HomeMy WebLinkAboutPROJECT INFORMATIONComponent Constructions Job:
Date: Mar31,2015
RTU 2 By: ProCalos, LLC.
ProCalcs -"Together we'll find the missing piece" Thomas Va.
PlataniaJr. , -®
4273 BE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 772-882-5700 Email: ProCalcs@gmail.com Web: w .PmCalcs.Net License: CACIS15254
•lect
Intormation
For:
Magic Oyster Bar
SCANNED
10999 South Ocean Blvd., Jensen Beach, FL
By
BY
St. Lucie County
Design
Htg Clg
Htg
Clg
Outside db (OF)
39 92
Ins idedb("F)
70
75
Outside RH (%)
80 54
Inside RH (%)
37
50
Outside wb (OF)
36 78
Inside wit ("F)
55
63
Dailyrange (OF)
- 16
Design TD ("F)
31
17
Moisture dill. (gr/lb)
26.9 56.7
Construction descriptions
or
Area
tf-value
uA
Loss
Gain
K
(Bluh1P+F)
(DuhrF)
(BNh)
(Btuh)
Walls
8" thk Blk wall, stucco ext, , R-4.2 Foil, 5/8" gypsum board int fish
n
191
0.12
23.8
740
489
e
120
0.12
16.0
465
672
s
68
0.12
8.4
262
186
all
378
0.12
47.2
1468
1347
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
w
108
0.16
17.0
528
293
nw
38
0.16
6.0
187
95
all
146
0.16
23.0
715
388
Partitions
Frm wall, r-11 cav ins, 1/2" gypsum board int fnsh, 2"x4" metal frm, 16"
254
0.14
34.5
1074
484
o.c. stud
Windows
htg
cig
htg
clg
1 glazing, clr glz, mg no brk frm mat, 1/8" thk; NFRC rated (SHGC=0:70); n
15
1.25 /
125
18.8 /
18.8
583
676
foreground = green grass (0.23); 1.5 It overhang (5 It window ht, 2 ft
sep.); 6.67 ft head ht
1 glazing, cir glz, mtl no brk fnn mat, 1/8" thk; NFRC rated (SHGC=0.70); n
42
1.25 /
1.25
52.5 /
52.5
1633
1893
foreground = green grass (0.23); 1.5 ft overhang (7 ft window ht, 2 It
n
42
1.25 /
1.25
52.5 /
52.5
1633
1893
sep.); 6.67 ft head ht
a
27
1.25 /
1.25
33.5 /
33.5
1043
1868
e
55
1.25 /
1.25
68.5 /
68.5
2132
3816
e
28
1.25 /
1.25
35.0 /
35.0
1089
1949
all
194
1.25 1
1.25
242 /
.242
7529
11419
Doors
Door, wd sc type
n
21
0.33
6.9
216
177
n
21
0.33
6.9
216
174
all
42
0.33
13.9
431
351
Ceilings
Attic ceiling, membrane roof mat, r-20 roof ins, suspended, acoustical
1084
0.16
172
5347
12355
int fnsh, dead air pinm
Floors
Bg Boor, light dry soil, on grade depth, file Br fnsh
84
0.60
50.2
1561
0
2015-Mar-31 13:39:02
wrlghtSoft' Right -Suite® Universal 201515.0.14 RSU17939 Pagel
...rthy Arch110999 South Ocean Blvd Oyster Bar mp Cale= RTS Front Door faces: E
2015-Mar-31 13:39:02
wri9htSGft' RlghtSuile®Unlversal201515.0.14RSU17939 Paget
...rthy Arch\10999 South Ocean Blvd Oyster Bar.rup Cale= RTS Front Door (aces: E
Component Constructions Job:
Date: Mar3l,2015
RTU 1 By: P oCalcs, LLC.
ProCalcs - "Together we'll find the missing piece"
4273 BE Cove Lake Cir. R203, Stuart, FL 34997 Phone: 772-8825700 Email: PioCalm@gmail.com Web: vxlw.ProCakcs.Net License: CAC1815254
Maidoect intormation
For: Magic Oyster Bar
10999 South Ocean Blvd., Jensen Beach, FL
Design Conditions
Htg
Clg
Htg
Clg
Outside db (7)
39
92
Inside db (OF)
70
75
Outside RH (%)
80
54
Inside RH (%)
38
50
Outside wb CF)
36
78
Inside wb (°F)
55
63
Dailyrange (OF)
-
16
Design TD (OF)
31
17
Moisture diff. (gr/lb)
26.9
56.7
Construction descriptions
Or
Area
U-value
UA
Loss
Gain
M
(atuhla'--T)
SWMF)
(BWh)
(BWh)
Walls
8" thk Blk wall, stucco ext, , R-4.2 Foil, 5/8" gypsum board int fnsh
e
- 85
0.12
10.6
328
398
w
281
0.12
35.0
1090
373
all
365
0.12
45.6
1418
771
Partitions
(none)
Windows
htg cig
htg
cig
1 glazing, cir giz, mill no brk frtn mat, 1/8" thk; NFRC rated (SHGC=0.70);a
21
1.25 / 1.25
26.3 /
26.3
816
2007
foreground = green grass (0.23); 1.5 ft overhang (7 ft window ht, 2 ft
e
28
1.25 / 1.25
35.0 /
35.6
1089
2675
sep.); 6.67 It head ht
a
168
1.25 / 1.25
210 /
210
6531
16052
all
217
1.25 / 1.25
271 /
271
8436
20734
Doors
Door, wd so type
w
21
0.33
6.9
216
123
Ceilings
Flat ceiling, membrane roof mat, trill deck, r-10 deck ins, suspended,
1474
0.06
90.9
2827
4969
acoustical int fnsh, dead air pinm
Floors
Bg floor, light dry soil, on grade depth, tile fir fish
67
0.60
40.2
1250
0
2015-Mar-31 13:39:02
Wrightsoft' Right-Sutte® Universal 201515.0.14 RSU17939 Page
...My Nch110999 South Ocean BNtl Oyster Bar.mp Cakc = RTS Front Doorfaces: E
RightSuite® Universal 2016 Short Form Date: Mar 37, 20,5
RTU 1 By: ProCales, LLc.
ProCalcs - "Together we'll find the missing piece"
4273 SE Cove Lake Ch. R203, Stuart, FL 34997 Phone: 772-882-5700 Emafl: ProCalcs@gmail.wrn Web: w .ProCalcs.Nel License: CAC1815254
For: Magic Oyster Bar
10999 South Ocean Blvd., Jensen Beach, FL
Htg Clg
Htg Clg
Outside db
(OF)
39 92
Inside db
(OF)
70 75
Outside RH
N
- 54
Inside RH
N
- 50
Outside wb
(OF)
- 78
Inside wb
(OF)
- 63
Daily range
(OF)
- 16
Design TD
(OF)
31 17
Moisture diff.
(gr/lb)
- 57
Heating Equipment Cooling Equipment
Make
Make
Trane
Model
Model
THCO92F
Type
Else strip
Type
Pkg AC
Efficiency
100 EFF
COP / EER / SEER
12.6
Heating Input
9.0
kW
Sensible Cooling
72.1
MBtuh
Heating Output
30.7
MBtuh
Latent Cooling
16.9
MBtuh
Humidifier
21.2
gpd
Total Cooling
89.0
MBtuh
Leaving Air Temp
78.7
OF
Leaving Air Temp
55.0
OF
Actual Heating Fan
3210
cfm
Actual Cooling Fan
3210
cfm
Equipment Location
RTU 1
System Type
PEAKCV
Fan Motor Heat Type
PACKAGE
Fan & Motor Combined Efficiency
0
%
Static. Pressure Across Fan
0
in H2O
NAME
Area I Heat Sensible
Latent Htg
I Clg
Time
fta Loss Gain
Gain
cfm
cfm
Mens
87 1075
1604
484
125
106
Jul 1600
LDT
Women
97 1254
1812
538
148
121
Jul 1600
LDT
Dining
777 21670
28947
12209
1989
20711
Jul 1600
LDT
Kitchen
513 24292
20685
16135
9491
9121
Jul 1600
LDT
RTU 1
I 1474 I 48290 I
53048
I 29366 I
32101
32101
Jul 1600
LDT
2015-Mor--31 13:39:02
wrightSOft' RightSUBe® Universal 201515.0.14 RSU17939 Page 1
...dhyAMh110999 South Ocean Blvd Oyster Bar.rup Calc=RTS Front Doorfaces: E
Right -Suite® Universal 2015 Short Form Job.
Date: Mar31,2016
RTU 2 By: ProCaIrsOLLC.
ProCalcs - "Together we'll find the missing piece"
4273 BE Cove Lake Cir. A203, Stuart, FL 34997 Phone: 772-8825700 Email: ProCalcs@gmail.com Web: v nv.ProCalcs.Net License: CAC1815254
Froject Intormation
For: Magic Oyster Bar
10999 South Ocean Blvd., Jensen Beach, FL
Htg Clg
Htg Clg
Outside db
(OF)
39 92
Inside db
(OF)
70 75
Outside RH
N
- 54
Inside RH
N
- 50
Outside wb
(OF)
- 78
Inside wb
(OF)
- 63
Daily range
(OF)
- 16
Design TD
(OF)
31 17
Moisture diff.
(gr/lb)
- 57
Heating Equipment Cooling Equipment
Make
Make
Trane
Model
Model
TCH092F
Type
Elec strip
Type
Pkg AC
Efficiency
100 EFF
COP / EER / SEER
12.6
Heating Input
9.0
kW
Sensible Cooling
62.3
MBtuh
Heating Output
30.7
MBtuh
Latent Cooling
26.7
MBtuh
Humidifier
14.9
gpd
Total Cooling
89.0
MBtuh
Leaving Air Temp
79.0
OF
Leaving Air Temp
55.0
OF
Actual Heating Fan
3110
cfm
Actual Cooling Fan
3110
cfm
Equipment Location
RTU 2
System Type
PEAKCV
Fan Motor Heat Type
PACKAGE
Fan & Motor Combined Efficiency
0
%
Static Pressure Across Fan
0
in H2O
NAME
Area I Heat Sensible
Latent Htg
Clg I
Time
ft Loss Gain
Gain
cfm
Cfm
Bar Area
880 30815 1
37930
1 13431 1
21001
18251
Jul 1600 LDT
Wait Station
180 9354
22446
6340
567
11401
Jul 1600 LDT
Office
24 6068 1
2850
4372 1
443
1451
Jul 1600 LDT
RTU 2
1084 1 46236 1
63226
1 24143 1
31101
31101
Jul 1600 LDT
2015-Mar-31 13:39:02
wrightsoft' R19htSutle® Universal 201515.0.14 RSU17939 Paget
...rthy Arrh110999 South Ocean Blvd Oyster Bar.rup Calc = RTS Front Door laces: E
Right -Suite@ Universal 2015 Load Summary Job:
RTU 1 Date: Mar 31, 2015
By: ProCalcs, LLC.
ProCalcs - "Together we'll find the missing piece"
4273 SE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 712-8825700 Email: PtoCalw@gmal.wnn Web: vmv.ProCelcs.Net License: CAC1815254
For: Magic Oyster Bar
10999 South Ocean Blvd., Jensen Beach, FL
Zone:—'RTU 1 COOLING_LOAD
1.
DESIGN CONDITIONS at Jul 1600 LDT
Peak load at Jul 1200 LDT
Inside: 75 OF Outside: 92 OF
TD:
17 OF
RH: 54 % MoistDiff: 56.7 gr/lb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
10189
3.
TRANSMISSION GAINS Sensible
11938
Walls: 1259
-
-
Glass: 3932
-
-
Doors: 303
-
-
Partitions: 0
-
-
Floors: 0
-
-
Ceilings: 6444
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
17888
4576
Occupants: 3804
4206
-
-
Lights: 6123
-
Motors: 0
-
Appliances: 7961
370
-
-
5.
INFILTRATION: Outside air cfm:
50
918
1927
6.
SUBTOTAL: Space load Sensible
Latent
40933
6503
Envelope 40933
6503
-
-
Less external 0
-
Redistribution 0
0
-
7.
SUPPLY DUCT
1228
-
S.
SUBTOTAL: Space load + supply duct
42161
-
Actual cfm: 3210 at supply TD:
20
-
-
9.
VENTILATION: Make-up air cfm:
593
10887
22864
10.
RETURN AIR LOAD: Lighting + plenum (net)
0
-
11.
RETURN DUCT
0
-
12.
TOTAL LOADS ON EQUIPMENT
53048
29366
HEATING LOAD,_,_. ^�
13.
DESIGN CONDITIONS
Mult: 1.0
Inside: 70 OF Outside: 39 OF
TD: 31 OF
14.
TRANSMISSION LOSSES
14147
Walls: 1418
-
Glass: 8436
-
Doors: 216
-
Partitions: 0
-
Floors: 1250
-
Ceilings: 2827
-
15.
INFILTRATION: Outside air cfm:
156 5342
16.
SUBTOTAL: Spaceload
19489
Envelope 19489
-
Less external 0
-
Less transfer 0
-
Redistribution 0
-
17.
SUPPLY DUCT:
585
18.
VENTILATION: Make-up air cfm:
593 20275
19.
HUMIDIFICATION
7941
Piping
0
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
48290
wrl htsoft' 201SMar-3113:39:02
9 RIghtSule® Universal 201515.0.14 RSU17939 Page 1
...rthy ArOM10999 South Ocean Blvd Oyster Bar.rup Cato -RTS Front Door faces: E
Right-Suite(g) Universal 2016 Load Summary Job:
RTU 2 Date: Mar 31, 2015
By: ProCalcs, LLC.
ProCalcs - "Together we'll find the missing piece"
4273 SE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 772-8825700 Email: PmCalcs@gmeil.cortl Web: x .PmCelos.Net License: CAC1815254
•ject Intormation
For: Magic Oyster Bar
10999 South Ocean Blvd., Jensen Beach, FL
Zone'.: RTU 2 - COOLING:COAD
1.
DESIGN CONDITIONS at Jul 1600 LDT
Peak load at Jul 1500 LDT
Inside: 75 OF Outside: 92 OF
TD:
17 OF
RH: 54 % MoistDiff: 56.7 gr/lb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
7810
3.
TRANSMISSION GAINS Sensible
18548
Walls: 2284
-
-
Glass: 3778
-
-
Doors: 362
-
-
Partitions: 0
-
-
Floors: 0
-
-
Ceilings: 12124
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
26232
5357
Occupants: 3411
3773
-
-
Lights: 7549
-
Motors: 0
-
Appliances: 15272
1584
-
-
5.
INFILTRATION: Outside air cfm:
205
3768
7913
6.
SUBTOTAL: Space load Sensible
Latent
56358
13270
Envelope 56358
13270
-
-
Less external 0
-
Redist6bution 0
0
-
7.
SUPPLY DUCT
1691
S.
SUBTOTAL: Space load + supply duct
58049
Actual cfm: 3110 at supply TD:
20
-
-
9.
VENTILATION: Make-up air cfm:
282
5177
10873
10.
RETURN AIR LOAD: Lighting + plenum (net)
0
-
11.
RETURN DUCT
p
12.
TOTAL LOADS ON EQUIPMENT
63226
24143
,'-
13.
DESIGN CONDITIONS
Mult: 1.0
Inside: 70 OF Outside: 39 OF
TD: 31 OF
14.
TRANSMISSION LOSSES
18708
Walls: 3257
-
Glass: 8112
-
Doors: 431
-
Partitions: 0
-
Floors: 1561
-
Ceilings: 5347
-
15.
INFILTRATION: Outside air cfm:
334 11405
16.
SUBTOTAL: Space load
30113
Envelope 30113
-
Less external 0
-
Less transfer 0
-
Redistribution 0
-
17.
SUPPLY DUCT:
903
18.
VENTILATION: Make-up air cfm:
282 9642
19.
HUMIDIFICATION
5578
Piping
0
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
46236
fi IIYSOfC' 2015-Mar-3113:39:02
W
g Right -Su Be® Universal 201615.0.14 RSU17939 Paget
...rthy ArU110999 South Ocean Blvd Oyster Bar.rup Calc=RTS Fmnt Doorfaces: E
ProCalcs
DISCLAIMER
The following pages summarize the heat gain and heat loss of the building using the
ACCA Manual J8 calculation procedure. The calculations are based on the information
given to ProCalcs in the form of drawings, sketches, and interviews. In certain cases,
ProCalcs may make assumptions about design conditions that may or may not be
accurate for the location of concern. It is the responsibility of the installing HVAC
contractor to verify the design conditions before equipment purchase and installation.
Any load calculations provided in the following pages are based upon information
provided by the party submitting a particular project to ProCalcs. ProCalcs has not and
does not independently verify that the data provided to ProCalcs is correct or complete,
and any calculations made by ProCalcs are based upon the information provided by
third parties. ProCalcs makes no claim that the information given to us is correct or
complete.
ProCalcs utilizes WrightSoft Residential 15.0 which is an ACCA Certified and ASHRAE
recommended computer program to determine the heating and cooling loads presented
in this report, and is therefore very accurate. If the information given to ProCalcs is
accurate, and the building is built as per the plans submitted, then the load calculations
presented in this report can be assumed to be accurate. A licensed mechanical
contractor may use these calculations as a starting point in system sizing and selection.
ProCalcs does not provide architectural or engineering plans or diagrams for the public
or for use by contractors or construction companies as final "construction documents".
ProCalcs works with architectural and engineering firms and with contractors in
connection with their designs of heating and air conditioning systems. If the HVAC duct
layout installed on -site DOES NOT match the Manual D duct design prepared by
ProCalcs, then ProCalcs cannot and will not guarantee the performance of any altered
duct design. Final HVAC sizing and selection should be done by a licensed HVAC
contractor. Many factors beyond the scope of this report must be considered prior to
final system selection and design, such as: exact equipment
availability and selections, system controls and location of controls, system air
distribution and cycling, Uniform Building Code requirements, Uniform Mechanical Code
requirements, and many other standard design conventions as listed by the American
Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE).
ProCalcs therefore assumes no liability for final equipment selection or final
system design. Various modifications to the information provided toProCalcs may
have occurred after this Design Support information was prepared, which would
require that this Design Support information be modified in order to be accurate.
After reviewing ProCalcs report, and prior to any system purchase or installation,
please inform ProCalcs in writing of any changes which may alter the
assumptions and calculations contained in this report.
"Florida Energy, Efficiency Code For Building Construction
EnergyGauge Summit®Fla/Com 2010, Effective Date: -March 15, 2012 — Form 506-2010
Total Building Performance Method for Commercial Buildings
PROJECT SUMMARY
Short Dese: Magic Oyster
Owner: Magic Oyster
Addressl: 10999 S. Ocean Blvd
Address2:
Description: Magic Oyster
City:
State:
Zip:
Type: Dining: Bar Lounge/Leisure Class:
Jurisdiction: ST LUCIE COUNTY, ST LUCIE COUNTY, FL (661000)
Conditioned Area: 2582 SF Conditioned & UnConditioned Area:
No of Stories: I Area entered from Plans
Permit No: 0 Max Tonnage
If different, write in:
Jensen Beach
FL
0
Renovation to existing
2582 SF
2582 SF
7.4
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Pagel of 8
Component
Gross Energy Cost (in
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design Criteria Result
2,481.0 2,492.0 PASSED
PASSES
PASSES
PASSES
No Entry
PASSES
No Entry
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 — — — An input report of this design building must be submitted along with this
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 2 of 8
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code; �•�•
ThomasV Platania
Prepared By: ProCalcs, LLC.
Building Official:
Date: 03/31/2015
Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent:
Date:
If Required by Florida law, I hereby certify (') that the system design is in compliance with the Florida Energy
Efficiency Code
Architect:
Reg No:
Electrical Designer:
Reg No:
Lighting Designer:
Reg No:
Mechanical Designer:
Reg No:
Plumbing Designer:
Reg No:
(') Signature is required where Florida Law requires design to be performed by registered design
professionals.
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 3 of 8
Project: Magic Oyster
Title: Magic Oyster
Type: Dining: Bar Lounge/Leisure
(WEAFile: FL_ST_LUCIE_CO_INTLAW)
Building End Uses
1) Proposed
2) Baseline
Total
155.10
195.40
$2,481
$3,115
ELECTRICITY(MBtulkWhl$)
155.10
195.40
45444
57266
$2,481
$3,115
AREA LIGHTS
16.80
33.40
4918
9794
$269
$533
MISC EQUIPMT
23.00
23.00
6746
6746
$368
S367
PUMPS & MISC
0.20
0.10
48
44
$3
$2
SPACE COOL
70.40
82.30
20626
24105
$1,126
$1,311
SPACE HEAT
9.80
8.20
2871
2403
$157
$131
VENT FANS
34.90
48.40
10235
14174
$559
$771
Credits Applied: None
PASSES
Passing Criteria = 2492
Design (including any credits) = 2481
Passing requires Proposed Building cost to be at most 80% of
Baseline cost. This Proposed Building is at 79.6%
EnergyGauge Summit® FlalCom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 4 of 8
Project: Magic Oyster
Title: Magic Oyster
Type: Dining: Bar Lounge/Leisure
(WEAFile: FL_ST LUCIE CO INTL.tm3)
'External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
Ext Light 1 Uncovered Parking Areas — Yes 0.15 180
Parking lots and Drives
Tradable Surfaces: 180 (W) Allowance for Tradable: 750 (W) PASSES
All External Lighting: 180 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
Project: Magic Oyster
Title: Magic Oyster
Type: Dining: Bar Lounge/Leisure
(WEAFile: FL ST LUCIE CO E'4n.tm3)
Lighting Controls Compliance
Acronym Ashrae Description
Area
Design
Min
Compli-
ID
(sq.ft)
CP
CP
ance
Dining
8 Food Service - Leisure Dining
777
1
1
PASSES
Kitchen
7 Food Service - Kitchen
513
1
1
PASSES
Mens Room
6 Toilet and Washroom
87
1
1
PASSES
Women Room
6 Toilet and Washroom
97
1
1
PASSES
Bar Area
9 Food Service - Bar/Lounge
880
1
1
PASSES
Wait Station
9 Food Service - Bar/Lounge
228
1
1
PASSES
PASSES
EnergyGauge Summit& FWCom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 5 of 8
Project: Magic Oyster
Title: Magic Oyster
Type: Dining: Bar Lounge/Leisure
(WEAFile: FL_ST_LUCIE_CO_1NTL.tm3)
System Report Compliance
RTUI System 1
Constant Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
89000
12.60 11.20 12.60 11.40
PASSES
65000 to I35000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
30709
1.00 1.00
PASSES
Au Handling
Air Handler (Supply) -
3210
0.25 0.82
PASSES
System -Supply
Constant Volume
Air Handling
Air Handler (Return) -
3210
0.25 0.82
PASSES
System - Return
Constant Volume
RTU2 RTU 2
Constant Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
89000
12.60 11.20 12.60 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
30709
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
3110
0.25 0.82
PASSES
System -Supply
Constant Volume
Air Handling
Air Handler (Return) -
3110
0.25 0.82
PASSES
System -Return
Constant Volume
PASSES
Plant Compliance
Description Installed Size Design Min Design
No Eff Eff IPLV
Min Category Comp
IPLV liance
None
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 6 of 8
Project: Magic Oyster
Title: Magic Oyster
Type: Dining: Bar Lounge/Leisure
(WEA File: FL_ST_LUCIE_CO_INTL.tm3)
Water Heater Compliance
Description Type
Category Design Min
Eff Eff
Design Max Comp
Loss Loss fiance
Water Heater 1 Electric water heater <= 12 [kW] 0.93 0.92
PASSES
PASSES
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.FJ
Non=:=j
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
3/31/2015 Page 7 of 8
.t: Magic Oyster
Magic Oyster
Dining: Bar Lounge/Leisure
,File: FL_ST_LUCIE_CO_INTL.tm3)
Other Required Compliance
Category Section
Requirement (write N/A in box if not applicable)
Check
Report 506.4.2
Input Report Print -Out from EnergyGauge FlaCom attached
Operations Manual 303.3.1,
Operations manual provided to owner
503.2.9.3,
505.7A.2
Windows & Doors 502.3.2
Glazed swinging entrance & revolving doors: max. 1.0 cfm/ft2, all
other products: 0.3 cfm/ft2
Joints/Cracks 502.3.3
To be caulked, gasketed, weather-stripped or otherwise sealed
El
Dropped Ceiling Cavity 502.3
Vented: seal & insulated ceiling. Unvented seal & insulate roof &
El
side walls
HVAC Efficiency 503.2.3
Minimum efficiencies: Tables 503.2.3(1)-(8)
HVAC Controls 503.2.4
Zone controls prevent reheat (exceptions); separate thermostatic
control per zone;
Ventilation 503.2.5
Outdoor air supply & exhaust ducts shall have dampers that
automatically shut when systems or spaces served are not in use.
Exhaust air energy recovery required for cooling systems
(Exceptions).
ADS 503.2.7.5
Duct sizing and Design have been performed
HVAC Ducts 503.2.7
Air ducts, fittings, mechanical equipment & plenum chambers shall
be mechanically attached, sealed, insulated & installed per Table
503.2.7.2. Fan power limitations.
Balancing 503.2.9.1
HVAC distribution system(s) tested & balanced. Report in
construction documents.
Piping Insulation 503.2.8
HAC and service hot water. In accordance with Table 503.2.8.
Water Heaters 504
Performance requirements in accordance with Table 504.2. Heat
❑
trap required.
Swimming Pools 504.7
Vapor -retardant or liquid cover or other means proven to reduce
heat loss on heated pools; Time switch (exceptions); readily
accessible on/off switch.
Motors 505.7.5
Motor efficiency criteria have been met
Lighting Controls 505.2, 502.3
Automatic control required for interior lighting in buildings >5,000
s.f.; Space control; Exterior photo sensor; Tandom wiring with 1 or
3 linear fluorescent lamps>30W
EnergyGauge SummitO Fla1Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012