Loading...
HomeMy WebLinkAboutPROJECT INFORMATIONComponent Constructions Job: Date: Mar31,2015 RTU 2 By: ProCalos, LLC. ProCalcs -"Together we'll find the missing piece" Thomas Va. PlataniaJr. , -® 4273 BE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 772-882-5700 Email: ProCalcs@gmail.com Web: w .PmCalcs.Net License: CACIS15254 •lect Intormation For: Magic Oyster Bar SCANNED 10999 South Ocean Blvd., Jensen Beach, FL By BY St. Lucie County Design Htg Clg Htg Clg Outside db (OF) 39 92 Ins idedb("F) 70 75 Outside RH (%) 80 54 Inside RH (%) 37 50 Outside wb (OF) 36 78 Inside wit ("F) 55 63 Dailyrange (OF) - 16 Design TD ("F) 31 17 Moisture dill. (gr/lb) 26.9 56.7 Construction descriptions or Area tf-value uA Loss Gain K (Bluh1P+F) (DuhrF) (BNh) (Btuh) Walls 8" thk Blk wall, stucco ext, , R-4.2 Foil, 5/8" gypsum board int fish n 191 0.12 23.8 740 489 e 120 0.12 16.0 465 672 s 68 0.12 8.4 262 186 all 378 0.12 47.2 1468 1347 Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh w 108 0.16 17.0 528 293 nw 38 0.16 6.0 187 95 all 146 0.16 23.0 715 388 Partitions Frm wall, r-11 cav ins, 1/2" gypsum board int fnsh, 2"x4" metal frm, 16" 254 0.14 34.5 1074 484 o.c. stud Windows htg cig htg clg 1 glazing, clr glz, mg no brk frm mat, 1/8" thk; NFRC rated (SHGC=0:70); n 15 1.25 / 125 18.8 / 18.8 583 676 foreground = green grass (0.23); 1.5 It overhang (5 It window ht, 2 ft sep.); 6.67 ft head ht 1 glazing, cir glz, mtl no brk fnn mat, 1/8" thk; NFRC rated (SHGC=0.70); n 42 1.25 / 1.25 52.5 / 52.5 1633 1893 foreground = green grass (0.23); 1.5 ft overhang (7 ft window ht, 2 It n 42 1.25 / 1.25 52.5 / 52.5 1633 1893 sep.); 6.67 ft head ht a 27 1.25 / 1.25 33.5 / 33.5 1043 1868 e 55 1.25 / 1.25 68.5 / 68.5 2132 3816 e 28 1.25 / 1.25 35.0 / 35.0 1089 1949 all 194 1.25 1 1.25 242 / .242 7529 11419 Doors Door, wd sc type n 21 0.33 6.9 216 177 n 21 0.33 6.9 216 174 all 42 0.33 13.9 431 351 Ceilings Attic ceiling, membrane roof mat, r-20 roof ins, suspended, acoustical 1084 0.16 172 5347 12355 int fnsh, dead air pinm Floors Bg Boor, light dry soil, on grade depth, file Br fnsh 84 0.60 50.2 1561 0 2015-Mar-31 13:39:02 wrlghtSoft' Right -Suite® Universal 201515.0.14 RSU17939 Pagel ...rthy Arch110999 South Ocean Blvd Oyster Bar mp Cale= RTS Front Door faces: E 2015-Mar-31 13:39:02 wri9htSGft' RlghtSuile®Unlversal201515.0.14RSU17939 Paget ...rthy Arch\10999 South Ocean Blvd Oyster Bar.rup Cale= RTS Front Door (aces: E Component Constructions Job: Date: Mar3l,2015 RTU 1 By: P oCalcs, LLC. ProCalcs - "Together we'll find the missing piece" 4273 BE Cove Lake Cir. R203, Stuart, FL 34997 Phone: 772-8825700 Email: PioCalm@gmail.com Web: vxlw.ProCakcs.Net License: CAC1815254 Maidoect intormation For: Magic Oyster Bar 10999 South Ocean Blvd., Jensen Beach, FL Design Conditions Htg Clg Htg Clg Outside db (7) 39 92 Inside db (OF) 70 75 Outside RH (%) 80 54 Inside RH (%) 38 50 Outside wb CF) 36 78 Inside wb (°F) 55 63 Dailyrange (OF) - 16 Design TD (OF) 31 17 Moisture diff. (gr/lb) 26.9 56.7 Construction descriptions Or Area U-value UA Loss Gain M (atuhla'--T) SWMF) (BWh) (BWh) Walls 8" thk Blk wall, stucco ext, , R-4.2 Foil, 5/8" gypsum board int fnsh e - 85 0.12 10.6 328 398 w 281 0.12 35.0 1090 373 all 365 0.12 45.6 1418 771 Partitions (none) Windows htg cig htg cig 1 glazing, cir giz, mill no brk frtn mat, 1/8" thk; NFRC rated (SHGC=0.70);a 21 1.25 / 1.25 26.3 / 26.3 816 2007 foreground = green grass (0.23); 1.5 ft overhang (7 ft window ht, 2 ft e 28 1.25 / 1.25 35.0 / 35.6 1089 2675 sep.); 6.67 It head ht a 168 1.25 / 1.25 210 / 210 6531 16052 all 217 1.25 / 1.25 271 / 271 8436 20734 Doors Door, wd so type w 21 0.33 6.9 216 123 Ceilings Flat ceiling, membrane roof mat, trill deck, r-10 deck ins, suspended, 1474 0.06 90.9 2827 4969 acoustical int fnsh, dead air pinm Floors Bg floor, light dry soil, on grade depth, tile fir fish 67 0.60 40.2 1250 0 2015-Mar-31 13:39:02 Wrightsoft' Right-Sutte® Universal 201515.0.14 RSU17939 Page ...My Nch110999 South Ocean BNtl Oyster Bar.mp Cakc = RTS Front Doorfaces: E RightSuite® Universal 2016 Short Form Date: Mar 37, 20,5 RTU 1 By: ProCales, LLc. ProCalcs - "Together we'll find the missing piece" 4273 SE Cove Lake Ch. R203, Stuart, FL 34997 Phone: 772-882-5700 Emafl: ProCalcs@gmail.wrn Web: w .ProCalcs.Nel License: CAC1815254 For: Magic Oyster Bar 10999 South Ocean Blvd., Jensen Beach, FL Htg Clg Htg Clg Outside db (OF) 39 92 Inside db (OF) 70 75 Outside RH N - 54 Inside RH N - 50 Outside wb (OF) - 78 Inside wb (OF) - 63 Daily range (OF) - 16 Design TD (OF) 31 17 Moisture diff. (gr/lb) - 57 Heating Equipment Cooling Equipment Make Make Trane Model Model THCO92F Type Else strip Type Pkg AC Efficiency 100 EFF COP / EER / SEER 12.6 Heating Input 9.0 kW Sensible Cooling 72.1 MBtuh Heating Output 30.7 MBtuh Latent Cooling 16.9 MBtuh Humidifier 21.2 gpd Total Cooling 89.0 MBtuh Leaving Air Temp 78.7 OF Leaving Air Temp 55.0 OF Actual Heating Fan 3210 cfm Actual Cooling Fan 3210 cfm Equipment Location RTU 1 System Type PEAKCV Fan Motor Heat Type PACKAGE Fan & Motor Combined Efficiency 0 % Static. Pressure Across Fan 0 in H2O NAME Area I Heat Sensible Latent Htg I Clg Time fta Loss Gain Gain cfm cfm Mens 87 1075 1604 484 125 106 Jul 1600 LDT Women 97 1254 1812 538 148 121 Jul 1600 LDT Dining 777 21670 28947 12209 1989 20711 Jul 1600 LDT Kitchen 513 24292 20685 16135 9491 9121 Jul 1600 LDT RTU 1 I 1474 I 48290 I 53048 I 29366 I 32101 32101 Jul 1600 LDT 2015-Mor--31 13:39:02 wrightSOft' RightSUBe® Universal 201515.0.14 RSU17939 Page 1 ...dhyAMh110999 South Ocean Blvd Oyster Bar.rup Calc=RTS Front Doorfaces: E Right -Suite® Universal 2015 Short Form Job. Date: Mar31,2016 RTU 2 By: ProCaIrsOLLC. ProCalcs - "Together we'll find the missing piece" 4273 BE Cove Lake Cir. A203, Stuart, FL 34997 Phone: 772-8825700 Email: ProCalcs@gmail.com Web: v nv.ProCalcs.Net License: CAC1815254 Froject Intormation For: Magic Oyster Bar 10999 South Ocean Blvd., Jensen Beach, FL Htg Clg Htg Clg Outside db (OF) 39 92 Inside db (OF) 70 75 Outside RH N - 54 Inside RH N - 50 Outside wb (OF) - 78 Inside wb (OF) - 63 Daily range (OF) - 16 Design TD (OF) 31 17 Moisture diff. (gr/lb) - 57 Heating Equipment Cooling Equipment Make Make Trane Model Model TCH092F Type Elec strip Type Pkg AC Efficiency 100 EFF COP / EER / SEER 12.6 Heating Input 9.0 kW Sensible Cooling 62.3 MBtuh Heating Output 30.7 MBtuh Latent Cooling 26.7 MBtuh Humidifier 14.9 gpd Total Cooling 89.0 MBtuh Leaving Air Temp 79.0 OF Leaving Air Temp 55.0 OF Actual Heating Fan 3110 cfm Actual Cooling Fan 3110 cfm Equipment Location RTU 2 System Type PEAKCV Fan Motor Heat Type PACKAGE Fan & Motor Combined Efficiency 0 % Static Pressure Across Fan 0 in H2O NAME Area I Heat Sensible Latent Htg Clg I Time ft Loss Gain Gain cfm Cfm Bar Area 880 30815 1 37930 1 13431 1 21001 18251 Jul 1600 LDT Wait Station 180 9354 22446 6340 567 11401 Jul 1600 LDT Office 24 6068 1 2850 4372 1 443 1451 Jul 1600 LDT RTU 2 1084 1 46236 1 63226 1 24143 1 31101 31101 Jul 1600 LDT 2015-Mar-31 13:39:02 wrightsoft' R19htSutle® Universal 201515.0.14 RSU17939 Paget ...rthy Arrh110999 South Ocean Blvd Oyster Bar.rup Calc = RTS Front Door laces: E Right -Suite@ Universal 2015 Load Summary Job: RTU 1 Date: Mar 31, 2015 By: ProCalcs, LLC. ProCalcs - "Together we'll find the missing piece" 4273 SE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 712-8825700 Email: PtoCalw@gmal.wnn Web: vmv.ProCelcs.Net License: CAC1815254 For: Magic Oyster Bar 10999 South Ocean Blvd., Jensen Beach, FL Zone:—'RTU 1 COOLING_LOAD 1. DESIGN CONDITIONS at Jul 1600 LDT Peak load at Jul 1200 LDT Inside: 75 OF Outside: 92 OF TD: 17 OF RH: 54 % MoistDiff: 56.7 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 10189 3. TRANSMISSION GAINS Sensible 11938 Walls: 1259 - - Glass: 3932 - - Doors: 303 - - Partitions: 0 - - Floors: 0 - - Ceilings: 6444 - - 4. INTERNAL HEAT GAIN Sensible Latent 17888 4576 Occupants: 3804 4206 - - Lights: 6123 - Motors: 0 - Appliances: 7961 370 - - 5. INFILTRATION: Outside air cfm: 50 918 1927 6. SUBTOTAL: Space load Sensible Latent 40933 6503 Envelope 40933 6503 - - Less external 0 - Redistribution 0 0 - 7. SUPPLY DUCT 1228 - S. SUBTOTAL: Space load + supply duct 42161 - Actual cfm: 3210 at supply TD: 20 - - 9. VENTILATION: Make-up air cfm: 593 10887 22864 10. RETURN AIR LOAD: Lighting + plenum (net) 0 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 53048 29366 HEATING LOAD,_,_. ^� 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 39 OF TD: 31 OF 14. TRANSMISSION LOSSES 14147 Walls: 1418 - Glass: 8436 - Doors: 216 - Partitions: 0 - Floors: 1250 - Ceilings: 2827 - 15. INFILTRATION: Outside air cfm: 156 5342 16. SUBTOTAL: Spaceload 19489 Envelope 19489 - Less external 0 - Less transfer 0 - Redistribution 0 - 17. SUPPLY DUCT: 585 18. VENTILATION: Make-up air cfm: 593 20275 19. HUMIDIFICATION 7941 Piping 0 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 48290 wrl htsoft' 201SMar-3113:39:02 9 RIghtSule® Universal 201515.0.14 RSU17939 Page 1 ...rthy ArOM10999 South Ocean Blvd Oyster Bar.rup Cato -RTS Front Door faces: E Right-Suite(g) Universal 2016 Load Summary Job: RTU 2 Date: Mar 31, 2015 By: ProCalcs, LLC. ProCalcs - "Together we'll find the missing piece" 4273 SE Cove Lake Cir. #203, Stuart, FL 34997 Phone: 772-8825700 Email: PmCalcs@gmeil.cortl Web: x .PmCelos.Net License: CAC1815254 •ject Intormation For: Magic Oyster Bar 10999 South Ocean Blvd., Jensen Beach, FL Zone'.: RTU 2 - COOLING:COAD 1. DESIGN CONDITIONS at Jul 1600 LDT Peak load at Jul 1500 LDT Inside: 75 OF Outside: 92 OF TD: 17 OF RH: 54 % MoistDiff: 56.7 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 7810 3. TRANSMISSION GAINS Sensible 18548 Walls: 2284 - - Glass: 3778 - - Doors: 362 - - Partitions: 0 - - Floors: 0 - - Ceilings: 12124 - - 4. INTERNAL HEAT GAIN Sensible Latent 26232 5357 Occupants: 3411 3773 - - Lights: 7549 - Motors: 0 - Appliances: 15272 1584 - - 5. INFILTRATION: Outside air cfm: 205 3768 7913 6. SUBTOTAL: Space load Sensible Latent 56358 13270 Envelope 56358 13270 - - Less external 0 - Redist6bution 0 0 - 7. SUPPLY DUCT 1691 S. SUBTOTAL: Space load + supply duct 58049 Actual cfm: 3110 at supply TD: 20 - - 9. VENTILATION: Make-up air cfm: 282 5177 10873 10. RETURN AIR LOAD: Lighting + plenum (net) 0 - 11. RETURN DUCT p 12. TOTAL LOADS ON EQUIPMENT 63226 24143 ,'- 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 39 OF TD: 31 OF 14. TRANSMISSION LOSSES 18708 Walls: 3257 - Glass: 8112 - Doors: 431 - Partitions: 0 - Floors: 1561 - Ceilings: 5347 - 15. INFILTRATION: Outside air cfm: 334 11405 16. SUBTOTAL: Space load 30113 Envelope 30113 - Less external 0 - Less transfer 0 - Redistribution 0 - 17. SUPPLY DUCT: 903 18. VENTILATION: Make-up air cfm: 282 9642 19. HUMIDIFICATION 5578 Piping 0 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 46236 fi IIYSOfC' 2015-Mar-3113:39:02 W g Right -Su Be® Universal 201615.0.14 RSU17939 Paget ...rthy ArU110999 South Ocean Blvd Oyster Bar.rup Calc=RTS Fmnt Doorfaces: E ProCalcs DISCLAIMER The following pages summarize the heat gain and heat loss of the building using the ACCA Manual J8 calculation procedure. The calculations are based on the information given to ProCalcs in the form of drawings, sketches, and interviews. In certain cases, ProCalcs may make assumptions about design conditions that may or may not be accurate for the location of concern. It is the responsibility of the installing HVAC contractor to verify the design conditions before equipment purchase and installation. Any load calculations provided in the following pages are based upon information provided by the party submitting a particular project to ProCalcs. ProCalcs has not and does not independently verify that the data provided to ProCalcs is correct or complete, and any calculations made by ProCalcs are based upon the information provided by third parties. ProCalcs makes no claim that the information given to us is correct or complete. ProCalcs utilizes WrightSoft Residential 15.0 which is an ACCA Certified and ASHRAE recommended computer program to determine the heating and cooling loads presented in this report, and is therefore very accurate. If the information given to ProCalcs is accurate, and the building is built as per the plans submitted, then the load calculations presented in this report can be assumed to be accurate. A licensed mechanical contractor may use these calculations as a starting point in system sizing and selection. ProCalcs does not provide architectural or engineering plans or diagrams for the public or for use by contractors or construction companies as final "construction documents". ProCalcs works with architectural and engineering firms and with contractors in connection with their designs of heating and air conditioning systems. If the HVAC duct layout installed on -site DOES NOT match the Manual D duct design prepared by ProCalcs, then ProCalcs cannot and will not guarantee the performance of any altered duct design. Final HVAC sizing and selection should be done by a licensed HVAC contractor. Many factors beyond the scope of this report must be considered prior to final system selection and design, such as: exact equipment availability and selections, system controls and location of controls, system air distribution and cycling, Uniform Building Code requirements, Uniform Mechanical Code requirements, and many other standard design conventions as listed by the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE). ProCalcs therefore assumes no liability for final equipment selection or final system design. Various modifications to the information provided toProCalcs may have occurred after this Design Support information was prepared, which would require that this Design Support information be modified in order to be accurate. After reviewing ProCalcs report, and prior to any system purchase or installation, please inform ProCalcs in writing of any changes which may alter the assumptions and calculations contained in this report. "Florida Energy, Efficiency Code For Building Construction EnergyGauge Summit®Fla/Com 2010, Effective Date: -March 15, 2012 — Form 506-2010 Total Building Performance Method for Commercial Buildings PROJECT SUMMARY Short Dese: Magic Oyster Owner: Magic Oyster Addressl: 10999 S. Ocean Blvd Address2: Description: Magic Oyster City: State: Zip: Type: Dining: Bar Lounge/Leisure Class: Jurisdiction: ST LUCIE COUNTY, ST LUCIE COUNTY, FL (661000) Conditioned Area: 2582 SF Conditioned & UnConditioned Area: No of Stories: I Area entered from Plans Permit No: 0 Max Tonnage If different, write in: Jensen Beach FL 0 Renovation to existing 2582 SF 2582 SF 7.4 EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Pagel of 8 Component Gross Energy Cost (in LIGHTING CONTROLS EXTERNAL LIGHTING HVAC SYSTEM PLANT WATER HEATING SYSTEMS PIPING SYSTEMS Met all required compliance from Check List? Design Criteria Result 2,481.0 2,492.0 PASSED PASSES PASSES PASSES No Entry PASSES No Entry Yes/No/NA IMPORTANT MESSAGE Info 5009 — — — An input report of this design building must be submitted along with this EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 2 of 8 CERTIFICATIONS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code; �•�• ThomasV Platania Prepared By: ProCalcs, LLC. Building Official: Date: 03/31/2015 Date: I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: Date: If Required by Florida law, I hereby certify (') that the system design is in compliance with the Florida Energy Efficiency Code Architect: Reg No: Electrical Designer: Reg No: Lighting Designer: Reg No: Mechanical Designer: Reg No: Plumbing Designer: Reg No: (') Signature is required where Florida Law requires design to be performed by registered design professionals. EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 3 of 8 Project: Magic Oyster Title: Magic Oyster Type: Dining: Bar Lounge/Leisure (WEAFile: FL_ST_LUCIE_CO_INTLAW) Building End Uses 1) Proposed 2) Baseline Total 155.10 195.40 $2,481 $3,115 ELECTRICITY(MBtulkWhl$) 155.10 195.40 45444 57266 $2,481 $3,115 AREA LIGHTS 16.80 33.40 4918 9794 $269 $533 MISC EQUIPMT 23.00 23.00 6746 6746 $368 S367 PUMPS & MISC 0.20 0.10 48 44 $3 $2 SPACE COOL 70.40 82.30 20626 24105 $1,126 $1,311 SPACE HEAT 9.80 8.20 2871 2403 $157 $131 VENT FANS 34.90 48.40 10235 14174 $559 $771 Credits Applied: None PASSES Passing Criteria = 2492 Design (including any credits) = 2481 Passing requires Proposed Building cost to be at most 80% of Baseline cost. This Proposed Building is at 79.6% EnergyGauge Summit® FlalCom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 4 of 8 Project: Magic Oyster Title: Magic Oyster Type: Dining: Bar Lounge/Leisure (WEAFile: FL_ST LUCIE CO INTL.tm3) 'External Lighting Compliance Description Category Tradable? Allowance Area or Length ELPA CLP (W/Unit) or No. of Units (W) (W) (Sgft or ft) Ext Light 1 Uncovered Parking Areas — Yes 0.15 180 Parking lots and Drives Tradable Surfaces: 180 (W) Allowance for Tradable: 750 (W) PASSES All External Lighting: 180 (W) Complicance check includes a excess/Base allowance of 750.00(W) Project: Magic Oyster Title: Magic Oyster Type: Dining: Bar Lounge/Leisure (WEAFile: FL ST LUCIE CO E'4n.tm3) Lighting Controls Compliance Acronym Ashrae Description Area Design Min Compli- ID (sq.ft) CP CP ance Dining 8 Food Service - Leisure Dining 777 1 1 PASSES Kitchen 7 Food Service - Kitchen 513 1 1 PASSES Mens Room 6 Toilet and Washroom 87 1 1 PASSES Women Room 6 Toilet and Washroom 97 1 1 PASSES Bar Area 9 Food Service - Bar/Lounge 880 1 1 PASSES Wait Station 9 Food Service - Bar/Lounge 228 1 1 PASSES PASSES EnergyGauge Summit& FWCom-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 5 of 8 Project: Magic Oyster Title: Magic Oyster Type: Dining: Bar Lounge/Leisure (WEAFile: FL_ST_LUCIE_CO_1NTL.tm3) System Report Compliance RTUI System 1 Constant Volume Packaged No. of Units System 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Conditioners Air Cooled 89000 12.60 11.20 12.60 11.40 PASSES 65000 to I35000 Btu/h Cooling Capacity Heating System Electric Furnace 30709 1.00 1.00 PASSES Au Handling Air Handler (Supply) - 3210 0.25 0.82 PASSES System -Supply Constant Volume Air Handling Air Handler (Return) - 3210 0.25 0.82 PASSES System - Return Constant Volume RTU2 RTU 2 Constant Volume Packaged No. of Units System 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Conditioners Air Cooled 89000 12.60 11.20 12.60 11.40 PASSES 65000 to 135000 Btu/h Cooling Capacity Heating System Electric Furnace 30709 1.00 1.00 PASSES Air Handling Air Handler (Supply) - 3110 0.25 0.82 PASSES System -Supply Constant Volume Air Handling Air Handler (Return) - 3110 0.25 0.82 PASSES System -Return Constant Volume PASSES Plant Compliance Description Installed Size Design Min Design No Eff Eff IPLV Min Category Comp IPLV liance None EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 6 of 8 Project: Magic Oyster Title: Magic Oyster Type: Dining: Bar Lounge/Leisure (WEA File: FL_ST_LUCIE_CO_INTL.tm3) Water Heater Compliance Description Type Category Design Min Eff Eff Design Max Comp Loss Loss fiance Water Heater 1 Electric water heater <= 12 [kW] 0.93 0.92 PASSES PASSES Piping System Compliance Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance [inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in] [F] SF.FJ Non=:=j EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 7 of 8 .t: Magic Oyster Magic Oyster Dining: Bar Lounge/Leisure ,File: FL_ST_LUCIE_CO_INTL.tm3) Other Required Compliance Category Section Requirement (write N/A in box if not applicable) Check Report 506.4.2 Input Report Print -Out from EnergyGauge FlaCom attached Operations Manual 303.3.1, Operations manual provided to owner 503.2.9.3, 505.7A.2 Windows & Doors 502.3.2 Glazed swinging entrance & revolving doors: max. 1.0 cfm/ft2, all other products: 0.3 cfm/ft2 Joints/Cracks 502.3.3 To be caulked, gasketed, weather-stripped or otherwise sealed El Dropped Ceiling Cavity 502.3 Vented: seal & insulated ceiling. Unvented seal & insulate roof & El side walls HVAC Efficiency 503.2.3 Minimum efficiencies: Tables 503.2.3(1)-(8) HVAC Controls 503.2.4 Zone controls prevent reheat (exceptions); separate thermostatic control per zone; Ventilation 503.2.5 Outdoor air supply & exhaust ducts shall have dampers that automatically shut when systems or spaces served are not in use. Exhaust air energy recovery required for cooling systems (Exceptions). ADS 503.2.7.5 Duct sizing and Design have been performed HVAC Ducts 503.2.7 Air ducts, fittings, mechanical equipment & plenum chambers shall be mechanically attached, sealed, insulated & installed per Table 503.2.7.2. Fan power limitations. Balancing 503.2.9.1 HVAC distribution system(s) tested & balanced. Report in construction documents. Piping Insulation 503.2.8 HAC and service hot water. In accordance with Table 503.2.8. Water Heaters 504 Performance requirements in accordance with Table 504.2. Heat ❑ trap required. Swimming Pools 504.7 Vapor -retardant or liquid cover or other means proven to reduce heat loss on heated pools; Time switch (exceptions); readily accessible on/off switch. Motors 505.7.5 Motor efficiency criteria have been met Lighting Controls 505.2, 502.3 Automatic control required for interior lighting in buildings >5,000 s.f.; Space control; Exterior photo sensor; Tandom wiring with 1 or 3 linear fluorescent lamps>30W EnergyGauge SummitO Fla1Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012 3/31/2015 Page 8 of 8