HomeMy WebLinkAboutCERTIFIED TEST - BALANCE REPORT` SCANNED BY St. Lucie County *.150C/— aka 9 ACCURATE BALANCING & COMMISSIONING, INC 2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429 Robert(@tabfirm.com Expires 3/31/2016 CERTIFIED TEST; ADJUST; BALANCE REPORT Project: Speedway 8580 US Hwy 1 Port St Lucie, FL 34952 Engineer: Richard L Bowen & Associates 13000 Shaker Blvd Cleveland, OH 44120 Phone: 216-491-9300 Drawings dated 5/20/15 Bulletin 1 Contractor: Great Dane Petroleum 1330 S Andrews Avenue FRn Pompano Beach, Florida 33311 Phone: 954-931-0186 AUG 1 0p Technicians: Robert Shorr, Travis Shorr Test Date: 8/7/15 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST -ADJUST -BALANCE REPORT PROJECT SUMMARY DUCT SMOKE DETECTOR TESTING AND CERTIFICATION VERIFIES THE DIFFERENTIAL PRESSURE ACROSS THE DETECTOR PICK UP TUBES ONLY AND DOES NOT TEST ANY ELECTRICAL OR DETECTOR OPERATION. ,r Robert Shorr, NEBB Certified Profession! Date ACCURATE BALANCING & COMMISSIONING, INC 2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429 Roberta,tabfirm.com Expires 3/31/2016 Equipment Calibration Schedule Instrument Serial # Model Application Dates of use Calibration Date Evergreen DP Meter with 8" & 15" Flow Hoods E2F5- 1400152 PNS-PV FPM CFM DP 8n1l5 8/4/2015 Evergreeen Temp Meter 1400168 RM-T-1 Temperature Not Used 8/4/2015 Evergreeen Temp/RH Meter 1400171 SH-3-5" Temperature & Humidity Not Used 8/4/2015 Fluke Electrical Meter 27351379 T5-600 Voltage, Amperage Not Used 3/2/2015 Air Velocity Meter 0713006 TSI 9545 Velocity 8/7/15 3/2/2015 Rotating Vane 500825005 RVA501 Velocity, CFM Not Used 3/3/2015 Amprobe Temp/RH Meter 100303037 THWD-3 Temperature & Humidity Not Used 3/3/2015 Monarch Tachometer 1835039 PLT200 RPM Not Used 3/2/2015 Alnor Hydrometer 70622061 HM 760 Water DP Not Used 3/2/15 Definitions FPM — feet per minute RPM — Revolutions per minute RH — Relative Humidity R/A — Return Air O/A —Outside Air HP —Horsepower EDH — Electric Duct Heater GPM — Gallons per minute AHU — Air Handling Unit " — Inches TBD — To Be Determined CFM — cubic feet per minute DP — Differential Pressure S/A — Supply Air E/A — Exhaust Air FL — Full Load SP — Static Pressure PSI — Pounds per square inch db - Decibels N/A — No Design Value on Drawings CHW — Chilled Water ft — Feet Head ACCURATE BALANCING & COMMISSIONING, INC 2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429 RobertAtabfirm.com Expires 3/31/2016 Project Summary Perform test & balance of supply grills and outside air flow for existing roof top unit and exhaust flow for existing hood. No deficiencies noted. Deficiencies Table of Contents Description Page Number AHU & Supply Grill Report 1-2 Exhaust Fan 3 Drawing with Supply Grill Numbers 4 tiL':GURATE BALANCING & COMMISSIONING, INC Air Handling Unit PROJECT: Speedway LOCATION: Port St Lucie, FL PROJECT #: 8580 US1 SYSTEM/UNIT: RTU-1 AREA: Store Unit Data Unit Manufacturer Trane Unit Model Number TCD18OB300 Unit Serial Number 842101520D RTU-1 / SF Filter Bank Filter Type 2" Pleated Filter Quantity -Size 1 4 Filter Dimensions - Size 1 20x25x2 Filter Quantity - Size 2 2 Filter Dimensions - Size 2 20x2Ox2 Test Data CIA Damper Position 20 % " Outside Air Duct Size 23xl8in RTUA / Supply Fan Motor Volts T1-T2 210 Volts Motor Volts T2-T3 212 Volts Motor Volts T1-T3 211 Volts Motor Amps T1 9.2 Amps Motor Amps T2 8.4 Amps Motor Amps T3 8.5 Amps DATE: 8/10/2015 CONTACT: Robert Shorr Motor Data RTU-1 I Supply Fan Motor Frame 56HZ Motor HP 3 HP Motor RPM 1725 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 9.4 Amps Motor Service Factor 1.15 Sheave Data RTU-1 / Supply Fan Motor Sheave Model 1 VP48 Motor Sheave Bore 1-1/8 in. Fan Sheave Model BK85 Fan Sheave Bore 1 in. Number of Belts 1 Belt Size BX62 Sheave Center Line 21.00 in. Sheave % Open 0 % Test Pressures Pre -Filter SP In -0.16 in, we Cool. Coil SP In -0.54 in. we Total SP Discharge 0.55 in. we Air Test Data Total S/A Outlet Design 6000 CFM Total SIA Outlet Actual 5665 CFM Outside Air Design Max 700 CFM Outside Air Actual Max 724 CFM Accurate Balancing and Commissioning Page 1 of 4 ACCURATE BALANCING & COMMISSIONING, INC Air Handling Unit PROJECT: Speedway LOCATION: Port St Lucie, FL PROJECT #: 8580 US1 SYSTEM/UNIT: RTU-1 (Cont.) AREA: Store RTU-1 Supply Outlet Summary DATE: 8/10/2015 CONTACT: Robert Shorr Syste Untt rea Served Des g 9 RMead -IBeg PFilm e d n °. Prel'm Deviation Fina Readin •° Pinal Deviation Outlet-01 Store 400 265 66 367 92 Outlet-02 Store 400 331 83 394 99 Outlet-03 Store 450 345 77 429 95 Outlet-04 Store 450 306 68 435 97 Outlet-05 Store 450 349 78 426 95 Outlet-06 Store 400 327 82 383 96 Outlet-07 Store 400 176 44 407 102 Outlet-08 Store 450 225 50 413 92 Outlet-09 Store 450 257 57 410 91 Outlet-10 Food Prep 400 202 51 383 96 Outlet-11 Food Prep 400 151 38 375 94 Outlet-12 Store 450 226 50 412 92 Outlet-13 Storage 250 107 43 231 92 Outlet-14 Storage 300 166 55 278 93 Outlet-15 Restroom 50 80 160 49 98 Outlet-16 Restroom 50 102 204 47 94 Outlet-17 Corridor 250 90 36 226 90 - NETatals 6,1ID0 ` 1 �-' * Notes RTU-1 10-Aug-15 Robert Shorr Filters clogged on pretest. Removed a filter for final testing. Owner needs to replace filters. Accurate Balancing and Commissioning Page 2 of 4 �.i ACCURATE BALANCING & COMMISSIONING, INC Fan Unit PROJECT: Speedway LOCATION: Port St Lucie, FL PROJECT #: 8580 US1 SYSTEM/UNIT: KEF-1 AREA: Unit Da Fan Manufacturer Captive Air Fan Model Number DU50HFA Test Data Total Fan Design Airflow 500 CFM Total Actual Airflow 543 CFM volts 117 Volts Motor Amps T7 2.9 Amps * Notes DATE: 8/10/2015 CONTACT: Robert Shorr Motor Da Motor HP 1/4 HP Motor RPM 1625 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 5 Amps Sheave Data Motor Sheave Model Direct Drive KEF-1 10-Aug-15 Robert Shorr Changed fan speed from high to low and installed damper to lower cfm from 1282 to 573. Accurate Balancing and Commissioning Page 3 of 4