HomeMy WebLinkAboutENERGY EFFICIENCY CODEF1ori&i,Energy Efficiency Code For Building Construction
EnergyGauge Summit@) Fla/Com-2010, Effective Date: March,l5 2012 '=- Form 506-2010
• Total Building Performance Method for Commercial Buildings
PROJECT SUMMARY
Short Desc:
SLC FAIR SCANNED Description:
SMALL ANIMAL CTR
Owner:
ST. LUCIE COUNTY FAIR BY
Addressl:
OKEECHOBEE/MIDWAYRD LUCIe CQUf11]/ City:
ST. LUCIE CO.
Addmss2:
State:
FL
Zip:
0
Type:
Workshop Class:
New Finished building
Jurisdiction:
ST LUCIE COUNTY, ST LUCIE COUNTY, FL (661000)
Conditioned Area:
850 SF Conditioned & UnConditioned Area:
850 SF
No of Stories:
1 Area entered from Plans
850 SF
Permit No:
0 Max Tonnage
3
If different, write in:
RECEPF-D
APR 2 9 2015
Public Works
St. Lucie County, FL
L"' CO
F 1: ry
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
4/27/2015 Page I of
Component
Gross Energy Cost (in $)
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design Criteria Result
1,324.0 1,444.0 PASSED
PASSES
None Entered
PASSES
None Entered
None Entered
None Entered
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
4/27/2015 Page 2 of 7
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: PAUL WELCH, P.E. Building Official:
Date: APR 312W5 Date:
I certify that this building is in compliance with the FLorida EnergyEfficiencyCode
Owner Agent: ST. LUCIE CO. FAIR kA4 Date:
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida
Energy Efficiency Code
Architect:
Reg No:
Electrical Designer: PAUL WELCK P.E. Reg No: 29945
Lighting Designer: PAUL WELCH, P.E. Reg No: 29945
Mechanical Designer: PAUL WELCH, P.E. Reg No: 29945
Plumbing Designer: PAUL WELCH, P.E. Reg No: 29945
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals.
EnergyGauge Summit0 FlalCom-2010. Section 506.4 CompliantSoftware. Effective Date: March 15, 2012
4/27/2015 Page 3 of 7
Project: SLC FArR
Title: SMALLANIMAL CTR
Type: Workshop
(WEA File: FL_ST_LUCIE_CO_D T ,.tm3)
Building End Uses
1) Proposed
2) Baseline
Total
82.30
112.30
$1,324
$1,805
ELECMCrrY(MBtulkWh($)
82.30
112.30
24125
32880
$1,324
$1,805
AREA LIGHTS
13.40
16.90
3920
4946
$215
S272
MISC EQUIPMT
4.30
4.30
1245
1245
$68
$68
PUMPS & MISC
0.10
0.10
26
21
$1
$1
SPACE COOL
37.30
53.10
10941
15559
S601
$854
SPACE HEAT
5.30
5.70
1562
1682
$86
S92
VENT FANS
21.90
32.20
6431
9427
$353
$518
Credits Applied: None
PASSES
Passing Criteria =1444
Design (including any credits) =1324
Passing requires Proposed Building cost to be at most 80% of
Baseline cost. This Proposed Building is at 73.4%
EnergyGauge Summit) Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
4/27/2015 Page 4 of 7
External Lighting Compliance
Description Category
Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: SLC FAIR
Title: SMALLANIMALCTR
Type: Workshop
(WEA File: FL_ST_LUCIE_CO_INTL.tm3)
Lighting Controls Compliance
Acronym Ashrae Description
Area Design Min Compli-
ED
(sq.ft) CP CP once
SLC FAIR 31,001 Workshop
850 4 1 PASSES
PASSES
Project: SLC FAIR
Title: SMALLANIMALCTR
Type: Workshop
(WEA File: FL_ST_LUCIE_CO INTL.tm3)
System Report Compliance
SLC FAIR System 1
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr I
Component Category
Capacity Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Conditioners Air Cooled
13.00 12.23 1.00 PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System Electric Furnace
1.00 1.00 PASSES
Air Handling System Air Handler (Supply) -
0.80 0.82 PASSES
-Supply Constant Volume
PASSES
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
4/27/2015 Page 5 of 7
Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV Hance
None
Water Heater Compliance
Description Type Category Design Min Design Max Comp
Eff Eff Loss Loss liance
None
Piping System Compliance
Category Pipe Din Is Operating Ins Cond Ins Req Ins
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.Fj
None
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
4/27/2015 Page 6 of 7
a: SLC FAIR
SMALLANIMALCTR
Workshop
File: FL ST_LUC1E_CO_INTL.tm3)
Other Required Compliance
Category Section
Requirement (write N/A in box if not applicable)
Check
Report 506.4.2
Input Report Print -Out from EnergyGauge FlaCom attached
Operations Manual 303.3.1,
Operations manual provided to owner
503.2.9.3,
505.7.4.2
Windows & Doors 502.3.2
Glazed swinging entrance & revolving doors: max. 1.0 cfln/ft2; all
other products: 0.3 cfin/ft'
Joints/Cracks 502.3.3
To be caulked, gasketed, weather-stripped or otherwise sealed
❑
Dropped Ceiling Cavity 502.3
Vented: seal & insulated ceiling. Unvented seal & insulate roof &
❑
side walls
HVAC Efficiency 503.2.3
Minimum efficiencies: Tables 503.2.3(1)-(8)
❑
HVAC Controls 503.2.4
Zone controls prevent reheat (exceptions); separate thermostatic
control per zone;
Ventilation 503.2.5
Outdoor air supply & exhaust ducts shall have dampers that
automatically shut when systems or spaces served are not in use.
Exhaust air energy recovery required for cooling systems
(Exceptions).
ADS 503.2.7.5
Duct sizing and Design have been performed
HVAC Ducts 503.2.7
Air ducts, fittings, mechanical equipment & plenum chambers shall
El
be mechanically attached, sealed, insulated & installed per Table
503.2.7.2. Fan power limitations.
Balancing 503.2.9.1
HVAC distribution system(s) tested & balanced. Report in
construction documents.
Piping Insulation 503.2.8
HAC and service hot water. In accordance with Table 503.2.8.
Water Heaters 504
Performance requirements in accordance with Table 504.2. Heat
trap required.
Swimming Pools 504.7
Vapor -retardant or liquid cover or other means proven to reduce
heat loss on heated pools; Time switch (exceptions); readily
accessible on/off switch.
Motors 505.7.5
Motor efficiency criteria have been met
Lighting Controls 505.2, 502.3
Automatic control required for interior lighting in buildings >5,000
s.f.; Space control; Exterior photo sensor; Tandom wiring with 1 or
3 linear fluorescent lamps>30W
4/27/2015
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
Page 7 of
EnergyGauge Summit® v4.10
INPUT DATA REPOR
Proiect Information
Project Name: SLC FAIR
Project Title: SMALL ANIMAL CTR
Address: OKEECHOBEE / MIDWAY RD
State: FL
Zip: 0
Owner: ST. LUCIE COUNTY FAIR
Orientation: North
Building Type: Workshop
Building Classification: New Finished building
No.of Stories: 1
GrossArea: 850 SF
Zones
No Acronym Description Type
Area
[s11
Multiplier
Tbtal Area
Isf]
I SLC FAIR Zone I CONDITIONED
850.0
1
850.0 ❑
Spaces
No Acronym Description Type Depth
[ft]
Width Height Multi
[ft] [It] plier
Total Area
[st1
Total Volume
[cq
4/27/2015 EnergyGauge Summit® v4.10 1
bi Zone: SLC FAIR
1 SLC FAIR Zo0Sp1
Workshop
50.00
17.00
10.00
1
850.0
8500.0
❑
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: SLC FAIR
In Space: SLC FAIR
1 Recessed
Fluorescent - General Lighting
10
128
1280
Manual
On/Off
4
❑
No vent
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance
Heat
Dens. R Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf. F]
Capacity
Vb/cf] [h.sEF/Btu]
[Btu/sEF]
In Zone: SLC FAHt
1 CBS
5/8" stucco 34.00
10.00 1
340.0
North
0.2067
5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
2 CBS
5/8" stucco 34.00
10.00 1
340.0
North
0.2067
5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
3 CBS
5 8' stucco 50.00
10.00 1
500.0
North
0.2067
5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
4 CBS
in. stucco, 50.00
10.00 1
500.0
North
0.0838
11.224
50.24 11.9
❑
2"styro,8"CMU,lx2
x24"oc, airspace, 0.5"
gyp
4/27/2015 EnergyGauge Summit® v4.10
Windows
No Description Type
Shaded U SHGC
Vis.Tra
W H (Effec) Multi
Total Area
[Btu/hr sf F1
[ft] [ft] plier
[sf1
In Zone: SLC FAIR
In Wall: E WALL
I SHW User Defined
No 1.2500 0.82
0.76
8.00 4.00 1
32.0
❑
In Wall: S WALL
1 SHW User Defined
No 1.2500 0.82
0.76
8.00 4.00 1
32.0
Doors
No Description Type
Shaded? Width H (Effec) Multi
Area
Cond. Dens. Heat Cap.
R-Value
[ft] [ft]
plier
[sf1
[Btu/hr. sE F1 [Ib/cf1 [Btu/sL F1
[h.sEFBtu]
In Zone:
In Wall:
Roofs
No Description Type
Width H(Effec) Multi
Area
Tilt
Cond. Heat Cap
Dens.
R-Value
[it] [it] plier
[sf1
[deg]
[Btu/hr. Sf. F] [Btu/sE 11
[Ib/cf1
[h.sLF/Btu]
in Zone: SLC FAIR
1 MYL Mtl Bldg Roof/R-19
34.00 50.00 1
1700.0
0.00 0.0492 1.34
9.49
20.3
❑
Batt
Skylights
No Description Type
U SHGC Vis.Trans
W
H (Effec) Multiplier
Area
Total Area
[Bta/hr sf F]
Ift]
[ft]
[S11
]SA
4/27/2015 EnergyGauge Summit® v4.10
In Zone:
In Roof:
Floors
No Description Type
Width
[ft]
H (Effec) Multi
[ft] plier
Area Cond. Heat Cap.
Is!] [Btu/hr. sE F] [Btu/sE F]
Dens. R-Value
[lb/cf] [h.sf.F/Btu]
In Zone: SLC FAIR
1 CONC I ft. soil, concrete
floor, carpet and
rubber pad
34.00
50.00 1
1700.0 0.2681 34.00
113.33 3.73
❑
Systems
SLC FAIR System 1
Constant Volume Air Cooled Split
System < 65000 Btu/hr
No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
36000.00
44000.00
1200.00
13.00 1.00
1.00
0.80
❑
❑
❑
Plant
Equipment Category
Size
Inst.No Ef. .
IPLV
Water Heaters
W-Heater Description CapacitlCap.Ifnit
I/P Rt.
Efficiency
Loss
4/27/2015 EnergyGauge Summit® v4.10
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units
Luminaires Luminaire [sVft/No]
Control Type Wattage
[W]
El
Piping
No Type Operating Insulation
Temperature Conductivity
[F] [ Btu-iu/h.sf.Fl
Nomonal pipe
Diameter
[in]
Insulation Is Runout?
Thickness
[in]
El
Fenestration Used
Name Glass Type No. of Glass SHGC VET
Panes Conductance
[Btu/b.sf.F]
ASHULSgICIrAII User Defined 1 1.2500 0.8200 0.7600 ❑
Frm
Materials Used
Mat No
Acronym
Description
Only R-Value RValue Thickness
Conductivity
Density
SpecificHeat
Used [h.sf.FBtu] [ft]
[Btu/h.ft.F]
[lb/cf]
[Btu4b.F]
Mat1187
No
BOARD,1/2IN
178
Mat1178
CARPET W/RUBBER PAD
Yes 1.2300
❑
265
Matl265
Soil, I ft
No 2.0000 1.0000
0.5000
100.00
0.2000
❑
48
Matl48
6 in. Heavyweight concrete
No 0.5000 0.5000
1.0000
140.00
0.2000
❑
4/27/2015 EnergyGauge Summit@ v4.10 5
267
Mat1267
0.75" stucco No
0.1563
0.0625
0.4000
16.00
0.2000
❑
215
Mat1215
POLYSTYRENE, EXP., No
8.3350
0.1667
A.0200
1.80
0.2900
❑
2IN,
105
Matll05
CONC BLK HW, 81N, No
1.1002
0.6667
0.6060
69.00
0.2000
❑
HOLLOW
256
Mat1256
WOOD, SOFT, 1-1/21N No
1.8939
0.1250
0.0660
32.00
0.3300
❑
268
Mat1268
0.625" stucco No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Mat142
8 in. Lightweight concrete No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
Matl269
.75" ISO BTWN24" oc No
2.2321
0.0625
0.0280
4.19
0.3000
❑
23
Matl23
6 in. Insulation No
20.0000
0.5000
0.0250
5.70
0.2000
❑
94
Mat194
BUILT-UP ROOFING, 3/81N No
0.3366
0.0313
0.0930
70.00
0.3500
❑
Constructs Used
No
Name
Simple
Construct
Massless Conductance Heat Capacity
Construct [Btu/h.sCF] [Btu/sCF]
Density
[lb/cf]
RValue
[h.st:FBtu]
1010
0.75 in. stucco,
No
No
0.08
11.22
50.24
11.9
❑
2"styro,8"CMU,lx2x24"oc
airspace,0.5"gyp
Layer
Material Material
Thickness
Framing
No.
IN
Factor
1
267 0.75" stucco
0.0625
0.000
❑
2
187 GYP ORPLASBOARD,1/2IN
0.0417
0.000
❑
3
215 POLYSTYRENE, EXP., 2IN,
0.1667
0.000
❑
4
105 CONC BLK HW, SIN, HOLLOW
0.6667
0.000
❑
5
256 WOOD, SOFT, 1-1/21N
0.1250
0.000
❑
4/27/2015 EnergyGauge Summit® A.10
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sEF]
[lb/cf]
[h.sEFBtu]
1011
518" stucco /8"CMU/3/4"ISO No
No 0.21
5.73
34.65
4.8
❑
BTWN24"oc/.5"
Gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
268
0.625" stucco
0.0521
0.000
❑
2
42
8 in. Lightweight concrete block
0.6670
0.000
❑
3
269
.75" ISO BTWN24" oc
0.0625
0.000
❑
4
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sEF]
[Btu/sal
[lb/cf]
[h.sl1F/Btu]
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sEF]
[Btu/sf.F]
[Ib/cf]
[h.sEFBtu]
1057
1 ft. soil, concrete floor, carpet and rubber pad No
No 0.27
34.00
113.33
3.7
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
4/27/2015 EnergyGauge Summit® v4.10