Field and Laboratory Report Transmittal Sheet
Client: Richard K . Davis
PO Box 186
Fort Pierce, Florida 34954
LOCATIONS:
• Atlaam
• Daytona Beach
• Fort Myers
• Fort Pierce
• Gainesville
• Jacksonville
• Kissimmee
Leesburg
• Miami
Ocala
Orlando (Headquarters)
• Palm Coast
• Panama City
• Pensacola
• Rockledge
SarOSom
Tampa
IV
JUL Z 9 2015
Public Works
St. Lucie County, FL
Project: Small Animal Exhibition Hall — Permit No. SLC 1504-0389
15601 W. Midway Road, Fort Pierce, FL 34945
Port St. Lucie, Florida
As requested, a representative of Universal Engineering Sciences, Inc. (UES) was at the
referenced project to provide construction materials testing services.
The results of the observations and/or tests are summarized on the attached sheets. The
reports are numbered as follows: 42751 ARDI, 42671 DTI. We trust this information is
sufficient for your immediate needs. If you have any questions, please do not hesitate to
contact the undersigned.
Reviewed By:
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 549
^»� Richard E. Hoaglin,
j P.E.
t. 2015.07.2911:11:52
p
-04'00'
Richard E. Hoaglin, P.E.
STATE OF FLORIDA
Licensed Professional Engineer No. 48796
mriestrl rkdavis.com
820 Brevard Avenue, Rockledge, Florida 32955 (321) 638-0808 Fax (321) 638-0978
www.UniversalEngineering.com
UNIVC'RSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Construction Materials Testing • Threshold Inspection
Building Inspection •PIan Review • Building Code Administration
820 Brevard Avenue • Rockledge, FL • 32955
321.638.0808 Fax:321.638.0978
Activity Record
A Project No: 0310.1500279.0000
LIES Report No: 42751 ARD2 072315
On -Site Time (hrs):
1.50
Lab Time (hrs):
0.00
Travel Time (hrs):
1.25
Total Time (hrs):
2.75
Client: Richard K. Davis Inc.
P.O. Box 186
Fort Pierce, FL 34954
Project: Small Animal Exhibition Hall — Permit No. SLC 1504-0389
15601 W. Midway Road, Fort Pierce, FL 34945
Date of Activity: Thursday, July 23, 2015
Technician: Francois Philippe
As requested, a Universal Engineering Sciences Technician was present at the above referenced project
site for the purpose of earthwork testing for the slab on grade and footing pad.
While on site, the technician observed the general condition of the areas to be tested and performed 3
density test(s) for slab on grade. All test(s) were performed in accordance with the ASTM D-6938 Nuclear
Gauge Method and were found to meet the project compaction requirements of 98% of the maximum dry
density perASTM D1557.
While on site, the technician observed the general condition of the areas to be tested and performed 2
density test(s) for footing pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear
Gauge Method and were found to meet the project compaction requirements of 98% of the maximum dry
density perASTM D1557.
The Contractor was notified of the test results or a copy was left for their records.
This test(s) was performed without deviation from ASTM procedure.
This report shall not he reproduced, except in full, without the written approval of Universal Engineering Sciences.
U N 1 V. R S A L S Project No: 0310.1500279.0000
ENGINEERING SCIENCES UESReportNo: 42751-1DT072315
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Construction Materials Testing • Threshold Inspection
Building Inspection •Plan Review • Building Code Administration
820 Brevard Avenue
• Rockledge, FL • 32955
321.638.0808
Fax:321.638.0978
In -Place Density Test Report
Client:
Richard K. Davis Inc.
P.O. Box 186
Fort Pierce, FL 34954
Project:
Small Animal Exhibition Hall — Permit No. SLC 1504-0389
15601 W. Midway Road, Fort Pierce, FL 34945
Area Tested:
Slab on grade
Type of Test:
Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 07/23/2015
Lab: ASTM D1557
Technician:
Francois Philippe
Requirements: 98% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions only and
do not address the condition of the underlying soils below the tested depths.
Test
#
Location of Test
Range
(FT)
Depth
(IN)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comme
(3)
1
25' S 15' E NW comer slab
0 to -1
12.00
18445
114.3
11.4
99
A
2
50' E from W center
0 to -1
12.00
18445
114.6
8.9
99
A
3
15' N 40' W comer SE
0 to -1
12.00
18445
113.8
8.7
98
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Proctor
Maximum
Optimum
#
Dry
Moisture
Density
Content
18445
116.0
10.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
i
UNIVERSAL
NIVERSAL UES Project No: 0310.1500279.0000
ENGINEERING SCIENCES UESReportNo: 42751-2DT072315
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Construction Materials Testing • Threshold Inspection
Building Inspection • Plan Review • Building Code Administration
820 Brevard Avenue • Rockledge, FL • 32955
321.638.0808 Fax:321.638.0978
In -Place Density Test Report
Client: Richard K. Davis Inc.
P.O. Box 186
Fort Pierce, FL 34954
Project: Small Animal Exhibition Hall — Permit No. SLC 1504-0389
15601 W. Midway Road, Fort Pierce, FL 34945
Area Tested: footing pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 07/23/2015
Lab: ASTM D1557
Technician: Francois Philippe
Requirements: 98% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions only and
do not address the condition of the underlying soils below the tested depths.
Test
#
Location of Test
Range
(FT)
Depth
(IN)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
4
20'S 5 W NE corner footing pad
0 to -1
12.00
18445
114.7
12.6
99
A
5
7W 2'N SE corner footing pad
0 to -1
12.00
18445
113.8
13.7
98
A
(1) Ref. Datum: 0 = Bottom of Footing
(2)
Proctor
Maximum
Optimum
Dry
Moisture
#
Density
Content
18445
116.0
10.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.