St. Lucie County
Report No.: CTLA 2037W-2
DC Not. No.: CTL 10011
CTL Certification #: 08-0528.05
Test Requested By:
Ingersoll Rand
9017 Blue Ash Rd.
Cincinnati, Ohio 45242
Date; June 28, 2010
Test Dates: June 21" — 26", 2010
Tests Conducted: TAS 201 (Lg. Missile), TAS 202 (with deviations, no water test) & TAS 203
Design Pressures:
Specimen 1 (TAS 202) - Outswing + 80.0 psf. - 60.0 psf.
Specimen 2 (TAS 202) - Inswing + 60.0 psf. - 80.0 psf.
Specimen 3 & 4 (TAS 201, TAS 203) + 70.0 psf. - 70.0 psf.
(1) DESCRIPTION OF SERIES
.Model Designation: SZ Series 3070 Steel Commercial Flush Door,18 gauge
Overall Size: All Specimens - (Frame) 40.00" wide x 86.00" high x 5.75"" deep.
Confi¢uration. All Specimens - X
No. & Size of Panels: All Specimens - (1) Slab 35.79" wide x 83.19" high.
(2) MATERIAL CHARACTERISTICS
Frame Material:
All Specimens ASTM A-366 16 Ga. Steel, cold rolled as stated by manufacturer
FrameConstruction:
All Specimens Cold rolled steel measuring 2.0" wide face x 5.75" deep x 4`y
Mitered comer tab and slot construction. Extruded alutnA;„
0.500" high x 5" wide x 36" long coped to fit into maipd'u rt' el . _;Nfiiel
three (3) #12 x 1.50" wood screws. __ *: NO 20;24
Page 2 of 8 Ingersoll Rand
Report #: CTLA 2037 W-2
Slab Construction:
All Specimens
Glazine•
Weather-stripping:
All Specimens
OTY
One (1) Strip
One (1) Strip
One (1) Strip
One (1) piece
Hardware:
All Specimens
Single slab measure 35.79" x 83.19" x 1.75". 18 Ga. Galvanized steel skins.
Polystyrene core laminated to both inside faces. Vertical edges square with a
continuous mechanical seam. Top and bottom rails contained 16 GA. steel
channels measuring .688" x 1.660" x 35.66" long, spot welded to face sheets
nominally 2" from each end and 6" on center thereafter. Lock reinforcement is 14 - - -
Ga. and 8 Ga. hinge reinforcements.
N/A
DESCRIPTION
PS-074 Weather-strip
PS-074 Weather-strip
Bulb vinyl bumper basket .250" o.d.
Fas-seal door sweep two (2) fin
LOCATION
Frame Head
Frame Jambs
Length of threshold
Slab bottom
OTY DESCRIPTION LOCATION
Three (3) Ives 5BB1 hinges 4.5" x 4.5" x .134" thick with Three in each frame jamb
four (4) .210" dia. X .525" self threading measuring from rabbet in head
Phillips head countersunk screws to frame and to center of hinge at 9.75",
four (4) Phillips head countersunk screws to the 41.69" and 73.625"
leaf.
Six (6) Wire hinge spacer. One behind each hinge on door
leaf.
One (1) Falcon T series, Grade 1, cylindrical lock 1/2" Door Slab
latch throw.
One (1) National Guard 950A Threshold w/bumper. Frame Sill.
Reinforcement:
All Specimens
OTY DESCRIPTION LOCATION
One (1) Cylindrical lock reinforcement, 14 GA Door leaf lock stile
galvanized steel
Three (3) Hinge reinforcement, 8 GA galvanized steel Door leaf hinge stile
measuring 1.25" x 8" long.
�4tlllttJ
Three (3) Hinge reinforcement, 7 GA steel measuring FrattspYla���/i�r
1.23" x 9.19" long.
�. sTArc or-
Page 3 of 8 Ingersoll Rand
Report#: ' CTLA2037W-2
Weep holes:
Sealant:
All Specimens
N/A
Latex caulking as needed to seal unit into rough opening.
INSTALLATION:
Screws and Method of Attachment:
All Specimens Specimens were tested in wooden test buck, installed with eight (8) 3/8 x 4" lag
bolts (4 per jamb) and three (3) #12 x 1.50" wood screws.
Head: None
Sill: Three (3) #12 x 1.5" wood screws located 6.5", 18", 29.5"
Jambs: Eight (8) 3/8" x 4" lag bolts. Four (4) in each Jamb, located
measuring from bottom to top at 4", 19.97", 51.9", ! 111111r11,
W
k
STATE OF Z'
Page 4 of 8
Report #:
Ingersoll Rand
CTLA 2037W-2 ' `
Test Sequence: TAS 202
1.
Air Infiltration
2.
Y2 Test Pressure Positive
3.
%2 Test Pressure Negative
4.
Design Pressure Positive
5.
Design Pressure Negative
6.
Full Test pressure Positive
7.
Full Test Pressure Negative
Performance Test Results
ASTM 283-91
ASTM E330-02
ASTM E330-02
ASTM E330-02
ASTM E330-02
ASTM E330-02
ASTM E330-02
Deflection Gauges locations
Deflection was measured with two (2) 5" CDI Dial Indicators
Location #1 2" above lock. Location # 2 Mid -span of fasteners in jamb.
AIR INFILTRATION
Air Infiltration Tests were conducted in accordance with TAS 202-94
Air @ 1.57 psf. Actual Allowable
Specimen 1 .13 cfm/ft2 .34 cfm/ft2
Specimen 2 .14 cfm/ft2 .34 cfin/fV
STATIC AIR PRESSURE TESTS
Static Tests were conducted in accordance with TAS 202-94
Specimen 1 - Outswing
Range of test Time (See.) Load (asE) Loc.
Positive loads (Design Pressure + 80.0 psf.)
1/2 Test 30 60
Design 30 80 Loc.I
Test
Negative loads
1/2 Test
Design
Test
Loc. 2
30 120 - Loc. 1
Loc. 2
(Design Pressure — 60.0 psf.)
30 45
30 60
30 90
Loc. I
Loc. 2
Loc. I
Loc. 2
I 2
91
Deflection Perm. Set
Allowable
0.286"
0.149"
0.022" 0.333"
0.041" 0.128"
0.322"
0.087"
All Permanent set numbers are gross numbers
Location (1) - Max. allowable Perm. Set after test load (0.4% of 83.25" span) = 0333
Location (2) - Max. allowable Perm. Set after test load (0.4% of 32.0" span) = 0.12��^.
0.140" 0.333"
0.014" 0.128"
Page 5 of 8
Ingersoll Rand
RBport #: '
CTLA 2037W-2
Performance Test Results
(Continued)
STATIC AIR PRESSURE TESTS (Continued)
Specimen 2 - Inswing
Range of test
Time (Sec.) Load (osf.)
Loc.
Deflection
Perm. Set
Allowable
Positive loads
(Design Pressure + 60.0 psf.)
1/2 Test
30 60
Design
30 80
Loc.1
0.336"
Loc.2
0.091"
Test
30 120
Loc.1
0.145"
0.333"
Loc.2
0.015"
0.128"
Negative loads
(Design Pressure — 80.0 psf.)
1/2 Test
30 45
Design
30 60
Loc.1
0.275"
Loc.2
0.145"
Test
30 90
Loc.1
0.023"
0.333"
Loc.2
0.042"
0.128"
All Permanent set numbers are gross numbers
Location (1) - Max. allowable Perm. Set after test load (0.4% of 83.25" span) = 0.333"
Location (2) - Max. allowable Perm. Set after test load (0,4% of 32.0" span) = 0.128"
Title of Test Method
Specimen 1 Forced Entry AAMA 1304 -02 Passed 300 Ibs
Resistance
Load peak was 30 seconds
Specimen 2 Forced Entry AAMA 1304 -02 Passed 300 Ibs
Resistance
Load peak was 30 seconds
Note: At the conclusion of testing, there was no opening thru which access to the interior hardware, or locking
devices could be gained. In addition there was no openingwhi6 allowed for entrance i `gkthkWpppjjnen tested. The
leaf remained locked, closed and no locks or hinges disengaged. �����51�C;AAy�ii
n
2092A4,11yf o
W_
,aCt
e_
STA'fHOF \
;,rN�
Page 6 of 8 Ingersoll Rand
Report #: CTLA 2037W-2
Performance Test Results (Continued)
Impact Test: Laree Missile
Impact tests were conducted in accordance with TAS 201-94
Each specimen was impacted with an 8 ft., 9 lb. Southern yellow pine 50mm x I00mm (2" x 4") at the
following locations:
Note: Specimen 3 (Outswing) & 4 (Inswing)
X measurement from left edge of specimen.
Y measurement from top edge of test specimen.
Type and weight of missile: # 2 Southern Yellow Pine 2x4, Length approx. 89-5/16" & 9 lb.
Specimen 3
Specimen 4
Specimen #
Impact No. Speed Ft/See.
X Meas.
Y Meas.
3
1 49.7
20.00"
41.50"
3
2 49.5
33.50"
75.00"
4 I 49.3 20.00"
4 2 50.1 33.00"
Result: None of the impacts penetrated the specimen.
42.00"
76.00"
itllilli
O:.
�i STATE OFOR
it
:2
Page 7 of 8 Ingersoll Rand
Report #_ CTLA 2037W-2
Performance Test Results (Continued)
Fatigue Loading Test
Cycle tests were conducted in accordance with TAS 203
Specimen 3 & 4
Positive loads
Design Pressure + 70.0 psf.
Ranee of Test Actual Load (psf.) # of Cycles Cycles/min.
+.0 to 0.5 35.0 600 56
+.6 to 0:6 42.0 70 56
+,.0 to 1.3 91.0 1
671 cycles completed
Negative Loads
Design Pressure - 70.0 psf.
Range of Test Actual Load (Qsf.)
+,0 to 0.5 35.0
+.0to0.6 42.0
+.0 to 1.3 91.0
671 cycles completed
it of Cycles Cycles/min.
600 56
70 56
Deflection Set
0.375" 0.00"
Deflection Set
0.250" 0.00"
Result: Specimen showed no resultant failure or duress after cycle test. No failure of fasteners. There were no cracks
longer than 5" x 1/16" through which air could pass observed.
The results obtained and reported apply only to the specimens tested.
Comment: Nominal 2 mil polyethylene film was used to seal against air leakage during structural loads.
The film was used in a manner that did not influence the test results.
Drawings to be Submitted:
Submittal drawings numbered, 2037W sheets 1 thru 3 of 3, and marked with the CTL st are a part of this
report.
'+,,, STATE OF
Page 8 of 8 Ingersoll Rand
Report M CTLA 2037 W
Remarks: Detailed drawings were available for laboratory records and comparison to the test specimen at
the time of this report. A copy of this report along with representative sections of the test
specimen will be retained by CTL for a period of ten (10) years. The results obtained apply only
to the specimen tested.
This test report does not constitute certification of this product, but only that the above test - -
results were obtained using the designated test methods and they indicate compliance with the
performance requirements (paragraphs as listed) of the above referenced specifications.
Certified Testing Laboratories assumes that all information provided by the client is accurate and
that the physical and chemical properties of the components are as stated by the manufacturer.
Observers
Yuriy Farber - Ingersoll-Rand
Kevin Schmidt - Ingersoll-Rand
Snehil Solanki - Ingersoll-Rand
Dade County Witness:
Not present
All Tests Witnessed by:
Ramesh Patel P.E.
Stephen Gibbs - CTL
Jonathan Pittenger
Lab Technician
Architectural Division
Certified Testing Laboratories
cc: Ingersoll-Rand (4)
Ramesh Patel (1)
File (1)
fr' No 20224 1
GrATE OF I
HA•
ILL I 40.875
yr
40'
FFRAME k
r-- y-.S76-
E HS i
I Hr hU1C'
L�
9.750
6 IfQ
FA`
(5E€ NOTE a)
Hxx
v EQ.-
® � � LEII'Haxz
HTTN I loin
� 4 1w.
@ SEE NGFE 7.
SPA* 11.5fF—i /
H s7s• w
I
FL30•
TW-
SILL ISTALLATMM
MPICAL' j
CI ,
Date'
Verity
1
2'
FRIIF ESHING ORATORIES
ARCHITECTURALiiiii DIVISION
7252 NARCOOSSEE ROAD
ORLANDO, FLORIDA 32822
HEMS,
L ONE ROV OF PS074 VEATIERSTRIPPDIG PER JAMS Alm HEAa
2. AfORt REQmIDpIT9
SEE SHD 2 FOR TESTED AlUQ2 AHm D6TALLATMN
3. HI REQUIREMENT&
KIN Go H DKFS
LOCATIMM A75' FROM RABBET I1 HEAD TO CL W TOM MiGE
I&W FROM FL" TO Cl- OF BITTTOM MD",
EQUALLY SPACED OH BLTWEEK
l SEE SHEET 6 FOR AVAILABLE STANDARD UPEKM MEs A m SPECD7CATDHS
S HAMAFE DISTALLATDN AS PER HAMFACTURER'S DSfRUCTm6
6. 4' FACE HEAD IS AVAD-ABLE WEN FRAME IS GRCUFCB VnW CamCRETE
7. APLLY FALLK AS IEEOE M
Fi PRCCUCf IS MOT APPROYM MERE EATER 09FLTRATXN
D NOTE:3- {.Y x 4X BUTT HWES .ISO 11A1. (4) 012-24 US PER MIME
CORE UATMAL•
'9 ,1 POLYSTYRENE 35.8H' X'81.3• YAX.
10 t —
Su r OL9ETi SHL2
NAri GUARD eDDA .tao',utna. soea is. ss x or x x• um
Ingersoll Rand
SerAT Tdhdoom
FS S HME FLUSH DOOR
IFT
BY FAUXIH
2037w A
'DCAD IT v 3
86"
�."It OF PART 6 SLOTS
Rxm^sEcnw
ITI— 35.625 -� �- 0.75"
g
28.12
FAS-SEAL MOOR SVEEP
TOTAL: (4) EMA
ANCHORS
NTH LAG 0.`25" 0.5"
BOLTS 31.93)
PER JAMB
OF WOOD
�— STUD IIATDNAL UARD 950 SERIES TVRESIILO
WITH SILICONE, VUM
15.97 1 1 ANCHOR TYP. OR NEOPRENE D�pER
_ /_�)
LREFER TO 4" J
SILL INSTALLATION DETAIL
(SHT.1)
LOCK —IN 19 WELD —IN
j�w
SHIM SPACE
1/{' MAX
1 74
SE)F-�DIE31E
AFwIfF1SiINi16
CfATv;3? ESi;.IG A"�..�'�,lSf-`..+1
ARCHITECTURAL DIVIS1014
7252 NARCOOSSEE ROAD
OALANDO. FLORIDA 32822
CTLA No. --
Date Verified:
Verified Bv.-
2"
5.75"
"Diw JAI®
1.94"
BENT TABS
V
SEASSEMBLY
'KD'
'KNOCKED -DOWN'
ASSEMBLY
VEAT/ERSTRD"PING DETAD_
WJ. 11I1Eld1M TYPICAL
EXCEPT WHEN SPECIFIED)
APPROVED
STRIKE JAMB
Ingersoll Rand
ANCHOR DETAILS / MOUNTING CONDITIONS
2037W
N
0FIT
NGLABMTOIC�1°
7252 NARCOOSSEE ROAD K c v i s r u N s
ORLANDO, FLORIDA 32M ` iEs IPTMN I DATE
CTL1 No. d.o3'1 w-A TEST mG usrzeno
I' 1)ati Verified:—
>;.. VcHried.By:
�4
li•
A: �1
cn�rwt ccr.»s�r
FALCON IU-SMM
` UORTM LOCKSET
I5-32 MS S 0
Fp120,000 PSI n
#12-24 MS
SS F1r-120;000 P.Si
FALCON, T-SERIES goo m.a
CYUNDRICAL LEVER LOCKSET W Ingersoll Rand
SorR� Tsdiedoyu
ee rur mv/lw
YNF �v+a+. NNRS76T
FIR TE SOWS 9NiE FW91 DOOR
BY WI slFFl.Cf1AFf
■m way BY c'KmR: T. a uo Mu -ass
2037W
4
APR'tOVE➢
M
#12-24 A
SS Fy=120 K
AVAILABLE
FUNCTIONS
T101
wG;Op T501
.MR
T381
_� T411
Q-1Qr T571
T511
T521
T561
u T581
T851
T881
DESIGN PRESSURE RATING
MAX. DOOR SIZE MIN. LATCH THROW 11 OUTSWING
I INSVVNG
L3070 9/16• +BOb60 PSF
+60/A0 PEP
LARGE AND SMALL MISSILE RESISTANT PER TAS 201 d 203
CYLINDRICAL LOCKSET FALCON T-SERIES
f a '
� a
CK ✓
cRIVIFI rMlIG A."RAT01LE5
o ARCHITECTURAL DIVISION
7252 NARCOOSSEE ROAD
ORLANDO, FLORIDA 32822
CTL.A No. ? o ! AI -
DateYerifictL_
Verified By:
AVAILABLE LEVER DESIGNS
I S•
Clf
ry avuaN
1 t5
I � TIASANS,
1T�
1
QUANTUM
DATE
I A I NEV YNF I6/8Dn0 1 1
ANTERIOR
1,F
an•Max
PANEL
OUTSYANG DOOR WRH
TSERIESCYDNWdUL
LOCK BY FKCON
BA'UA+C j
PANEL
HEIG4Tg--
Ws"HG DOOR Ym
T.SFN£S CYL1MOfUCN.
LOCX BY F'ALOIX1
NOTES,
1. ALL FINISHES OFFERED.
2. SEE CHART FOR AVAILABLE FUNCTIONAL OPTIONS
3. ELECTRICAL INSTALLATION IS UNDER SEPARATE APPROVAL AND MUST BE
RENEWED BY CORRESPONDING AUTHORITY.
a. THIS LOCKSET IS APPROVED TO BE EQUAL ALTERNATIVE TO BE USED IN
SINGLE 18 GA STEEL COMMERCIAL DOORS MOLDING CURRENT APPROVAL
WITH MID PANEL HARDWARE LATCHING
THE LOWEST DESIGN PRESSURE RATING SHALL APPLY.
5. THE DEVICE SHOULD BE INSTALLED W COMMERCIAL STEEL DOOR NO V40ER
THAN OPTIONAL
AND SIGNAL
NIGHER THAW 0!•.
6. ALLOWED
SIGNAL SWITCH ANDPOWEROESN'T TRANSFER UNITS MAY BE USED
AS ALLOWED BY CODE AND IF IT DOESN'T AFFECT THE MECHANICAL PROPERR
7. ALL ELECTRICAL COMPONENTS MUST BE UL APPROVED.
S. THIS HARDWARE CAN BE INSTALLED AS PART OF IMPACT RESISTANT UNIT.
FLORIDA BUILDING CODE
PRODUCT APPROVAL
T SERIES BY FALCON
CYLINDRICAL LOCK
SHEET I DF I I a..