GENERAL NOTES:
MIN. SETBACK
FRONT
DESIGN CALCULATIONSSIDES.
CNR SI
REAR
FOR ZNG.
FLORIDA TURNPIKE
FT PIERCE C-STORE
WALL -MOUNTED SIGNS
Fort Pierce Service Plaza — Milepost 144, Florida's Turnpike — Port St. Lucie
1. Design is in accordance with the 2010 Florida Building Code for use within
and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-10 as
shown herein.
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly specified
herein and/or in accompanying engineering drawings. The existing host
structure (if any) must be capable of supporting the loaded system as
verified by building department or architect / engineer of record. No
warranty, either expressed or implied, is contained herein.
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
5. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
6. Aluminum components in contact with steel or embedded in concrete shall
be protected as prescribed in the 2005 Aluminum Design Manual, Part 1A.
Steel components in contact with, but not encased in, concrete shall be
coated, painted, or otherwise protected against corrosion.
7. Engineer seal affixed hereto validates structural design as shown only. Use
of this specification by contractor, et. Al, indemnifies and saves harmless
this engineer for all costs & damages including legal fees & apellate fees
resulting from deviation from this design.
THESC- PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY COMECTIONS
REQUIRED BY PIELD tNSPEC10148 THAT
MAY BE NECESSARY IN ORDL9q TO
COMPLY WITH ALL APPLICABLE CODES.
Index:
Pg 1
Cover
Pg 2
Wind Loads
Pg3
Anchors toWall
Pg4
Bolts at Standoff Tubes
Easy
valid
# 67382
# 29531
Federal Hwy, #200 Eas Seals .com Page 1
Bocaoca Raton, FL 33432 7
CALCULATIONS FOR WALL -MOUNTED SIGNS
/SCE 7-10 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed
Exposure C
Calculations
a = 9.5 3-sec gust speed power law exponent
zg = 900, Nominal ht. of atmos. boundary layer
Gcpi = 0 Internal pressure coeff
160 mph - Exp
"C"
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
HEIGHT
(Zone 4)
(Zone 5)
15 ft
32.2 psf
39.7 psf
20 ft
33.2 psf
42.2 psf
25 ft
34.8 psf
44.2 psf
30 ft
36.1 psf
46.0 psf
35 ft
37.3 psf
47.5 psf
40 ft
38.4 psf
48.8 psf
45 ft
39.3 psf
50.1 psf
50 ft
40.2 psf
51.2 psf
55 ft
42.0 psf
52.2 psf
60 ft
41.8 psf
53.2 psf
70 ft
35.3 psf
70.6 psf
80 ft
36.3 psf
72.6 psf
90 ft
37.2 psf
74.5 psf
100 ft
38.1 psf
76.1 psf
110 ft
38.8 psf
77.7 psf
120 ft
39.6 psf
79.1 psf
130 ft
40.2 psf
80.5 psf
140 ft
40.9 psf
81.7 psf
0 ft
41.5 psf
82.9 psf
5 ft
42.8 psf
85.7 psf
0 ft
L25
44.1 psf
88.1 psf
00 ft
46.2 psf
92.3 psf
ASD Load Combo Coeff: 0.6
Kd = 0.85 Directionality factor
Kzt = 1.0 Topographic factor
A = 10 sq ft Tributary area
Y Y
qx
a
L a
a
( N
0.85
47.3
-1.10
-1.40
0.90
50.2
-1.10
-1.40
0.95
52.7
-1.10
-1.40
0.98
54.7
-1.10
-1.40
1.01
56.5
-1.10
-1.40
1.04
58.1
-1.10
-1.40
1.07
59.6
-1.10
-1.40
1.09
60.9
-1.10
-1.40
1.12
62.2
-1.10
-1.40
1.14
63.3
-1.10
-1.40
1.17
65.4
-0.90
-1.80
1.21
67.3
-0.90
-1.80
1.24
69.0
-0.90
-1.80
1.27
70.5
-0.90
-1.80
1.29
71.9
-0.90
-1.80
1.32
73.3
-0.90
-1.80
1.34
74.5
-0.90
-1.80
1.36
75.7
-0.90
-1.80
1.38
76.8
-0.90
-1.80
1.42
79.3
-0.90
-1.80
1.46
81.6
-0.90
-1.80
1.53
85.5
-0.90
-1.80
Page 2
` EdsySeals
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
CALCULATIONS FOR WALL -MOUNTED SIGNS
P = 46.0 psf
Cabinet
A = 23.7 sqft (entire cabinet)
Wall material: Masonry (ASTM C90, t,so0 psi min)
Anchor type/size: 3/8" Large Diam Tapcon
Ref: Red Head LDT, catalog
Min Embedment: 1.5"
Min edge dist: 4" Min Spacing: 4"
Anchor tensile capacity: Tcap = 229.0 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt = 1087 lb ... = P'A (entire cabinet)
No. of anchors req'd: n = 4.7 total anchors ...= Rt/Tcap
Total anchors required: 5 total anchors balanced over cabinet
OK, use (4) per standoff tube = (32) total.
Page 3
Easy Seats
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
Wall material:
Anchor type/size:
CALCULATIONS FOR WALL -MOUNTED SIGNS
P = 46.0 psf
Cabinet
A= 23.7 sgft (entire cabinet)
Metal Steel studs or extrusions/shapes
3/8" Bo It + Nut
Ref: AAMATIR-A9-1991
Min Embedment: 0.125"
Min edge dist: 1.5" Min Spacing: 1.5"
Anchor tensile capacity: Tcap = 240.4 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt = 1087 lb ... = P*A (entire cabinet)
No. of anchors req'd: in = 4.5 total anchors ...= Rt/Tcap
Total anchors required: 5 total anchors balanced over cabinet
OK, use (2) per standoff tube = (16) total.
Page 4