HomeMy WebLinkAboutCERTIFIED TEST - BALANCE REPORT` SCANNED
BY
St. Lucie County
*.150C/— aka 9
ACCURATE BALANCING & COMMISSIONING, INC
2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429
Robert(@tabfirm.com Expires 3/31/2016
CERTIFIED TEST; ADJUST; BALANCE REPORT
Project: Speedway
8580 US Hwy 1
Port St Lucie, FL 34952
Engineer: Richard L Bowen & Associates
13000 Shaker Blvd
Cleveland, OH 44120
Phone: 216-491-9300
Drawings dated 5/20/15 Bulletin 1
Contractor: Great Dane Petroleum
1330 S Andrews Avenue FRn
Pompano Beach, Florida 33311
Phone: 954-931-0186 AUG 1 0p
Technicians: Robert Shorr, Travis Shorr
Test Date: 8/7/15
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB
PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.
ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE
TEST -ADJUST -BALANCE REPORT PROJECT SUMMARY DUCT SMOKE DETECTOR TESTING AND
CERTIFICATION VERIFIES THE DIFFERENTIAL PRESSURE ACROSS THE DETECTOR PICK UP TUBES ONLY
AND DOES NOT TEST ANY ELECTRICAL OR DETECTOR OPERATION.
,r
Robert Shorr, NEBB Certified Profession! Date
ACCURATE BALANCING & COMMISSIONING, INC
2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429
Roberta,tabfirm.com Expires 3/31/2016
Equipment Calibration Schedule
Instrument
Serial #
Model
Application
Dates of use
Calibration
Date
Evergreen DP Meter with
8" & 15" Flow Hoods
E2F5-
1400152
PNS-PV
FPM CFM DP
8n1l5
8/4/2015
Evergreeen Temp Meter
1400168
RM-T-1
Temperature
Not Used
8/4/2015
Evergreeen Temp/RH
Meter
1400171
SH-3-5"
Temperature & Humidity
Not Used
8/4/2015
Fluke Electrical Meter
27351379
T5-600
Voltage, Amperage
Not Used
3/2/2015
Air Velocity Meter
0713006
TSI 9545
Velocity
8/7/15
3/2/2015
Rotating Vane
500825005
RVA501
Velocity, CFM
Not Used
3/3/2015
Amprobe Temp/RH Meter
100303037
THWD-3
Temperature & Humidity
Not Used
3/3/2015
Monarch Tachometer
1835039
PLT200
RPM
Not Used
3/2/2015
Alnor Hydrometer
70622061
HM 760
Water DP
Not Used
3/2/15
Definitions
FPM — feet per minute
RPM — Revolutions per minute
RH — Relative Humidity
R/A — Return Air
O/A —Outside Air
HP —Horsepower
EDH — Electric Duct Heater
GPM — Gallons per minute
AHU — Air Handling Unit
" — Inches
TBD — To Be Determined
CFM — cubic feet per minute
DP — Differential Pressure
S/A — Supply Air
E/A — Exhaust Air
FL — Full Load
SP — Static Pressure
PSI — Pounds per square inch
db - Decibels
N/A — No Design Value on Drawings
CHW — Chilled Water
ft — Feet Head
ACCURATE BALANCING & COMMISSIONING, INC
2247 Palm Beach Lakes Blvd., Suite 105. West Palm Beach, FL 33409 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 Fax 561-855-8105 NEBB Certification #3429
RobertAtabfirm.com Expires 3/31/2016
Project Summary
Perform test & balance of supply grills and outside air flow for existing roof top unit and
exhaust flow for existing hood.
No deficiencies noted.
Deficiencies
Table of Contents
Description Page Number
AHU & Supply Grill Report 1-2
Exhaust Fan 3
Drawing with Supply Grill Numbers 4
tiL':GURATE BALANCING & COMMISSIONING, INC
Air Handling Unit
PROJECT: Speedway
LOCATION: Port St Lucie, FL
PROJECT #: 8580 US1
SYSTEM/UNIT: RTU-1
AREA: Store
Unit Data
Unit Manufacturer
Trane
Unit Model Number
TCD18OB300
Unit Serial Number
842101520D
RTU-1 / SF Filter Bank
Filter Type
2" Pleated
Filter Quantity -Size 1
4
Filter Dimensions - Size 1
20x25x2
Filter Quantity - Size 2
2
Filter Dimensions - Size 2
20x2Ox2
Test Data
CIA Damper Position
20 % "
Outside Air Duct Size
23xl8in
RTUA / Supply Fan
Motor Volts T1-T2
210 Volts
Motor Volts T2-T3
212 Volts
Motor Volts T1-T3
211 Volts
Motor Amps T1
9.2 Amps
Motor Amps T2
8.4 Amps
Motor Amps T3
8.5 Amps
DATE: 8/10/2015
CONTACT: Robert Shorr
Motor Data
RTU-1 I Supply Fan
Motor Frame
56HZ
Motor HP
3 HP
Motor RPM
1725 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
9.4 Amps
Motor Service Factor
1.15
Sheave Data
RTU-1 / Supply Fan
Motor Sheave Model
1 VP48
Motor Sheave Bore
1-1/8 in.
Fan Sheave Model
BK85
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
BX62
Sheave Center Line
21.00 in.
Sheave % Open
0 %
Test Pressures
Pre -Filter SP In
-0.16 in, we
Cool. Coil SP In
-0.54 in. we
Total SP Discharge
0.55 in. we
Air Test Data
Total S/A Outlet Design
6000 CFM
Total SIA Outlet Actual
5665 CFM
Outside Air Design Max
700 CFM
Outside Air Actual Max
724 CFM
Accurate Balancing and Commissioning Page 1 of 4
ACCURATE BALANCING & COMMISSIONING, INC
Air Handling Unit
PROJECT: Speedway
LOCATION: Port St Lucie, FL
PROJECT #: 8580 US1
SYSTEM/UNIT: RTU-1 (Cont.)
AREA: Store
RTU-1 Supply Outlet Summary
DATE: 8/10/2015
CONTACT: Robert Shorr
Syste Untt
rea Served
Des g 9
RMead -IBeg
PFilm
e d n
°. Prel'm
Deviation
Fina Readin
•° Pinal
Deviation
Outlet-01
Store
400
265
66
367
92
Outlet-02
Store
400
331
83
394
99
Outlet-03
Store
450
345
77
429
95
Outlet-04
Store
450
306
68
435
97
Outlet-05
Store
450
349
78
426
95
Outlet-06
Store
400
327
82
383
96
Outlet-07
Store
400
176
44
407
102
Outlet-08
Store
450
225
50
413
92
Outlet-09
Store
450
257
57
410
91
Outlet-10
Food Prep
400
202
51
383
96
Outlet-11
Food Prep
400
151
38
375
94
Outlet-12
Store
450
226
50
412
92
Outlet-13
Storage
250
107
43
231
92
Outlet-14
Storage
300
166
55
278
93
Outlet-15
Restroom
50
80
160
49
98
Outlet-16
Restroom
50
102
204
47
94
Outlet-17
Corridor
250
90
36
226
90
-
NETatals
6,1ID0
`
1
�-'
* Notes
RTU-1 10-Aug-15 Robert Shorr Filters clogged on pretest. Removed a filter for final
testing. Owner needs to replace filters.
Accurate Balancing and Commissioning Page 2 of 4
�.i
ACCURATE BALANCING & COMMISSIONING, INC
Fan Unit
PROJECT: Speedway
LOCATION: Port St Lucie, FL
PROJECT #: 8580 US1
SYSTEM/UNIT: KEF-1
AREA:
Unit Da
Fan Manufacturer
Captive Air
Fan Model Number
DU50HFA
Test Data
Total Fan Design Airflow 500 CFM
Total Actual Airflow
543 CFM
volts
117 Volts
Motor Amps T7
2.9 Amps
* Notes
DATE: 8/10/2015
CONTACT: Robert Shorr
Motor Da
Motor HP
1/4 HP
Motor RPM
1625 RPM
Motor Rated Volts 115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
5 Amps
Sheave Data
Motor Sheave Model Direct Drive
KEF-1 10-Aug-15 Robert Shorr Changed fan speed from high to low and installed
damper to lower cfm from 1282 to 573.
Accurate Balancing and Commissioning Page 3 of 4