Photo No. No. 4 - Roof panel fasteners dry in
9
Services:
l
Terracon Rep.: Louis, Perini
Reported To:
Contractor: Hutton
Report Distribution:
(1) Hutton Con=c idn, htc.,
(1) Platinum Construction, Inc,
gahnond(a?hutton.conshuction
iamesgPlatinumConstruction.org
(I) St. Lucie Cmmty, cicnq@sduci«o.org
(1) Velcon Group, Inc: Reviewed By:
emcstovAvcicongouo.com
(1) Velcun Group, Inc,
- -
mndyaiilvcicocWo .corn
FL Regis
"on No082
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusiv
for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted
rein are only applicable
to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently sit
iar or identical materials.
Page 1 of 1 I
i
STRUCTURAL STEEL OBE ,
-IfATIONS REPORT
l ��rr�con
Report HB161065:0074
Service Dater 09/06/16
607 NW Commodity Cv
Report Date: 09/09/16
Port St Lucie, FL 34986-2250
772-343-9787 Reg No:6870
Client
Hutton construction, Inc.
SCANNED
Project
Family Dollar
Attn:Nancy Bunch
BY
10331 Lennard Road
732 Cherty Street
St. Lucie County
Port St. Lucie, FL 34952
Chattanooga; TN 37402
Project Number. HB16.1005.
Photo No. 1 Roof rake parapet wall corrected bolted
connections; 9-62616
Roof rake parapet wall
Photo No. 3 connections, 9-6-2016
Roof rake parapet wall corrected bolted
Photo No. 2 connections, 9-6-2016
Roof rake parapet wall corrected bolted "
Photo No. 4 connections, 9-6-2016
Services:
Terracon Rep.: Louis, Perini `
Reported To: Client
Contractor: Hutton Construction
Report Distribution:
(1) Hutton Construction, Inc., (1) Platinum Construction, Inc,
galmond@hutton.consttucdon james@Platimanconsumcnon.mg
(1)St. Lucia County, cicioj@sducieco.org (1)Velcon Group,Inc, R¢VI¢W¢d By:
ttnestov�t{velcongouD.com
(1) Velcon Group, Inc,
randyr@velconmup.com
FL
The tests were performed in general accordance with applicable ASTM, AASHTO; or DOT test methods. This report is
indicated above and shall not be reproduced except in full without the written consent of our company. Test results tran
the actual "samples tested at the location(s) referenced and are hot necessarily indicative of the properties of other appa
Page 1 of 2
INo. 44082
r the use of the client
rare only applicable to
or identical materials.
STRUCTURAL STEEL OBSI. 'ATIONS REPORT
Report Number: HB161005.0073
Service Date: 09/01/16
Report Date: 09/09/16
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
SCANNED
BY
St. Lucie County
1 rerracon
607 NW Commodity Cv
Port St Lucie, FL 34986-2250
772-343-9787 Reg No: 6870 _
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB161005
Services Requested By: Garrett @ Hutton
Connection Type/Description: Metal Building Bolting
Visual Observation Elevation(s)/Location(s): Parapet walls framing bolted connections
Type of Observation: Structural steel
Referenced Documents: Official construction documents
Observation Results:
Based on out visual observations, the connections observed today DID NOT APPEAR to be placed in general accordance
with the identified referenced documents. As a result, the observation is noted as Non -Conforming.
Exceptions: Re -inspection to verify roof parapet wall framing & bolting deficiencies noted in report dated 4-27-16, report
number 42. See attached photographs.
Comments: No deficiencies corrected as detailed on report number 42, dated 4-27-2016.
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor:
Report Distribution:
(1) Hutton Construction, Inc., (1) Platinum Construction, Inc, �
gahaond(a7,hutton.construction iames(olPlatirunConsnuctiomorx
(1) st Lucie Comity, cicioj@stlucieco.org (I) Velcon Group, lnc, Reviewed By:
emestov@velconxroup.com
(1) Velcon Group, Inc,
raudyr@velcotutroup.com
FL
The tests were performed in general accordance with applicable ASTM; AASHTO, or DOT test methods. This report is
indicated above and shall not be reproduced except in full without the written. consent of our company. Test results her
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other appe
Cr0019,161613,Rev.2 Page I oft
SEP 1 6 REC'D
wion No. 44082
ely for the use of the client
herein are only applicable to
milar or Identical materials.
.ti
STRUCTURAL STEEL OB4---__VATIONS REPORT ���������
Report HB161005:0073
Service Date: 09/01/16 607 NW Commodity Cv
Report Date: 09/09/16 Port St Lucie, FL 34986-2250
772-349-9787 Reg No:6870
Client Project
Hutton Construction, Inc. Family Dollar
Attn: Nancy Bunch 10331 Lennard Road
732 Cherry Street Port St. Lucie, FL 34952
Chattanooga, TN 37402
Project Number. HB161005
V
_ y
Photo No.1 Rake parapet wall metal framing bolts missing,
not per plan.
Photo No. 3
Services:
pPhotoNo.2
i
Rake. parapet wall metal framing bolts missing,
not per plans.
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor:
Report Distribution:
(1) Huttou Construction, Inc., (1) platinum Conshuction, Inc,
olmondphunon.wnstmction jamcs(a?PlatinumConstruction.org
(1)StLucm County, nigriucieco.org (1) Velcon Group, Inc. Reviewed By:
emestovftvelcongroup.com
(1) Velcan Group, Inc,
], O'COIlnO
randvrra�velcongoup.wm
FL Regis
ation No. 44082
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report Is exclus' I ly for the use of the client
Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitte
erein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily Indicative of the properties of other apparently
ilar or identical materials.
Page 1 of 1
STRUCTURAL STEEL OBSI= "ATIONS REPORT 7 F�rr�con
Report Number: HB161005.0070
Service Date: 08/24/16 607 NW Commodity Cv
Report Date: 09/02/16 Port St Lucid, FL 34986-2250
772-343-9787 Reg No: 6870 .
Client Project
Hutton Construction, Inc. SCANNED Family Dollar
Attn: Nancy Bunch BY 10331 Leonard Road
732 Cherry Street Port St. Lucie, FL 34952
Chattanooga, TN 37402 St. LUCID. Cnunty
Project Number: HB161005
Services Requested By: Garrett Almond
Connection Type/Description: Structural Steel Metal Wall Panels Fasteners
Visual Observation Elevation(s)/Lodation(s): Exterior North, South East West, Parapet walls.
Type of Observation: Structural Steel Metal Building Components
Referenced Documents: Official construction documents permit set.
Observation Results:
Based on our visual observations, the connections observed at the referenced locations appeared to be the proper
size, type, in the proper location and placed in general accordance with the identified referenced documents.
Exceptions: NA
Comments: NA
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton
Report Distribution:
(1) Hutton Construction, Inc.,
r1mond inigon.construction
(1) St. Lucie Cowty, cicioj@sducieco.org
(1) Velcon Group, Inc,
mndYK4velcon=up.com
(1) Platinum Construction, Inc,
iamesAPlafiniunConswction.org
(1) Velcon Group, Inc, - Reviewed By:
emestovAvelconmoup.com
FL
5EP 1 6 OECD
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclu:
Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitte
the actual samples tested at the location(s) referenced and are not necessarily indicative of the.properties of other apparently
Cfa019,1 &D, Irevl Page 1 of 1
1 No. 44082
r the use of the client
1 are only applicable to
or identical materials.
STRUCTURAL STEEL OB;,,� _,VATIONS REPORT
Report HB161005.0070
Service Date: 08/24/16
Report Date: 09/02/16
Hutton Construction, Inc.
Attn: Nancy Bunch
732 Cherry Street
Chattanooga, TN 37402
Services:
Terracon Rep.: Louis, Perini
Reported To: Client
Contractor: Hutton
Report Distribution:
Irerracon
607 NW Commodity Cv
Port St Lucie. FL 34986-2250
Project
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
Project Number. HB161005
(1) Hutton Construction, Inc., (1) Platinum Construction, Inc,
galmwd(alutlon.cons"etion jumes(dPlatinumCarmuction.org
(I) St Lucie County, cicioj(av)stlucimo.org (1) Velcon Group, Inc, Reviewed By:
emestovielvcleonguaga.eom
(1) Velcon Group, Inc,
sandwAvelcanpmw.com
FL Regi tration No. 44082
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exGu iv y for the use of the client
Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitte rein are only applicable to
the actual samples tested at the locations) referenced and are not necessarily Indicative of the properties of other apparenlly Her or Identical materials.
Page 1 of 1
EARTHWORK OBSERVATIOP� ~--PORT
Report Number: HB161005.0020
Service Date: 03/08/1
Report Date: 03/08/1 LE2 C 12 0 V pp
I
Client v
Hutton Construction, Inc. MAR 9 Ui
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402 _AZ_
I RECEV.'D j�:. : 0 '116
1 rerracon
607 NW Commodity Cv
Port St Lucie, FL 34986-2250
Project
Family Dollar SCANNED
10331 Leonard Road BY
Port St. Lucie, FL 34952 St. Lucie Countv
ProiectNumber: FIB161005
Summary of Earthwork Observations and Density Testing for the Building Pad:
This summarizes the earthwork observations and density testing during the preparation of the building pad for the
proposed Family Dollar at 10331 Lennard Road in Port St. Lucie, FL. The earthwork was performed between
February 3rd and March 71h, 2016. Our on -site contact was Kevin O'Steen with Hutton Construction. Our field
personnel typically discussed the daily earthwork activities with Kevin and provided verbal results of the daily
observations and testing.
As outlined in the Geotechnical Engineering Services Report prepared by KCI Technologies (KCI), dated
November 19, 2012, there was uncontrolled fill and buried debris that need to be removed from the building pad
area and replaced with compacted embankment fill. At the time of our initial observations it appeared that some of
the uncontrolled fill had been removed from the building pad area.'The site contractor utilized a large trackhoe to
excavate about 8 to 8 1/z feet of uncontrolled fill and buried debris from the building pad. Based on the survey
.stakes in the field (by others), the building excavation was oversized approximately 10 feet beyond the building
footprint. The bottom of the excavation ranged from approximate elevation +8 NAVD in the NW corner of the
excavation to about elevation +9- NAVD along the east side of the excavation (see attached sketch). The soils
encountered at the excavation bottom consisted of a poorly graded gray to light gray fine to medium grained sand
that were judged to be native soils. A dozer was used to level the excavation bottom and push the standing water
to the lowest point (NW corner) of the excavation. The contractorused pumps to dewater the excavation bottom. A
large vibratory smooth' drum roller used to surface compact the. soils at the excavation bottom prior to
embankment fill placement.
The embankment fill was relatively clean sand with less than 10% fines imported from another site consisting of
gray and brown fine to medium sand. The fill was hauled to the site with double -axle dump trucks and placed in
thin, uniform lifts about 1-foot thick with a dozer then compacted with the large vibratory smooth drum roller. In -
place density tests.were taken as each lift of embankment fill in the building pad area. A total of thirty (30) density
tests were performed, all tests met or exceeded the density requirement of 95% Modified Proctor density (ASTM D
1557).
Based on our observations and testing, the earthwork to prepare, the building pad was completed in general
accordance with the project plans and specifications. The daily earthwork observation reports, laboratory Proctor
test reports and in -place density test reports have been previously submitted. As requested, original signed and
sealed reports will be delivered to Mr. Joe Cicio with the St. Lucie County Building Inspection Department.
11 F 0 PY
ILL 06
Services: Turbidity measurement readings performed in the field at the locations indicated.
TerraconRep.: David T. Youngstrom .
Reported To: Client
Contractor: Platinum
Report Distribution:
(I) Huaon Construction, Inc., Emailed
(1) St Lucie County, cicioiCastlucieco.org
Reviewed By:
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exc t
ely for the use of the client
indicated above and shall not be'reproduced except in full without the written consent of our company. Test results transmi hereinare only applicable to
the actual samples tested.at the location(s) referenced and are not necessarily indicative of the properties of other apparenimilar or identical materials.
AFONZ 10.16-13, Re 3 Page 1 of 1
° W/ 5' HIGH MASONRY WALLS
6 OPAQUE GATES
(SEE DETAIL)
Iq +81n
In PROP. +9
(6) BIKE
SPACES -
16'
81.92'7LL.0AbING—
b+8
WALL PACKMOUNTED ATE
11.5' ABOVE FFE
(TYP.)
PAVEMENT
PROP. (TYP')
1-STORY CBS
DISCOUNT STORE
0
GROSS FLOOR AREA = 8,593 S.F.
F.F.E. = 15.25 N.A.V.D.1988 0
+9
PROP.
WATER
SERVICE 'F9
a D
BLDG.
SEWER
od
m . PROP
o. PAVT.. w
Excavation Sketch
Site Plan: N/A
-
Hutton Construction, Inc.
ReportNumber: HB361005.0020
Attn: Lucas Borneman
Technician: Jerry Logan
607 NW Commodity Cv
736 Cherry Street
Date: 03/08/16
Port St Lucie, FL 34986-2250 -
Chattanooga, TN 37402
Scale: Not to Scale
772-343-9787 Reg No: 6870
U 020, M&v, Re .O
FIELD DENSITY TEST REPOR'_ - ,� rL'���COr
Report Number: HB161005.0009
Service Date: 02/22/16 607 NW Commodity Cv
ReportDate: 02/25/16 Port St Lucie, FL 34986-2250
Task: 772-343-9787 Reg No: 6870
Client
Hutton Construction, Inc.
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402
Project
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB161005
Material Information
Lab Test Data
Project Requirements
Optimum
Water
Max. Lab
-Water
Mat. Proctor
Laboratory Content
Density
Content Compaction
No. Ref. No.
Classification and Description
Test Method (%)
(pcf)
(%) (%)
1 HB161005.0003
Grey fine to medium SAND, trace
ASTM D1557 11:8
104.2
N/A Min 95
silt '
2 HB 161005.0002 Grey fine to medium SAND, trace
ASTM D 1557
13.2
110.5
N/A
Min 95
clay & shell
Field Test Data
Probe Wet
Water
Water
- Dry
Percent
Test Lift/ Mat.
Depth Density
Content
Content
Density
Compaction
No. Test Location Elev. No.'
(in) (pcf)
(pcf)
(%)
(pcf)
(%)
Building Pad, Excavation Subgrade
SE Comer of Pad 10.50 2 0-12 123.1 14.7 13.6 108.4 98
NE Comer of Pad 9.50 2 0-12 125.4 15.6 14.2 109.8 99
Center of Pad 10.00 1 0-12 114.8 13.4 13.2 101.4 97
Datum: NAVD Serial No: 36817 Stal. Cut. M:723 Std. Cut. D: 1931
Comments: Test and/or retest results on this report meet project requirements as noted above.
Test and/or retest results on this report meet project requirements as noted above. The western 1/3 of the building excavation
subgrade was still too wet to take density tests. ..
Services: Perform in -place density tests to determine degree of compact
Terracon Rep.: Jerry Logan
Reported To: Client
Contractor:- Platimum
Report Distribution:
(I) Hutton Construction, Inc., Emailed .
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT
indicated above and shall not be reproduced except in full without the written consent of ou
actual samples tested at the Iocaflon(s) referenced and are not necessarily indicative of the
CaeoOr, 1-W12, Re 3 - Page I of I
FIELD DENSITY TEST REPORr - 1rerracon
Report Number: 1-IB161005.0011
Service Date: 02/27/16 607 NW Commodity Cv
Report Date: 03/04/16 Port St Lucie, FL 34986-2250
Task: 772-343-9787 Reg No: 6870
Client
Hutton Construction, Inc.
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402
Project
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
Project Number: HB161005
Material Information
Lab Test Data
Project Requirements
Optimum
Water Max. Lab
Water
Mat. Proctor
Laboratory Content Density
Content Compaction
No. Ref. No. Classification and Description
Test Method (%) (pef)
(%) (%)
1 HB161005.0003 Grey fine to medium SAND, trace
ASTM D1557 11.8 104.2
N/A Min 98
silt
Field Test Data Probe Wet Water
Test Lift / Mat. Depth Density Content
No. Test Location Elev. No. (in) (pcf) (pef)
Water
Content
(%)
Dry
Density
(pcf)
Percent
Compaction
(%)
Building Pad, Embankment Fill
1 SE Comer of Building Pad 11.00 1 12 117.1 14.0
13.6
103.1
99
Excavation
Datum: NAVE) Serial No: 36817 Std. Cnt. M:722 Std. Cut. D: 1931
Comments: Test and/or retest results on this report meet project requirements as noted above.
Test and/or retest results on this report meet project requirements as noted above.
Services: Perform in -place density tests to determine degree of compacti
Terracon Rep.: Jerry Logan
Reported To: Client
Contractor: Platinum -
Report Distribution: .:
(1) Hutton Construction, Inc., Entailed
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT t
indicated above and shall not be reproduced except in full without the written consent of our
actual samples tested at the location(s) referenced and are not necessarily indicative of the
CR0001, 11-1&12, Ra 3 Page 1 of 1
FIELD DENSITY TEST REPORT:
1 rerracon
Report Number: HB161005.0014
Service Date: 02/29/16
607 NW Commodity Cv
Report Date: 03/07/16
Port St Lucie, FL 34986-2250
Task:
772-343-9787
Reg No: 6870
Client
Project
Hutton Construction, Inc.
Family Dollar
Attn: Lucas Bomeman
10331 Lennard Road
736 Cherry Street
Port St. Lucie, FL 34952
Chattanooga, TN 37402
Project Number: HB161005
Material Information
Lab Test Data
Project Requirements
Optimum
Water Max. Lab
Water
Mat. Proctor
Laboratory Content Density
Content Compaction
No. Ref. No. Classification and Description
Test Method (%) (pef)
(%) (%)
1 HB161005.0003 Grey fine to medium SAND, trace
ASTM D1557 11.8 104.2
N/A Min 98
silt
2 HB161005.0007 Brown fine to medium SAND, trace
ASTM D1557 11.8 111.0
N/A Min 98
silt
Field Test Data
Probe Wet Water Water
Dry Percent
Test Lift! Mat.
Depth Density Content Content
Density Compaction
No. Test Location Elev. No.
(in) (pcf) (pef) (%)
(pcf) (%)
Building Pad, Embankment Fill
1
NW Comer of Building Pad
11.00
1
12
119.2
15.9
15.4
103.3
99
Excavation
2
SW Comer of Building Pad
11.00
1
12
118.8
15.2
14.7
103.6
99
Excavation
3
SE Comer of Building Pad
11.00
1
12
119.3
15.4
14.8
103.9
100
Excavation
4
NE Comer of Building Pad
11.00
1
12
118.2
15.5
15.1
102.7
99
Excavation
5
Center of Building Pad, South
11.00
1
12
118.5
15.9
15.5
102.6
98
Side
6
Center of Building Pad, North
11.00
1
12
118.2
15.4
15.0
102.8
99
Side
7
NE Corner of Building Pad
12.00
2
12
125.5
14.7
13.3
110.8
100
8
NW Comer of Building Pad
12.00
2
12
123.8
12.9
11.6
110.9
100
-9--SE"Comer
-99
10
SW Corner of Building Pad
12.00
2
12
124:3
13.6
12.3
110.7
100
11
Center of Building Pad .
12.00
2
12
124.9
12.3
10.9
112.6
100+
Datum: N"D Serial No: 36817 Slid. Cut. M:716 Std. Cut. D: 1913
Comments: Test and/or retest results on this report meet project requirements as noted above.
Test and/or retest results on this report meet project requirements as noted above.
I
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods - port is exciusivelyfor the use of the client
Indicated above and shall not be reproduced except in full without the written consent of our company. r Its transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties o othe pparently similar or identical materials.
CR0009, I I-I6-12, Rev.] Page 1 of 2 2� 8 -;4( 4
FIELD DENSITY TEST REPOK. "I erracon
Report Number: HB161005.0014
Service Date: 02/29/16 607 NW Commodity'Cv
Report Date: 03/07/16 Port St Lucie, FL 34986-2250
Task: 772-343-9787 Rea No:6870
Client Project
Hutton Construction, Inc.
Attn: Lucas Borneman
736 Cherry Street
Chattanooga, TN 37402
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB 161005
Services: Perform in -place density tests to determine degree of compaction and material
Terracon Rep.: Jerry Logan - - - - -
Reported To:
Contractor: Platinum
Report Distribution:
(1) Hutton Construction, Inc., Emailed (1)St. Lucie County, cicioj@silucieco.org Reviewed By:
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods.
indicated above and shall not be reproduced except in full without the written consent of our company. Te
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties Of othe
ca000r, a-1&I3, acaa Page 2 of 2
i . 'b / -
ly for the used I�he client
fitted herein are only applicable to the
similar or identical materials.
FIELD DENSITY TEST REPOR`. I rerracon
Report Number: H13161005.0017
Service Date: 03/02/16 607 NW Commodity Cv
Report Date: 03/07/16 Port St Lucie, FL 34986-2250
Task: 772-343-9787 Reg No: 6870
Client
Hutton Construction, Inc.
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402
Project
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
Project Number: HB 161005
Material Information
Lab Test Data
Project Requirements
Optimum
Water
Max. Lab
Water
Mat. Proctor
Laboratory
Content
Density
Content
Compaction
No. Ref. No.
Classification and Description
Test Method
(%)
(Pei)
(%)
(%)
I HB 161005.0007
Brown fine to medium SAND, trace
ASTM D 1557
11.8
111.0
N/A
Min 98
silt,
Field Test Data
Probe Wet
Water
Water
Dry
Percent
Test
Lift/ Mat.
Depth Density
Content
Content
Density
Compaction
No. Test Location Elev. No.
(in) (Pei)
(Pei)
(%)
(Pei)
(%)
Building Pad, Embankment Fill
1
NW Comer of Building Pad
13.00
1
12
129.5
14.5
12.6
115.0
100+
2
SW Comer of Building Pad
13.00
1
12
127.2
14.4
12.8
112.8
100+
3
SE Comer of Building Pad
13.00
1
12
126.8
15.4
13.8
111.4
100
4
NE Comer of Building Pad
13.00
1
12
128.3
15.3
13.5
113.0
100+
5
Center of Building Pad
13.00
1
12
125.3
15.1
13.7
110.2
99
Datum: NAVD Serial No: 36817 Std. Cut. M:715 Std. Cut. D: 1927
Comments: Test and/or retest results on this report meet protect requirements as noted above.
Test and/or retest results on this report meet project requirements as noted above.
Are
OServices: Perform in -place density tests to determine degree of compaction and material MendNN 44082
Terracon Rep.: Jerry Logan s
Reported To: STATE OF =
Contractor: Platinum
Report Distribution:
(1) Hutton Construction, Inc., Emailed (I) St. Lucie County, cicioj@sducieco.org Reviewed By:
�t r
F R�b3LL4�L'11at�io.44082
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. s e J_ (ivvel he use�the client
Indicated above and shall not be reproduced except in full without the written consent of our company. T s t nsmitted""herein are only applicable to the
actual samples tested at the location(s) referenced and are, not necessarily indicative of the properties of o er a barently similar or identical materials.
Ca0007, a.141Y. aevv Page 1 of I 1�
FIELD DENSITY TEST REPOR': •' � �C'��c7.COr1
Report Number: HB161005.0019
Service Date: 03/07/16 607 NW Commodity Cv
Report Date: 03/08/16 Port St Lucie, FL 34986-2250
Task: 772-343-9787 Reg No: 6870
Client
Hutton Construction, Inc.
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402
Project
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
Number: HB161005
Material Information
Lab Test Data
Project Requirements
Optimum
Water
Max. Lab
Water
Mat. Proctor
Laboratory
Content
Density
Content
Compaction
No. Ref. No.
Classification and Description
Test Method
(%)
(PC')
(%)
(ova)
1 HB161005.0007
Brown fine to medium SAND, trace
ASTM D1557
11.8
111.0
N/A
Min 98
silt
Field Test Data
Probe Wet
Water
Water
Dry
Percent
Test
Lift / Mat.
Depth Density
Content
Content
Density
Compaction
No. Test Location Elev. No. -
(in) (pcf)
(pcf)
(%)
(pcf)
(%)
Building Pad, Embankment Fill
1
NE Comer of Building Pad
14.00
1
12
125.3
13.7
12.3
111.6
100+
2
NW Comer of Building Pad
14.00
1
12
124.9
12.2
10.8
112.7
100+
3
SE Corner of Building Pad
14.00
1
12
123.4
11.3
10.1
112.1
100+
4
SW Comer of Building Pad
14.00
1
12
125.5
12.3
10.9
113.2
100+
5
Center of Building Pad
14.00
1
12
126.2
12.3
10.8
113.9
100+
6
NE Comet of Building Pad
15.00
1
12
124.0
11.3
10.0
112.7
100+
7
NW Comer of Building Pad
15.00
1
12
127.8
13.0
11.3
114.8
100+
8
SE Comer of Building Pad
15.00
1
12
125.4
12.3
10.9
113.1
100+
9
SW Comer of Building Pad
15.00.
1
12
128.1
12.3
10.6
115.8
100+
10 1
Center of Building Pad
15.00
1
12
126.9
12.4
10.8
114.5
100+
Datum: NAVD Serial No: 36817
Comments: Test and/or retest results on this report meet project reqt
Test and/or retest results on this report meet project requirem
tents as noted :
as.noted above.
Std. Cut. M:714 Std. Cut. D: 1956
Services: Perform in -place density tests to determine degree of compaction and material moisture condition.'
Terracon Rep.: Jerry Logan
Reported To: Client
Contractor: Platinum
Report Distribution: Reviewed B
(1) Hutton Conswction, Inc., Entailed (1) St. Lucie County, ciciolQsducieco.urg 1'
Test Methods: ASTM D6938
-o (to
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repor¢is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-1&12, Rev.] Page 1 of I '
ReportNumber: HB161005.0002
Service Date: 02/01/16
Report Date: 02/05/16
Hutton Construction, Inc.
Attn: Lucas Borneman
736 Cherry Street
Chattanooga, TN 37402
Material Information
Source of Material: Existing Material
Proposed Use: Embankment Fill
Laboratory Test Data
Test Procedure: ASTM D1557
Test Method: Method
Sample Preparation: Dry
Rammer Type: Mechanical
Maximum Dry Unit Weight (pep: 110.5
Optimum Water Content (%): 13.2
Comments:
1 rerracon
607 NW Commodity Cove
Port St. Lucie, FL 34986
772-343-9787 Reg No: 6870
Family Dollar
10331 Leonard Road
Port St. Lucie, FL 34952
ProjectNumbet BB161005
Sample Information
Sample Date: 02/01/16
Sampled By: Michael Cohen
Sample Location: Center of building pad
Sample Description: Grey fine to medium SAND, trace clay &
shell
Result Specifications
Liquid Limit: N/A
Plastic Limit: N/A
Plasticity Index: N/A
In -Place Moisture (%):
Passing #200 (%): 5.6
USCS: SP
Zero Air Volds CurveforAssumed Specific
Gravity 2.65
m'
A T A A In N 11 13 IA IS 1B 17 IA IQ 'NI 11 9J 9
Water Content (%)
Services: Proctor Test: Sample from project site which was delivered to laboratory on Service Date.
sample for Moisture Density Relationship.
Terracon Rep.: Armindo Gonzalez
Reported To:. Client
Contractor: Eddie Huggins
Report Distribution:
(1) Hutton Construction, Inc., Emailed
Reviewed By:
SF
N0.44082
Test Methods:
The tests were performed in general accordance with applicable ASTM, at methods. This report is exclusively for the use of ,
the client indicated above and shall not be reproduced except in full withou Hen consent of our company. Test results transmitted herein
are only applicable to the actual samples tested at the location(s) reference n re It nec�sari i tiye of the properties of other apparently
similar or identical materials. / / /p
ae000Q tatal3,Ra.J Page 1 of 1
Report Number: HB161005.0003
Service Date: 02/01/16
Report Date: 02/05/16
Client
Hutton Construction, Inc.
Attn: Lucas Bomeman
736 Cherry Street
Chattanooga, TN 37402
Family Dollar
10331 Lennard Road
Port St. Lucie, FL 34952
1rerracon
607 NW Commodity Cove
Port St. Lucie, FL 34986
772-343-9787 Reg No: 6870
ProjectNumbei BB161005
Material Information Sample Information
Source of Material: On -site Material Sample Date: 02/01/16
Proposed Use: Compacted Subgrade Sampled By: Michael Cohen
Sample Location: On -site Stockpile
Laboratory Test Data
Test Procedure: ASTM D1557
Test Method: Method
Sample Preparation: Dry
Rammer Type: Mechanical
Maximum Dry Unit Weight (pet): 104.2
Optimum Water Content (%): 11.8
Comments:
Sample Description: Grey fine to medium SAND, trace silt
Result Specifications
Liquid Limit: N/A
Plastic Limit: N/A
Plasticity Index: N/A
In -Place Moisture
Passing #200 (%): 5.3
USCS: SP
Zero Airvolds Curvefor Assumed Specific
,Gravity 2.65 . .
5 6 7 8 9 161112131415161718192D21222324
Water Content (%)
Services: Proctor Test: Sample from project site which was delivered to laboratory on Service Date.
sample for Moisture Density Relationship.
Terracon Rep.: Anders Youngstrom
Reported To: Client
Contractor: Eddie Huggins
Report Distribution:
(1) Hutton Consmcdon, Inc., Entailed
J��;'�No.44082
STATE OF
dewed B :01Y 5"o._�__ ez�
FL Aeeistration No. 44082
Test Methods:
The tests were performed in general accordance with applicable ASTM, MSHTO ids. This report is exclusively for the use of
the client indicated above and shall not be reproduced except in full without the w co sent of our company. Test results transmitted herein
are only applicable to the actual samples tested at the locations) referenced and a not cessarily indicative of the properties of other apparently
similar or identical materials. w Ih 1
cg0005, tat5-t3,xes.7 Page 1 of 1 Zi (y[, I/l`(^/
LABORATORY COMPACTION _ MACTERISTICS
OF SOIL REPOF'
- ��rracon
Report Number: HB161005.0007
Service Date: 02/22/16
607NW CommodityCv
Report Date: 02/26/16
Port St Lucie, FL 34986-2250
772-343-9787 Reg No: 6870
Client
Project
Hutton Construction, Inc.
Family Dollar
Attn: Lucas Bomeman
10331 Lennard Road
736 Cherry Street
Port St. Lucie, FL 34952
Chattanooga, TN 37402
ProjectNumbet HB161005
Material Information
Sample Information
Source of Material: Imported Fill
Sample Date:
02/22/16 Sample Time: 1030
Proposed Use: Embankment
Sampled By:
Jerry Logan
Sample Location:
Northside Stockpile
Laboratory Test Data
Test Procedure: ASTM D1557
Test Method: Method D
Sample Preparation: Dry
RammerType: Mechanical
Maximum Dry Unit Weight (pep: 111.0
Optimum. Water Content (%): 11.8
Comments:
Sample Description: Brown fine to medium SAND, trace silt
Result Specifications
Liquid Limit: N/A
Plastic Lim(t: N/A
Plasticity Index: N/A
In -Place Moisture (%):
Passing #200 (%): 4.0
USCS: SP
Zero Air Volds Curve for Assumed Specilic
Gravity 2.65
3
u
„z
a
m
t
rn
no
3
109
c
108
r
,or
106
A ] G a in „ I, Iq ,d 19 to 11 1N 19
Water Content (%)
Services: Proctor Test: Sample from project site which was delivered to laboratory on Service Date.
sample for Moisture Density Relationship.
Terracon Rep.: Anders Youngstrom
Reported To: Client
Contractor: Platimum
Report Distribution:
(1) Hutton Construction, Inc., Emailcd
OF
FLIIegistration No.44082
Test Methods:
The tests were performed in general accordance with applicable ASTM, AASHT , r t s. This report is exclusively for the use of
the client indicated above and shall not be reproduced except in full without the 1 ant of our company. Test results transmitted herein
are only applicable to the actual samples tested at the location(s) referenced and a not I cessarily indicative of the properties of other apparently
similar or identical materials. �O _ /
CRa006, 14[6U;Rn�] Page 1 of 1 3 `g � ��',/1/.1