Loading...
HomeMy WebLinkAboutCODE REQUIRMENT FOR BULK RESIN STORAGESCANNED BY St Lucie County CODE REQUIRMENT FOR BULK RESIN STORAGE In the following paragraphs we will attempt to explain the national fire codes for storage of polyester resin that are Class 1, Division II Stable Liquids with a specific gravity greater than 1. These codes will cover inside and outside bulk storage. In this explanation we will reference several publications: 1. 2. 3. 4. 5. 6. F Uo 0 Y IFC (International Fire Code) NFPA 30 (National Fire Protection Association) UL-142, UL-2080 and UL-2085 Steel Above Ground Tanks for Flammable and Combustible Liquids. Single and double -walled tanks. CFR (Code of Federal Regulations Title-40 Part-112 and Title-29 Part-1910.) ANSI/API 650 NFPA 33 (National Fire Protection Association) Chapter 6 & 15 Most agencies use the above mentioned codes as guidelines, but there may also be local differences in interpretation. It is very important to have the input of local agencies. We stress to our clients the need to consult with the local and/or State Fire Marshall, and insurance carrier. In most code books you will see the term "The authority Having Jurisdiction." The "Authority Having Jurisdiction" is the organization, office or individual responsible for "approving" equipment, an installation or a procedure. NOTE: The phrase "authority having jurisdiction" is used in NFPA documents in a broad manner. Several jurisdictions and "approval' agencies may have varying responsibilities for a given installation. Where public safety is of primary concern, the "authority having jurisdiction" may be a federal, state, local or other regional department, health department, building inspector, electrical inspectors or others having statutory authority. For insurance purposes, an insurance inspector, rating bureau or other insurance company representative may be the "authority having jurisdiction." In some circumstances, such as a Federal Installation, the property owner or designated agent assumes the role of the "authority having jurisdiction" Our intent is to make all installation as safe as we know how, and to conform to all safety requirements, codes and statutes. FIRST, THE TANKITSELF. IFC: Section 3404.2.7 Design, construction and general installation requirements for tanks. The design, fabrication and construction of tanks shall comply with NFPA 30. Each tank shall bear a permanent nameplate or marking indicating the standard used as the basis of design. Page 1. 4� NFPA-30: 21.4 Design and construction of tanks. NFPA-30: 21.3.1 GENERAL REQUIREMENTS. Tanks shall be permitted to be of any shape, size, or type consistent with recognized engineering standards. Metal tanks shall be welded, riveted and caulked, or bolted, or constructed using a combination of these methods. NFPA-30: 21.4.1 MATERIALS OF CONSTRUCTION. Tanks shall be of steel or other approved noncombustible material and shall meet the applicable requirements of 21.4.1.1 through 21.4.1.5. NFPA-30: 21.4.1.1 The materials of construction for tanks and their appurtenances shall be compatible with the liquid to be stored. In case of doubt about the properties of the liquid to be stored, the supplier, producer of the liquid, or other competent authority shall be consulted. NFPA-30: 21.4.1.2 Tanks shall be permitted to be constructed of combustible materials when approved. Tanks constructed of combustible materials shall be limited to any of the following: (1) Underground installation (2) Use where required by the properties of the liquid stored (3) Aboveground storage of class IIIB liquids in areas not exposed to a spill or leak of Class I or Class II liquid (4) Storage of Class IIIB liquids inside a building protected by an approved automatic fire -extinguishing system NFPA-30: 21.4.1.3 Unlined concrete tanks shall be permitted to be used for storing liquids that have a gravity of 40' API or heavier. Concrete tanks with special linings shall be permitted to be used for other liquids provided they are designed and constructed in accordance with recognized engineering standards. NFPA-30: 21.4.1.4 Tanks shall be permitted to have combustible or noncombustible linings. The choice of the lining material and its required thickness shall depend on the properties of the liquid to be stored. NFPA-30: 21.4.1.5An engineering evaluation shall be made if the specific gravity of the liquid to be stored exceeds that of water or if the tank is designed to contain liquids at a liquid temperature below 0°F (-18°C). NFPA-30: 21.4.2 DESIGN STANDARDS FOR STORAGE TANKS. NFPA-30: 21.4.2.1 DESIGN STANDARDS FOR ATMOSPHERIC TANKS. NFPA-30: 21.4.2.1.1 Atmospheric tanks shall be designed and constructed in accordance with recognized engineering standards. Atmospheric tanks that meet any of the following standards shall be deemed as meeting the requirements of 21.4.2.1: (1) UL 58, Standard for Steel Underground Tanks for Flammable and Combustible Liquids; UL 80, Standard for Steel Inside Tanks for Oil Burner Fuel; UL 142, Standard for Steel Aboveground Tanks for Flammable and Combustible Liquids; UL 2080, Standard for Fire Resistant Tanks for Flammable and Combustible Liquids; or Page 2. 4; UL 2085, Standard for Insulated Aboveground Tanks for Flammable and Combustible Liquids (2) API Specification 12B, Bolted Tanks for Storage of Production Liquids: API Specification 12D, Field Welded Tanks for Storage of Production Liquids; API Specification 12F, Shop Welded Tanks for Storage of Production Liquids; or API Standard 650, Welded Steel Tanks for Oil Storage (3) UL 1316, Standard for Glass -Fiber Reinforced Plastic Underground Storage Tanks for Petroleum Products, Alcohol, and Alcohol -Gasoline Mixtures (4) UL 1746, Standard for External Corrosion Protection Systems for Steel Underground Storage Tanks NFPA-30: 21.4.2.1.2 Except as provided for in 21.4.2.1.3 and 21.4.2.1.4, atmospheric tanks designed and constructed in accordance with Appendix F of API Standard 650, Welded Steel Tanks for Oil Storage, shall be permitted to operate at pressures from atmospheric to a gauge pressure of 1.0 psig (gauge pressure of 6.9 kPa). All other tanks shall be limited to operation from atmospheric to a gauge pressure of 0.5 psig (gauge pressure of 3.5 kPa). NFPA-30: 21.4.2.1.3 Atmospheric tanks that are not designed and constructed in accordance with Appendix F of API Standard 650, Welded Steel Tanks for Oil Storage, shall be permitted to operate at pressures from atmospheric to a gauge pressure of 1.0 psig (gauge pressure of 6.9 kPa) only if an engineering analysis is performed to determine that the tank can withstand the elevated pressure. NFPA-30: 21.4.2.1.4 Horizontal cylindrical and rectangular tanks built according to any of the standards specified in 21.4.2.1.1 shall be permitted to operate at pressures from atmospheric to 1.0 psig (gauge pressure of 6.9 kPa) and shall be limited to 2.5 psig (gauge pressure of 17.2 kPa) under emergency venting conditions. Notes: 1. The fifth tank listed in 21.4.2.1.1 (5) is a UL 58 which is for underground tanks. We do not recommend underground storage of polyester due to the new EPA Regulations. Please consult CFR40 Parts 280 to 282 Underground Storage Tank Technical Requirements and State Program Approval. Final Rule. Also please consult EPA 530 UST-88/005 and EPA 530 UST-88/008. 2. The sixth (6) tank listed is UL80 which is for inside tanks for oil burner fuel, which does not apply. The seventh (7) tank listed in this sub -paragraph are described in UL142, UL2080 and UL2085 section 1.1 These requirements cover shop fabricated, aboveground atmospheric and Fire Resistant Tanks intended for storage of stable flammable or combustible liquids that have a specific gravity not greater than 1.0 and that are compatible with the material and construction of the tank. Page 3. As you can see by this paragraph, it immediately disallows these specifications for polyester resin use, because of the high specific gravity of the resin which is 1.1 to 1.4. A UL142, UL2080 and UL2085 type of tank does not have the structural strength to hold polyester resin. 3. NFPA-30: Section 21.4.2.1.1 (4) refers to the American Petroleum Institute Standard No. 650, Welded Steel Tanks for Oil Storage. This specification, in combination with the guidelines in NFPA 30 will provide an acceptable design, in most cases. NFPA 30 references API-650 in Exception No. 1 Atmospheric tanks that are not designed and constructed in accordance with Appendix F of API Standard 650, Welded Steel Tanks for Oil Storage, shall be permitted to operate at pressures from atmospheric to 1.0 psig (gauge pressure of 6.9 kPa) only if an engineering analysis is performed to determine that the tank can withstand the elevated pressure. NFPA-30: Section 21.4.2.1.1 (8) refers to UL-1316 this is a glass fiber reinforced plastic storage tank for underground use. Please consult the EPA Regulations cited in note 1 above. NFPA-30: Section 21.4.2.1.1 (9) refers to UL-1746 refers to external corrosion protection systems for underground storage tanks. Please consult the EPA Regulations cited in note 1 above. (CFR) Title 29-Labor Part 1910 Under Tank storage: (f) Special engineering consideration shall be required if the specific gravity of the liquid to be stored exceeds that of water or if the tanks are designed to contain flammable or combustible liquids at a liquid temperature below 0 F. In summing up this section, the only specifications that can be applied are API- 650. API-650 is an above ground tanks, we can use their design requirements in Appendix J to determine the appropriate structural strength. This is the standard that we use to design our storage tanks along with all the safety requirements in NFPA-30. Note: Some people ask for double -walled aboveground storage tanks. The only standard for these types of tanks are UL-142, UL-2080 and UL-2085. Section 1.1 in these codes reads as follows: These requirements cover shop fabricated, aboveground atmospheric and Fire Resistant Tanks intended for storage of stable flammable or combustible liquids that have a specific gravity not greater than 1.0 and that are compatible with the material and construction of the tank. As you can see by this paragraph, it immediately disallows these specifications for polyester resin use, because of the high specific gravity of the resin which is 1.1 to 1.4. A UL142, UL2080 and UL2085 type of tank does not have the structural strength to hold polyester resin. The requirements of IFC and NFPA 30 must be included to develop the appropriate fitting designs. Particular attention must be paid to the following sections: 1. IFC: 3404.2.7.5.5 & NFPA-30: 21.4.4 Page 4. Fill pipes and discharge lines. For top -loaded tanks, a metallic fill pipe shall be designed and installed to minimize the generation of static electricity by terminating the pipe within 6 inches of the bottom of the tank, and it shall be installed in a manner which avoids excessive vibration. 2. IFC: 3404.2.7.4 Emergency venting. Stationary, aboveground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with section 4.2.5.2 of NFPA-30. NFPA-30: 22.7 Emergency relief venting for fire exposure for aboveground tanks 22.7.1.1 Every aboveground storage tank shall have emergency relief venting in the form of construction or a device or devices that will relieve excessive internal pressure caused by an exposure fire. 22.7.1.1.2 This requirement shall also apply to each compartment of a compartmented tank, the interstitial space (annulus) of a secondary containment -type tank, and the enclosed space of tanks of closed -up dike construction. This requirement shall also apply to spaces or enclosed volumes, such as those intended for insulation, membranes, or weather shields, that can contain liquid because of a leak from the primary vessel and can inhibit venting during fire exposure. The insulation, membrane, or weather shield shall not interfere with emergency venting. 22.7.1.1.3 Tanks storing Class IIIB liquids that are larger than 12,000 gal (45,400 L) capacity and are not within the diked area or the drainage path of tanks storing Class I or Class II liquids shall not be required to meet the requirements of 22.7.1.1. NFPA-30: 22.7.1.2 For vertical tanks, the emergency relief venting construction referred to in 22.7.1.1 shall be permitted to be a floating roof, a lifter roof, a weak roof -to -shell seam, or another approved pressure -relieving construction. 22.7.1.3 Weak Roof -to -Shell Seam Construction. If used, a weak roof -to -shell seam shall be constructed to fail preferential to any other seam and shall be designed in accordance with API Standard 650, Welded Steel Tanks for Oil Storage, or UL 142, Standard for Steel Aboveground Tanks for Flammable and Combustible Liquids. Notes: Emergency Venting Capacity for our tanks: The formula given: Cubic feet of free air per hour = V x 1,337/ L x SQR (M) The tank in question has a total surface area Of 550 sq. ft. Per NFPA-30 22.7.3.2.2 (2) you only use 75% for table 22.7.3.2 or 480 sq. ft. This gives a requirement for 354,000 cu. ft. The next item in the formula is the Latent heat of Vaporization of Styrene. This is 102.4 calories per gram or 184 BTU per pound. Page 5. The last item in the formula is the Molecular weight of Styrene 104.14. The Formula works as follows: 354,000 x 1,337/ 184 x SQR (104.14) 354,000 x 1,337/ 184 x 10.2 354,000 x 1,337/1,877 354,000 x .712 = 252,048 This gives a required venting capacity of 252,048 cubic feet of free air per hour. If you further realize we are dealing with a Resin Solution of only 35% Styrene, we have a significant safety margin. 3. IFC: 3404.2.7.3 Tank vents for normal venting. Tank vents for normal venting shall be installed and maintained in accordance with sections 3404.2.7.3.1 through 3404.2.7.3.6 NFPA-30: 21.4.3 Normal venting for storage tanks. NFPA-30: 21.4.3.1 Atmospheric Storage tanks shall be vented to prevent the development of vacuum or pressure that can distort the roof of a cone roof tank or that exceeds the design pressure of other atmospheric tanks when filling or emptying the tank or because of atmospheric temperature changes. NFPA-30: 21.4.3.2 Normal vents shall be sized in accordance with either API Standard 2000, Venting Atmospheric and Low -Pressure Storage Tanks, or another approved standard. Alternatively, the normal vent shall be at least as large as the largest filling or withdrawal connection but in no case shall it be less than 1.25-in. (32-mm) nominal inside diameter. NFPA-30: 21.4.3.9 Flame arrestors or venting devices required in 21.4.3.6 and 21.4.3.7 shall be permitted to be omitted on tanks that store Class IB or Class IC liquids where conditions are such that their use can, in case of obstruction, result in damage to the tank. Liquid properties justifying the omission of such devices include but are not limited to, condensation, corrosiveness, crystallization, polymerization, freezing, or plugging. When any of these conditions exist, consideration shall be permitted to be given to heating, use of devices employing special materials of construction, the use of liquid seals, or inerting. The codes explanation for the variance makes reference to the importance of frequent vent inspection. Because of the way polyester resin does polymerize, our design allows for easy removal of the vents for inspection and cleaning as necessary. Also with our filling procedure they are checked each time the tank is filled. 4. IFC: 3404.2.7.5.8 Overfill prevention. An approved means or method in accordance with section 3404.2.9.6.6 shall be provided to prevent the overfill of all Class I, II and IIIA liquid storage tanks. Page 6. IFC: 3404.2.9.6.6 Overfill prevention. Protected aboveground tanks shall not be filled in excess of 95 percent of their capacity. An overfill prevention system shall be provided for each tank. During tank - filling operations, the system shall: Provide an independent means of notifying the person filling the tank that the fluid level has reached 90 percent of tank capacity by providing an audible or visual alarm signal, providing a tank level gauge marked 90 percent of tank capacity, or other approved means. A filling procedure shall require person filling the tank to determine the gallonage required to fill it to 90 percent of capacity before commencing the fill operation. Our tank systems have load cells that displays the weight of the fluid in the tank at all times. Also the system has low and high level alarms that are audible and visual. This is the only way that we have found in are years of installing resin storage tank to keep track of the material in each tank. This along with are filling procedure will stop the over filling of the tanks. IFC: 3404.2.9.6.4 Secondary containment. Protected aboveground tanks shall be provided with secondary containment, drainage control or diking in accordance with section 2704.2. A means shall be provided to establish the integrity of the secondary containment in accordance with NFPA-30. NFPA-30: 22.11 Control of spill from aboveground tanks. Every tank that contains a Class I, II or IIIA liquid shall be provided with means to prevent an accidental release of liquid from endangering important facilities and adjoining property or from reaching waterways. Such means shall meet the requirements of 22.11.1, 22.11.2, 22.11.3, or 22.11.4, whichever is applicable. NFPA-30: 22.11.2.2 The volumetric capacity of the diked area shall not be less than the greatest amount of liquid that can be released from the largest tank within the diked area, assuming a full tank. 22.11.2.2.1 To allow for volume occupied by tanks, the capacity of the diked are enclosing more than one tank shall be calculated after deducting the volume of the tank, other than the largest tank, below the height of the dike. 6. MC: 3404.212 Testing. Tank testing shall comply with sections 3404.2.12.1 and 3404.2.12.2 IFC: 3404.2.12.1 Acceptance testing. Prior to being placed into service, tanks shall be tested in accordance with section 4.4 ofNFPA-30. NFPA-30: 21.5 Testing requirements for tanks. NFPA-30: 21.5.1 Initial testing. All tanks, whether shop -built or field -erected, shall be tested before they are placed in service in accordance with the applicable requirements of the code under which they were built. Page 7. NFPA-30: 21.5.1.1 An approved listing mark on a tank shall be considered to be evidence of compliance with this requirement. Tanks not so shall be tested before placed in service in accordance with recognized engineering standards or in accordance with the requirements for testing in the codes listed in 21.4.2.1.1,21.4.2.2.1 or 21.4.2.3.1. NFPA-30: 21.5.2.3 Horizontal shop -fabricated aboveground tanks shall be tested for tightness either hydrostatically or with air pressure at not less than 3 psig and not more than 5 psig. Our tanks are horizontal shop -fabricated aboveground tanks, we test each unit at 3 psig and not only do we mark the tank but we also give a testing certificate with all the test data. PLACEMENT OF THE TANK ON YOUR PROPERTY OUTSIDE YOUR BUILDING: Prior to deciding on tank placement, it is important to obtain the input of the local Fire Marshal. Many state and local agencies have additional requirements beyond IFC and NFPA-30. 1. NFPA-30: 22.5 Installation of aboveground tanks. NFPA-30: 22.4.1 Location with respect to property lines, public ways, and important buildings. NFPA-30: 22.4.1.1 Tanks storing Class I, Class II, Class IIIA stable liquids whose internal pressure is not permitted to exceed a gauge pressure of 2.5 psig (17 kPa) shall be located in accordance with Tables 22.4.1.1(a) and Table 22.4.1.1 (b). Where tank spacing is based on a weak roof -to -shell seam design, the user shall present evidence certifying such construction to the authority having jurisdiction upon request. NOTE: USE TABLE NFPA-30: 22.4.1.l(a) STABLE LIQUIDS [OPERATING PRESSURE 2.5 PSIG OR LESS] for horizontal and vertical tanks with emergency relief venting to limit pressure to 2.5 psig and protection NONE. This states to use 2 times table 22.4.1.1 (b) for minimum distance in feet from property line that is or can be built upon, including the opposite side of a public way, and shall not be less than 5ft. Also use table 22.4.1.1 (b) for the minimum distance in feet from nearest side of any public way or from nearest important building on the same property and shall not be less than 5 ft. If you reference table 22.4.1.1 (b) using a storage tank with a capacity of 751 to 12,000 gallons you will need to be 30 feet from the property line. 1. iChe required distance fromt e proper v linet orlourtan stkisdaldistanceioT'f30A�' Page 8. 2. The I'' imum distance from nearest side of any public wa or from the nearest important building on the same property is a distance o 5 feet.. PLACEMENT OF THE TANK ON YOUR PROPERTYINSIDE YOUR BUILDING. IFC: 2206.2.2 Aboveground tanks located inside buildings. Aboveground tanks for the storage of a Class I, II and IIIA liquids are allowed to be located in building.,Such tanks shall be located in special enclosures complying with section 2206.2.6 in a liquid storage room or a liquid storage warehouse complying with Chapter 34, Or shall be listed and labeled as protected aboveground tanks in 3404.2.8. IFC: 2206.2.6 Special enclosures. Where installation of tanks in accordance with section 3404.2.11 is impractical (Underground tanks, please is page 3-note 1.), or because of property or building limitation, tanks for liquid are allowed to be installed in special enclosures in accordance with all of the following: 1. The special enclosure shall be liquid tight and vapor tight. 2. The special enclosure shall not contain backfill. 3. Sides, top and bottom of the special enclosure shall be of reinforced concrete at least 6 inches thick, with openings for inspection through the top only. 4. Tank connections shall be piped or closed such that neither vapors nor liquid can escape into the enclosed space between the special enclosure and any tanks inside the special enclosure. 5. Mean shall be provided whereby portable equipment can be employed to discharge to the outside any vapors which might accumulate inside the special enclosure should leakage occur. 6. Tanks containing Class I, II and IIIA liquids inside a special enclosure shall not exceed 6,000 gallons (22 710 L) in individual or 18,000 gallons (68 130 L) in aggregate capacity. 7. Each tank within special enclosures shall be surrounded by a clear space of not less than 3 feet to allow for maintenance. IFC: 3404.2.8 Vaults. Vaults shall be allowed to be either above or below grade and shall comply with sections 3404.2.8.1 through 3404.2.8.18. IFC: 3404.2.8.1 Listing required. Vaults shall be listed in accordance with UL 2245. NOTE: UL-2245: Below -Grade Vaults for Flammable Liquid Storage Tanks Page 9. I Scope 1.1 These requirements cover below -grade vaults intended for the storage of flammable or combustible liquids in an aboveground atmospheric tank. Below -grade vaults are designed to contain one aboveground tank which can be a compartment tank. Adjacent vaults may share a common wall. The lid of the vault may be at or below - grade. 1.2 Below -grade vaults are constructed of a minimum of 6 inches (152.4 mm) of reinforced concrete or other equivalent noncombustible material and form a complete, liquid -tight enclosure that does not allow external ground water to permeate through the vault walls. Below -grade vaults can be evaluated as secondary containment vaults. 1.3 Below -grade vaults covered by these requirements do not include an evaluation of components, such as ventilation equipment, leak detection and monitoring equipment, overfill protection equipment, and access ladders. 1.4 Below -grade vaults are intended for installation and use in accordance with the manufacturer's instructions and the following fire codes: the Flammable and Combustible Liquids Code, NFPA 30, the Automotive and Marine Service Station Code, NFPA 30A , and the Uniform Fire Code, Appendix II-J. 1.5 Below -grade vaults covered by these requirements may be shipped in parts that require final assembly in the field. When field assembly is required, detailed installation instructions shall be provided. 1.6 These requirements do not cover seismic loading. 1.7 A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this Standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end -product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Standard shall not be judged to comply with this Standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this Standard. IFC: 3404.2.8.2 Design and construction. The vault shall completely enclose each tank. There shall be no openings in the vault enclosure except those necessary for access to, inspection of, and filling, emptying and venting of the tank. The walls and floor of the vault shall be constructed of reinforced concrete at least 6 inches thick. The top of an above -grade vault shall constructed of noncombustible material and shall be designed to be walls of the vault, to ensure that the thrust of an explosion occurring inside the vault is directed upward before significantly high pressure can develop within the vault. Page 10. The top of an at -grade or below -grade vault shall be designed to relieve safely or contain the force of an explosion occurring inside the vault. The top and floor of the vault and the tank foundation shall be designed to withstand the anticipated loading, including loading from vehicular traffic, where applicable. The walls and floor of a vault installed below grade shall be designed to withstand anticipated soil and hydrostatic loading. Vaults shall be designed to be wind and earthquake resistant, in accordance with the International Building Code. IFC: 3404.2.8.3 Secondary containment. Vaults shall be substantially liquid tight and there shall be no backfill around the tank or within the vault. The vault floor shall drain to a sump. For premanufactured vaults, liquid tightness shall be certified as part of the listing provided by a nationally recognized testing laboratory. For field -erected vaults, liquid tightness shall be certified in an approved manner. IFC: 3404.2.8.4 Internal clearance. There shall be sufficient clearance between the tank and the vault to allow for visual inspection and maintenance of the tank and its appurtenances. Dispensing devices are allowed to be installed on the top of vaults. IFC: 3404.2.8.5 Anchoring. Vaults and their tanks shall be suitable anchored to withstand uplifting by ground water or flooding, including when the tank is empty. IFC: 3404.2.8.6 Vehicle impact protection. Vaults shall be resistant to damage from the impact of a motor vehicle, or vehicle impact protection shall be provided in accordance with section 312. IFC: 3404.2.8.7 Arrangement. Tanks shall be listed for aboveground use, and each tank shall be in its own vault. Compartmentalized tanks shall be allowed and shall be considered as a single tank. Adjacent vaults shall be allowed to share a common wall. The common wall shall be liquid and vapor tight and shall be designed to withstand the load imposed when the vault on either side of the wall is filled with water. IFC: 3404.2.8.8 Connections. Connections shall be provided to permit venting of each vault to dilute, disperse and remove vapors prior to personnel entering the vault. IFC: 3404.2.8.9 Ventilation. Vaults that contain tanks of Class I liquids shall be provided with an exhaust ventilation system installed in accordance with section 2704.3. The ventilation system shall operate continuously or be designed to operate upon activation of the vapor or liquid detection system. The system shall provide ventilation at a rate of not less than 1 cubic foot per minute (cfm) per square foot of floor area [0.00508 m3/(s x m2)], but not less than 150 cfm[0.071 m3/(s x m2)]. The exhaust system shall be designed to provide air movement across all parts of the vault Page 11. I - \ floor. Supply and exhaust ducts shall extend to within 3 inches, but not more than 12 inches, from the floor. The exhaust system shall be installed in accordance with the International Mechanical Code. IFC: 3404.2.8.10 Liquid detection. Vaults shall be equipped with detection system capable of detecting liquids, including water, and activating an alarm. IFC: 3404.2.8.11 Monitoring and detection. Vault shall be provided with approved vapor and liquid detection systems and equipped with on -site audible and visual warning devices with battery backup. Vapor detection systems shall sound an alarm when the system detects vapor that reach or exceed 25 percent of the lower explosive limit (LEL) of the liquid stored. Vapor detectors shall be located no higher then 12 inches above the lowest point in the vault. Liquid detection systems shall sound an alarm upon detection of any liquid, including water. Liquid detectors shall be located in accordance with the manufacturer's instructions. Activation of either vapor or liquid detection system shall cause a signal to be sounded at an approved, constantly attended location within the facility serving the tanks or at an approved location. Activation of vapor of vapor detection systems shall also shut off dispenser pumps. IFC: 3404.2.8.12 Liquid removal. Means shall be provided to recover liquid from the vault. Where a pump is used tp meet this requirement, the pump shall not be permanently installed in the vault. Electric -powered portable pumps shall be suitable for use in Class I, Division I locations, as defined in the ICC Electrical Code IFC: 3404.2.8.13 Normal vents. Vent pipes that are provided for normal tank venting shall terminate at least 12 feet above ground level. IFC: 3404.2.8.14 Emergency vents. Emergency vents shall be vapor tight and shall be allowed to discharge inside the vault. Long -bolt manhole covers shall not be permitted for this purpose. IFC: 3404.2.8.15 Access way. Vaults shall be provided with an approver personnel access way with a minimum dimension of 30 inches and with a permanently affixed, nonferrous ladder. Access ways shall be designed to be nonsparking. Travel distance from any point inside a vault to an access way shall not exceed 20 feet. At each entry point, a warning sign indicating the need for procedures for safe entry into confined spaces shall be posted. Entry points shall be secured against unauthorized entry and vandalism. IFC: 3404.2.8.16 Fire protection. Vaults shall be provided with a suitable means to admit a fire suppression agent. IFC: 3404.2.8.17 Classified area. Page 12. The interior of a vault containing a tank that stores a Class I liquid shall be designated a Class I, Division I location, as defined in the ICC Electrical Code. IFC: 3404.2.8.18 Overfill protection. Overfill protection shall be provided in accordance with section 3404.2.9.6.6. As you can see by the codes, its almost impractical to put a tank inside a building or enclosure. The cost for the engineering, monitoring and detection equipment, fire protection, ventilation and electrical would be quite high as compared to an outside tank system. Keep in mind these are just the fire codes, there are other federal and state regulations that do apply to storage tanks being placed inside. Also your insurance carrier may have special guide lines that you will need to follow. INSTALLATION OF PIPING AND EQUIPMENT IFC: 3403.6 Piping systems. Piping systems, and their component parts, for flammable and combustible liquids shall be in accordance with this section. IFC: 3403.6.2 Design and fabrication of system components. Piping system components shall be designed and fabricated in accordance with NFPA-30, chapter 3, except as modified by this section. NFPA-30: 27.1 Scope. NFPA-30: 27.1.1 This chapter shall apply to the design,installation,testing,operation, and maintenance of piping systems for flammable and combustible liquids or vapors. Such piping systems shall include but not be limited to pipe, tubing, flanges, bolting, gaskets, valves, fittings, flexible connectors, the pressure -containing parts of other components such as expansion joints and strainers, and device that serve such purposes as mixing, separating, snubbing, distributing, metering, controlling flow, or secondary containment. NFPA-30: 27.7 Testing of piping systems. NFPA-30: 27.7.1 Initial Testing. Unless tested in accordance with the applicable sections of ASME B31, Code for Pressure Piping, all piping shall be tested before being covered, enclosed, or placed in use. NFPA-30: 27.7.1.1 Test shall be done hydrostatically to 150 percent of maximum anticipated pressure of the system or pneumatically to 110 percent of the maximum anticipated pressure of the system, and the test pressure shall be maintained for a sufficient time to conduct a complete visual inspection of all joints and connections. NFPA-30: 27.7.1.2 In no case shall the test pressure be less than 5 psig measured at the highest point of the system, and in no case shall the test pressure be maintained less than 10 minutes. Page 13. IFC: Section 3405 Dispensing, Use, Mixing and Handling. IFC: 3405.1 Scope. Dispensing, use, mixing and handling of flammable liquids shall be in accordance with section 3403 and this section. Tank vehicle and tank car loading and unloading and other special operation shall be in accordance with section 3406. IFC: 3403 General Requirements IFC: 3403.1 Electrical. Electrical wiring and equipment shall be installed and maintained in accordance with the ICC Electrical Code. IFC: 3403.1.1 Classified locations for flammable liquids. Areas where flammable liquids are stored, handled, dispensed or mixed shall be in accordance with Table 3403.1.1. A classified area shall not extend beyond an unpierced floor, roof or other solid partition. The extent of the classified area is allowed to be reduced, or eliminated, where sufficient technical justification is provided to the fire code official that concentration in the area in excess of 25% of the lower flammable limit (LFL) can not be generated. IFC: 3403.1.2 Classified locations for combustible liquids. Areas where Class II or III liquids are heated above their flash points shall have electrical installations in accordance with Section 3403.1.1. Exception: Solvent distillation units in accordance with Section 3405.4. NFPA-33: Chapter 6 Storage, handling, and distribution of flammable and combustible liquids 6.1 General. Storage, handling, and mixing of flammable and combustible liquids shall meet all the applicable requirements ofNFPA 30, Flammable and Combustible Liquids Code. Storage, handling, and mixing of flammable and combustible liquids at process areas shall also meet the requirements of this chapter. 6.2 Storage in Process Areas. 6.2.1 There shall be not more than three approved flammable liquid storage cabinets in any single process area without the approval of the authority having jurisdiction. Storage cabinets shall be listed or shall be designed and constructed to meet the requirements of NFPA 30, Flammable and Combustible Liquids Code. Any single cabinet shall contain not more than 120gal (454 L) of Class I, Class II, or Class III liquids, of which not more than 60gal (227 L) shall be Class I and Class II liquids. 6.2.2 The quantity of liquid located in the vicinity of spraying operations, but outside of a storage cabinet, an inside storage room, a cut-off room or attached building, or other specific process area that is cut off by at least a 2-hour fire -rated separation from the Page 14. spraying operations, shall not exceed the quantity given in either (1) or (2), whichever is greater: A supply for one day 25 gal (95L) of Class IA liquids in containers, plus 120ga1(454L) of Class IB, IC, II or III liquids in containers, plus 2 portable tanks each not exceeding 6600gal (2498L) of Class IB, IC, Class II, or Class IIIA liquids, plus 20 portable tanks each not exceeding 660 gal (2498L) of Class IIIB liquids. 6.2.3 The quantity of flammable and combustible liquids located in a spray area or in a mixing room adjacent to a spray area shall meet the requirements of Section 6.3. 6.3 Mixing 6.3.1 Dispensing or transfer of liquids from containers, mixing of liquid, and filling of containers, including portable mixing tanks and "pressure pots", shall be done only in a mixing room or spray area. 6.3.2 Mixing rooms shall meet all of the following requirements: The mixing room shall meet the construction requirements of Section 3.1. The mixing room shall not exceed 1502 (14m2). The mixing room shall be designed to contain a spill of the contents of the room. The mixing room or a spray area used for mixing and dispensing operations shall be provided with continuous mechanical ventilation capable of providing not less than 1 c&n of air movement per ft2 (0.3m3/m m2) of floor area or 150cfm (4m3/min), whichever is greater. The ventilation system shall be in operation at all times. Dispensing and mixing rooms shall be classified, for purposes of electrical area classification, the same as enclosed spray booths, in accordance with 4.3.4. The mixing room shall be provided with an approved automatic fire protection system that meets all applicable requirements of Chapter 7. The mixing room shall be provided with portable fire extinguishers located in accordance with NFPA 10, Standard for Portable Fire Extinguishers. Exception: See 6.3.6 6.3.3 The amount of liquid in a single spray area shall not exceed 60gal (227L). 6.3.4 Where a separate mixing room is provided and the mixing room is located within 6ft (1830mm) Of an adjacent spray area or areas, the combined quantities of liquids located in the spray areas and the mixing room shall not exceed 120gal (454L), as shown in Figure 6.3.4(a) and 6.3.4(b). Exception See 6.3.6 6.3.5 Where a separate mixing room is provided and the mixing room is located 6ft (I830mm) or more from an adjacent spray area or areas, the quantity of liquid permitted Page 15. in the mixing room shall not exceed 2gal/ft2 (80L/m2), up to a maximum of 300gal (1135L), as shown in Figure 6.3.5. Exception 6.3.6 6.3.6 Where the quantities of liquids required or the floor area necessary to provide a suitable mixing room exceeds the limits specified in 6.3.2 through 6.3.5, the mixing room shall meet all applicable requirements ofNFPA 30, Flammable and Combustible Liquids Code. 6.4 Distribution Systems —Piping 6.4.1 Piping systems that convey flammable or combustible liquids between storage tanks, mixing rooms (paint kitchens), and spray areas shall be of steel or other material having comparable properties of resistance to heat and physical damage. Piping systems shall be properly bonded and grounded. 6.4.2 Piping systems within the spray area shall be of steel or material having comparable heat and physical resistance where possible. Where tubing or hose is used, a shut-off valve shall be provided on the steel pipe at the connection. 6.4.3 Tubing or hose shall be inspected and replaced as necessary. Replacement tubing or hose shall be that recommended by the equipment manufacturer. 6.4.4 Where a pump is used to supply the liquid used in the spray application process, piping, tubing, hose, and other accessories shall be designed to withstand the maximum working pressure of the pump, or means shall be provided to limit the discharge pressure of the pump. 6.4.5 Where a pump is used to supply the liquid used in the spray application process, an automatic means shall be provided to shut off the supply of liquid in the event of a fire. When pressurized tanks larger than 5gal (19L) are used to supply the liquid used in the spray application process, an automatic means shall be provided to shut off liquid flow at the tank outlet in the event of fire. 6.4.6 All pressure tubing, hose, and couplings shall be inspected at regular intervals. With the hose extended, the hose and couplings shall be tested using the "in-service maximum operating pressure." Any hose showing material deterioration, signs of leakage or weakness in its carcass or at the couplings shall be replaced. 6.5 Distribution Systems —General 6.5.1 Liquids shall be transported by means of closed containers, approved safety cans, or approved portable tanks, or shall be transferred by means of a piping system. Open containers shall not used for moving or storing liquids. 6.5.2 Wherever liquids are transferred from one container to another, both containers shall be effectively bonded and grounded to dissipate static electricity. Page 16. 6.5.3 Containers that supply spray nozzles shall be of the closed type or shall be provided with metal covers that are kept closed. Containers that do not rest on the floor shall have supports or shall be suspended by wire cables. Containers that supply spray nozzles by gravity flow shall not exceed 10gal (38L) capacity. 6.5.4 Original shipping containers shall not be subjected to air pressure for supplying spray nozzles. 6.5.5 Containers that are pressurized to supply spray nozzles, air storage tanks, and coolers shall comply with all applicable requirements of the ASME, Boiler and Pressure Vessel Code, Section VIII, for construction, tests, and maintenance. Exception: The following need not meet the requirement. Pressure containers less than 6in (150 mm) in diameter Pressure containers that operate at less than 15 psig (gauge pressure of 103kpa) Siphon -type spray cups 6.5.6 If a heater is used to heat the liquid being sprayed, it shall be low-pressure steam, low-pressure hot water or electric. If electric, it shall be approved and listed for the specific location in which it was used. (See Chapter 4) Heaters shall not be located in spray booths or other locations subject to the accumulation of deposits of combustible residue. Agitators, if used, shall be driven by compressed air, water, low-pressure steam or electricity. If powered by an electric motor, the motor shall meet the requirements of Chapter 4. NFPA-33: Chapter 15 Styrene Cross -Linked Composites Manufacturing (Glass Fiber Reinforced Plastics) 15.1 Scope. This chapter shall apply to manufacturing processes involving spray application of styrene cross -linked thermoset resins (commonly known as glass fiber reinforced plates) for hand lay-up or spray fabrication methods, that is, resin application areas, and where the processes do not produce vapors that exceed 25 percent of the lower flammable limit. 15.2 Resin Application Equipment. The equipment and apparatus for spray application of the resin shall be installed and used in accordance with the requirements of Chapters 14 and 15. 15.3 Fire Protection. Resin application areas shall protected by an automatic sprinkler system that is designed and installed in accordance with the requirements ofNFPA 13, Standard for the Installation of Sprinkler Systems, for at least Ordinary Hazard, Group 2 occupancies. 15.4 Resin Storage. The quantity of flammable and combustible liquids located in the vicinity of resin application areas outside of inside storage room or storage cabinet in any one process area shall not exceed the greater of any of the following: A supply for one day: Page 17. The sum of 25gal (95L) of Class IA liquids in containers and 120gal (454L) of Class 1B, Class IC,II, III liquids in containers. One approved portable tank not exceeding 660gal (2498L) of Class IB, IC, II or III liquids. 15.5 Electrical and Other Hazards. 15.5.1 Electrical wiring and utilization equipment located in resin application areas that is not subject to deposits of combustible residues shall be installed in accordance with the requirements ofNFPA 70, National Electrical Code, for ordinary hazard locations. 15.5.2 Electrical wiring and utilization equipment located in resin application areas that is subject to deposits of combustible residues shall be listed for such exposure and shall be suitable for Class I, Division I or Class II, Division I locations, whichever is applicable. Such wiring and utilization equipment shall be installed in accordance with the requirements of NFPA 70, National Electrical Code, for the hazardous (classified) location involved. 15.5.3 All metal parts of resin application areas, exhaust ducts, ventilation fans, spray application equipment, work pieces. or containers that receive the spray stream, and piping that conveys flammable or combustible liquids shall be electrically grounded. 15.5.4 Space heating appliances or other hot surfaces in resin application areas shall not be located where deposits or residues accumulate. 15.6 Ventilation 15.6.1 Mechanical ventilation shall be designed and installed throughout the resin application area in accordance with the requirements of Chapter 5. Exception: Buildings that are not enclosed for at least three-quarters of their perimeter shall not be required to meet this requirement. 15.6.2 Local ventilation shall be provided where personnel are under or inside of the work piece being fabricated. 15.7 Use and Handling 15.7.1 The storage and use of organic peroxide formulations shall meet the requirements of Chapter 14. Also see NFPA-1 UFC 2003 Chapter 70 Oxidizers & Organic Peroxides. This chapter is for the storage, use and handling of solid and liquid oxidizers or organic peroxides. You may also need to see IFC chapter 39 Organic Peroxides and IFC chapter 40 Oxidizers. 15.7.2 Excess catalyzed resin, while still in the liquid state, shall be drained into an open - top, noncombustible container. Enough water shall be added to the container to cover the contained resin by at least tin (51 mm). Page 18. 15.7.3 In areas where chopper guns are used, paper, polyethylene film, or similar material shall be provided to cover the exposed surfaces of the walls and floor to allow the build- up of over chop to be removed. When the accumulated over chop has reached an average thickness of 2in (51 mm), it shall be disposed of after a minimum curing time of 4 hours. Exception: A single day's accumulation of more than an average of 2in (51mm) shall be permitted, provided that it is properly cured and disposed of before operations are resumed. 15.7.3.1 Used paper, polyethylene film, or similar material shall be placed in a noncombustible container and disposed of when removed from the facility. Resin Pumping Systems: IFC: 3405.2.1 & NFPA-30 18.3.5 Pumps. A positive -displacement pump shall be provided with pressure relief discharging back to the tank, pump suction or other approved location, or shall be provided with interlocks to prevent over pressure. 1. We install cast iron positive -displacement gear pumps with pressure relief discharging back to the pump suction. These are electric pumps that are made for Class I locations with overloads and thermal interlocks. 2. An air -operated diaphragm pump does not meet IFC: 3405.2.1. Also with the way Fire Marshall's are reading the codes, many states have ruled that this type of pump: In a fire 1. The diaphragms and exhaust vent melt, which will allow the material to feed the fire. 2. The air in which operates the pump can add to that fire. 3. Although under UL specification 79 they have this type of pump on portable fuel tanks for small equipment, they are not meant to be used on bulk storage tanks. 4. Even if you put a thermal safety valve on before the pump, because of the fact that the way polyester resin does polymerize it will stick open and will let the resin pass -by to feed the fire. 5. Code of Federal Regulations Title 29-Labor: CHAPTER XV1I--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR PART 1910--OCCUPATIONAL SAFETY AND HEALTH STANDARDS (iii) Transfer. (a) The transfer of large quantities of flammable or combustible liquids shall be through piping by means of pumps or water displacement. Except as required in process equipment, gravity flow shall not be used. The use of compressed air as a transferring medium is prohibited. (b) Positive displacement pumps shall be provided with pressure relief discharging back to the tank or to pump suction. Page 19. What about the Grandfather Clauses? We all know the genesis of the term "Grandfather" as it relates to codes and standards. The "Grandfather" clause is a phase used in code terminology that speaks to a condition existing before or at the time a requirement is enacted that allows that condition to exist without mandating compliance. Unfortunately, the fact that any number of these changes cited can and do create hazardous or unsafe conditions in a systems we once thought were state of the art in terms of fire protection. Let's understand one thing right from the start, "Grandfather" clauses were never meant to allow unsafe conditions or circumstances to exist in any system that would put the life of workers or occupants at risk regardless of its age or how long it has been in service. The problem arises when we recognize that a hazard does exist, and understand that something needs to be done about it. Waiting for a tragedy to become the impetus for these changes is not an option. So if you think you might be in this type of circumstance, please have an inspection so that problems can be identified and take the necessary action to correct the problem. The definitions of "flammable liquid" and 'combustible liquid" in NFPA 30 differ from those used by the U.S. Department of Transportation. Why? Definition and classification of flammable and combustible liquids are addressed in Section 1.7 of NFPA 30. A flammable liquid is defined as a liquid whose flash point does not exceed 100°F, when tested by closed -cup test methods, while a combustible liquid is one whose flash point is 100°F or higher, also when tested by closed -cup methods. These broad groups are further classified as follows: • Class IA - Flash Point less than 73°F; Boiling Point less than 100°F • Class IB - Flash Point less than 73°F; Boiling Point equal to or greater than 100°F • Class IC - Flash Point equal to or greater than 73°F, but less than 100°F • Class II - Flash Point equal to or greater than 100°F, but less than 140°F • Class-IIIA - Flash Point equal to or greater than 140°F, but less than 200°F • Class IIIB - Flash Point equal to or greater than 200°F Notice that boiling point is only used to distinguish between ClassIA and Class IB. Class IA liquids are extremely volatile, but there are few liquids that are so classed. Note also that, theoretically, there is no upper limit to Class IIIB. These definitions and classifications were agreed to years ago by NFPA, the U. S. Department of Transportation (DOT), and the U. S. Occupational Safety and Health Administration (OSHA) in an attempt to remove inconsistencies in the definitions Page 20. used at the time. Since then, DOT has changed its definition of "flammable liquid" by raising the upper limit to 141°F (60.51C). This was done because the United States is a partner to a world-wide set of hazardous materials regulations sponsored by the United Nations and must use the UN definitions, at least for international transportation. Note, however, that DOT regulations include a so-called "domestic exemption" that allows a shipper to redesignate as a combustible liquid any liquid whose flash point is in the NFPA Class II range and which does not meet any other hazardous material definition. Just remember Authority Having Jurisdiction can rule on any and all of these codes. So if you are given a variance, make sure that it is done in writing. These are just some of the key regulations and statutes that we use to insure that our systems are up to code. Please remember to consulate not only your state Fire Marshall, but also your insurance carrier, and any other agency that may have regulations for aboveground storage tanks in your area. We have a list for each states ASTs to help owners and operators understand the related technology, federal and state regulations, codes and standards and related issues with storing and handling polyester resin. Also you should read the Code of Federal Regulations Title-29 Part-1910.106, these codes are the ones for Flammable and Combustible Liquids and Title40 Part-112, these are the code for Protection of Environment and Applicability, Definitions, and General Requirements for All Facilities. For your reference with these codes and regulations, copies can be obtained from the following: IFC: (International Fire Code) 800-2144321 NFPA-30: (National Fire Protection Association) 800-344-3555 Page 21. CIPP Bulk Resin Installations Insituform - Bessemer, AL Insituform - Cedar City, UT 0 v 0 r >a µ X", F i Moore Construction - Clarksville, TN Lanzo Lining - Roseville, MI M 0 Michel's Corporation - Brownsville, WI Kenny Construction - Bedford Park, IL Insituform - Kapolei, Hawaii Insituform - Ocala, FL Sun Coast Infrastructure - Florence, MS LMK - Ottawa, IL Mri State Utilities - Chesapeake, VA United Survey - Cleveland, OH Veolia ES Canada - Quebec, Ontario Canada Masterliner Inc. - Hammond, LA Mark XXV Bulk Resin Storage Tank Data Sheet Inside Dimensions: 7'x7'xl6'6" Surface Area: 550Sq./Ft Outside Dimensions: 8'-11"x8'-3"xl8'-3" Insulation: 3,300 Board feet Capacity: 5880 Gallons Heat Loss/Gain @ 100 Deg. F TD: 1100 Btu/Hr 784 Cu/Ft Weight: 6.5 Tons 1) Storage tank and all accessories do comply with NFPA 30 and API 650. These tanks are made to store liquid resin that is a Class I—C flammable Liquid with specific gravity of 1.1 to 1.4. 2) The tank will be fabricated from carbon steel A-36 plate & to be all welded construction. 3) Tank will be covered entirely with 6" of insulation with 29 gage bone white Tuff Rib sheeting over the insulation. 4) Inside of tank will be sandblasted white and coated with two coats of "PSE" heavy- duty epoxy tank coating. 5) Tank comes standard with 14" flange on front for discharge, 44" & 2-2" flanges on top for filling, vent and return lines. 2-2" front flanges for the heat exchanger coils hook-up. 6) This system come with 1-2 inch vent that is a Morrison Brothers 2 inch double outlet vent #155 and 1-8 inch emergency vent that is a Morrison Brothers 8 inch pressure and vacuum relief #143-A. 7) The storage tank's fill and return piping will be installed as per NFPA-30 Section 2.3.2.5.4. 8) Tank is agitated with a 42" axial flow turbine blade with a 6" blade width. The drive on this unit will move this blade at 50 RPMs. 9) Tank has heat exchanger coils which are made from 320 feet of 2" SCH-40 / GRADE A / ASTM A53-120 pipe. These coils are also coated with the "PSE" heavy-duty epoxy tank coating. 10) This tank system also come standard with load cell mounting. e � 2 c ♦e+ pe k� � n +`gaaGGd®•iG�� p ,1 J�� NJR industries. Inc. I""hi I 1300 Wafter Smith Road MobJe, Alabama 36695 Tank Drz ing r A m y iL p a E K e D i ^ R^ g £pp a 1g 22'd 3 �� y P.i a b gggg� �Z SI a n z i t y8,N�$3m �gZy719 � �a y�t g�yg tlP gN�R Sgg= i� 3iy A 19Y71 3 G2 �� Fri R_ N N i d tl ri tl 6 — ej rt a5 'C ad� o �+ a a o ! s F F c F J 4 r 6 � s 3 C � "tl 4Fi A A i u 0 J Z w u i lv�ll vsn Sf69E'Id'av>!d uad 51-61-10 CMG euul r�r-,1 5699C vwvge.jV ry •al!gayy.q.N � pua quws 1011%00CI a Feld 1 `Y ¢nAI xM ONx.aA rm O mm1x� DQa�RP N.L� Y tlbna Wll� O TOP LAYOUT A�NSOTES� r PA[ IVA v.• . e I' gPMW 1y'ii'lip° s/ i PW 1N501°Om�N ro Pc rAamulm u rrn R �iq c� �vnR sn 2 iK iA4V IS r���LIiO iMl A-b tlABdI SIRE RAIE M'p 6 O �ER .VML I{Rpn�mRp�y pO`l��y�y �Sg1�p� 1 pASS 1. C RNNIHL SIIAE IRm INA� • sEGf1R? 6 1.11D 131 nE FLAT PAR PLATE `' w cLeoc�wrz iirl"wpyYe'��Ipa�Erl°sWR"'Ina Aro({�M(tp/x vY NIARGED DETAIL ''AA ' MR 6 �DRs sla�w R hODD'IIAm MmtrzIIMM cure nIAYuFmW i rtP i.NA) IJ�U .°dwu urx gR PAD EYE ARMS FRONT ELEVATION 4 M r rs T 15 A WM HIInN6 As P T NRA-b RLna zu1 t. z IWP�a�I�W Is A,,rj A . a1Rr wlr P. A VAWDY PI EMLIl}ARABWa PPFSIC AND ]. M LAM 6161m AT m PRA-]D SEt D1 6 W 1/.V(5 iLL AIO I P 6 PP I6PA-b YCItl1 24A,. 1r i 5Artry[I-R—K lke YSC A SIER W V4H lPRD aT ME. H i. P. 2,1A rAVP ML PAVE all81LL PIS�IIIdI AS PLP MPM]II ]I.]. ME lYK NAK LDI➢ 0L5'MM .WIIIY nYr YUND AT °M V GPASry 16 NL W p1i. IpL S A-M W0M . A r5N AIID gS1AL[D AS rFR ISPA-$D sFCMN z] a ALi B)1. It ON �m(2)) M. Ivw R�EW rua� Na M r ER M MP T AI9'A'M a AND POWD ME PE'A' .. I" W DE MPEP W-. ra u. N A wsa 4 MW D lOCA1KK1. IS ALL WA-b CRkS .1fS PRW 11¢ St® aQ BWt TANK DATA a"'mDmOwn:lac� •TM u an rwn sAR 9 ^ � a o a aaaR.a.a N vm.Atu .• u. a RTC A-2 of 12 DD>a I� D 4 I(< Ir< r � mix — rov[v�IlmWo— ti 4 Im.mmw�m,R� L raW[r�ll rw un mu — L O FOUNDATION PLAN .'K- to �Yn�mj�� aim F uM i�i¢dW m�m�rzY m alv DRAIN DETAIL A DRAIN DETAIL 8 PIPE BOLLARD DETAIL (IF NECESSARY) NOTES, 1.) CONCRETE IS TO BE 3000 PSI. 2) CONTRACTOR TO ENSURE THAT FOOTING OEPIH BE BMW MOST LINE FOR THE AREA, TO PRESENT HEANNG OF SLAB DUE TO CROWD FREEZING 1) CONTRACTOR PROVIDE (Z) DRAINS AS 9 Offi IN DETAIL a1STWEA TO DETERMINE LOCATION. I.) ALL CONCRETE WORK IS TO BE DONE IN ACa]RDANCE VOTH Aa STANDARDS G) LOAD CE115 TO 6E INSTAllEO USING REDHEAD ANCHOR BOLTS AS REWIRED. 6.) CONCRETE "lL BE AS STET k L£ AS POSSIBLE. {y F H �s �tl o E C m L 6 ��TT,l1I 4 CIII ra 11 W.- TYPICAL GRADE BEAM A-3 of 12 PROPERTY LINE aI I mill Nili h - =Hni HH 1HE INE" 1, i i2 FF)pl lil - — — — — — — — — — — — — --- — — — — — — — — — — — — — — — — — — - i PROPERTY LINE NOTES 1, STORAGE TANK AND An ACCESSORIES TO BE FABRICATED AS PER 7. THE TANK IS TESTED AS PER NMA-30 SECTION 4.4.2.1. NFPA-30, IFC-2000 AND API-650 APPENDIX J. 6. AS PER NFPA-30 4.3.2.5.4 THE FILL AND RETURN UNES WILL 2. THE TANK IS FABRICATED FROM A-35 CARBON STEEL PLATE AND IS TERMINATE 6 INCHES OF THE BOTTOM OF THE TANK. ALL WELDED CONSTRUCTION, 9. ALL RESIN PIPING WILL BE GRADE A CARBON STEEL ASIM A53 120 3. THE POLYESTER RESIN THAT WILL BE STORED IN THIS TANK IS A AND INSTALLED AS PER NFPA-30 SECTION 5.1.1. SYSTEM WILL BE CLASS 1, C FLAMMABLE LIQUID WITH A SPEcHnC GRAVITY OF 1.10 TESTED AS PER NFPA-3D SEC. 5.6.1. TO 1.25. SEE SEC. 1.7 OF NFPA-30 FOR DERNMON. 10. AS PER NMA-30 4.3.2.2.1 SHELL TO SHELL SPACING BETWEEN TANKS 4. THE TANK IS COVERED WTH 6 INCH OF INSULATION AND WITH NOT OVER 150 FEET IN DIAMETER THAT IS A HORIZONTAL TANK IS 1/6 29 CAGE BONE WHITE TUFF RIB SHEETS. X THE SUM OF THE ADJECENT TANKS DIAMETER BUT NOT LESS THAN 3 FEET. ti 5. STORAGE TANK WILL HAVE SECONDARY CONTAINMENT AS PER 11. AS PER NFPA-30 4.3.2.1 LOCATION WTH RESPECT TO PROPERTY UNES, PUBLIC WAYS, AND IMPORTANT BUILDINGS ON SAME PROPERTY. USING NFPA-30 SEC. 4.3.2.3 AND THE lFr TABLE 4.3.2I.I(A) IN NFPA-30 FOR A STABLE UOUID MTH AN OPERATING PRESSURE OF 2.5 PSIG OR LESS FOR HORIZONTAL TANK WTH EMERGENCY 6. THE TANK IS EQUIPPED WTH VENTING AS PER NFPA-30 SEC. 4.2.5. RELIEF VENTING TO LIMIT PRESSURE TO 2.6 PSIG AND PROTECTION OF NONE 1. 2 INCH VENT IS A 2 INCH DOUBLE OUTLET VENT 9 165, THIS STATES TO USE 2 TIMES TABLE 2.3.2.1.1 TbFOR MINIMUM DISTANCE IN n 2. 8 INCH EMERGENCY VENT IS A 6 INCH FEET FROMPROPERTY UNE THAT IS OR CAN B UILT UPON, INCLUDING THE OPPOSITE SIDE OF A PUBLIC WAY. AND SHALL NOT BE LESS THAN 5 FEET. PRESSURE AND VACUUM RELIEF # 143-A. ALSO USING TABLE 4.3.2.1.1(8) FOR THE MINIMUM DISTANCE IN FEET FROM THIS TANK IS AN ATMOSPHERIC TANK AS PER NFPA-30 13.41.2 NEAREST SIDE OF ANY PUBUC WAY OR MOM NEAREST IMPORTANT BUILDING ON THE SAME PROPERTY AND SHALL NOT BE LESS THAN 5 FEET. IF YOU Y THE WORKING PRESSURE OF THE TANK IS IwO PSIG MEASURED AT REFERENCE TABLE 4.3.2 tff USING A STORAGE TANK WTH A CAPACITY U THE TOP OF THE TANK. EED TO % 30 FEET MOM THE PROPERTY �IMJUUONS Y D 751 TO 12a,00 U V% NEAREST LINE AND IN U DISTANCE FROM NEAREST I PORTANT BUILDING ON THE SAME PROPERTY IS A DISTANCE OF 5 FEET. WE EXCEED THESE DISTANCES. 12. ALL ELECTRICAL EQUIPMENT AND VARE IN AND ROUND THE RESIN A-4 STORAGE TANK WU- BE AS PER NEC-70 FOR USE IN A CLASS 1, 12 DIMSION It, GROUP D LOCATION. of tv m " --------'- 9F ti-T Eat i-T lt y t z i, II II .i I it ,i ii 11 ii '1I II 9� ] g F g� _ pp P p SEA- b�• R�"' F�- P ° rr�..uPs ^ L—sews � gg 4 P• Y " � { I�`_^`I L- L=®— J Y q , $ -� m ggss F" m Y„ p55 ; 1 I j44. L ti <�E E a sa s •fl `s N �SxF f✓ €�: bag be F °A - - 1: � In All R ^? C E • a a a CF5 LJ LJ LJ LJ � C N EF EP EF E_ _ : IFS cc Fq Ri ty pi cc NJR Industries. Inc. Cuswmm v i{' DFYYI ]I�' � a`I�Y 130 wgwsmiWRoad 11�� 1683Fef a oTmee 4 4 I I T5I A f Y � } �� 366v5 l Ave p1 *112I1pII i• fl D e g a g y 4$ A n P=el Da D w:0 .2n 1 OrnvmB Da4: o1-20.15 4945 USA F.PmBNumbe�r. A S 1-+ Dn G 0 m YIIRING LEGEND IANt 1 IeAowi ] E A -- 6 P lAb(]PEMWi NI 1S IIBjG(IL x ]0300 Z�m mm irw� �- INTERFACE BOX +^ nL P "] "IF-1" wAr awxL¢mn. m] 1] A - IILL�VIA I NIA PYYP V yAy)iva 1} WI p. —vax�m fAlf-] 11 FI P ] m—wn Ma.a WI -] .9"v7.w .YawiID. LOAD CENTERag iANxeIeAWO Cu1WW my 6 e plLf sEN J N LxX 2 CCQINO W1111Q ImI I �• CQ f-1 yam. h`E V u �O�a®®Da®0®®9 - � a lam. IC'W�`��• Y Ay SI ° N $u LCGPNIA AS FIX NEC-)4 iH A YA59 4 qN§W Y. qWY 4 q T fi t g 2 aUSC 4L WIC-RLV] [I[CIA VL aM4ATC iql MI] YNL. (Tj� `� ® � L ^ L H 6� 21NpWlo w M LaAO Qlli m INE NduRN SNW➢ @ IYAm N i°n m Cmi¢'OlaoiAnul IA ra. sENY mw ra M0'l. M ...Oq' ]AlIp11RW M LOI➢ CD].[ IIW LM M - [iRIAT4V m dC - CLNS EPW ra NPNTNE YiM M 9AOt - Ekp1AIXx IPIY lXC lo/h mLS YNOM INX nE � 9qY ]Rp1 M P01GCW io M 1{Nm'MiE EPtlI nE LOAO h INE- aGN0.1AW M /SSA1W m ra wm r]e raL4Ymz ! µ� YfOh --•TTT ��•PPP +]p YP]F Y8} Tip "TT ��TT INNI4 mW N-lOi xmulm ro ra uanw Lvn Wsr � PAh a uNw v Cbol]A �, �� � P WN EKEEDZNIi m1FFl AWE Im LanM TM ICI 141 Im In n'S m 6ELIIE6W9 91CYD � GR6YL N MIWI4 ra mlY m ra .rmSln�aNplrox mms Pva rs Wtt w a ira m]s Aro cW Ic 'S C y � � -� Itt /.lYa wRNli .Nd 120VAC O S Aw 6 N w wci NEAT SENW tt N x mx OOIS lxC]E aLL Nun m eC Yaem a r211uu umE uxa ON.00 Aceo..A roe. unl EExsoP slArsuwi rrls ns oNN LNI� "OUTSIDE OF CONTROL PANEL" "INSIDE OF CONTROL PANEL" � a 3 l g c 60MN S]iEry S1NIw6 ISW Pm B/ OMFA IOCY f4iES 911LL fe NPIn9® 91' Mlxl[R Al U A— 6. t OLCIW INMN° VI °E OWE M SM OM W L N NEC. ]. ALL LIECIPNJL {NfiHE aINL 9E ME a Eo N1 NO YAPE ro SE Vsm. n. MC L°.b ILNRA N9L /L•p pprFp M ISO aLX p]i12AR h M SCAIIt VI. IISD IN VE I V of 12 Pu yJ MAY�xV. vXh[ 14 w Vii 9 17 w •1 Alq 1 ANI uIMKI vJP 1 uiuKT z EwK p m RJo I µy a >' • 1�-'I rd911 i , W1K J f 3`, 1`�F4``I I w 1 _j B LIYIA-T ` e pRAP E-I WIW ] 9I1 e l t��fU-f RI 11y[p tlWlj Jp P]IM WI XI A YA'R f3'Mn .1; 2 NwxN �/Mrz 1 a 34 IS e m CON31Pa fAB-1 103-1 ql-1 Rn-1 °W` M a z m Io ] • 1• 1 u 1. IIµRLKEI 01-1 a E n a i En•-] EAN-a z Sx fd 111 2 11 ] MIR0. 8 p3-1 9 6 =1 E c INo CAiµKI 1 a 1• J ] MME_mme I 1 rz R • WAL INNI � B6 qIS I ] C NO • R x Ila 1• ] PMS9IRE W-1 I W]-1 plµµJ$i 9NIiBANtE Ilx II3 J 6 I• 1 I i OIo-1 R 3 1 I p 3 XI I I NAlll/ U. n0 R4-]I PoJ-• g13-I 1• A] 125iN SOIORBµ[E 1 z 1 a O 5 Me-1 B h XIJ S Xl q�T µAGx NMl EpSM� _ 5�1 J1• I °�0 ] p5NR8.UIQ `®o ®o n oo m o a a ®®®®®®a l o u s 1. M mP W Y1ME NEED M K EEi M AI33 . 0008: F. T. 2 OdJ= Po"Y RM C" W A 1Wt Mn a Nv11 WEAR IMER Po"YN J. Ed1NFERq AS EXENN. (EPEEO VOIf 1 m ME Y u]E x umgiMtlllLS YW .. •. M MO PJa ME ME xI. FqE K JNICIES 6 Al IS ME WT CHIMES ON ME WM WAY VµW FOR ME CATC O. RN 13 ME LNR WTWM ON ME MOM WAY VNK FM ME RM% J. MS wW13 x AgA. I. gVOM a. MOJPO L YW 3. IPE µARK .-OP. YYS NEED iO M IINNIM A NO SET OF CMIA RING LEGEND A-7 of 1 ) " ; | _ r• ;�� - ---- —/ i -� WIRING LEGEND n ,.—wvuiw Hu.—>w.ue .. �wuru.aamncrs IF-1 BY OTHERS CCP FU1 C1 COMPRESSOR Ng M -1 -- ----- -- ------- 3 ..—...�. f•�vo. Mnx HENAKTER�qSE FAN FU3 M 2 ° —wmna Xi PRIMARY: 230/208 VAC SECONDARY: 24 VAC CCP IF-1 IF-1 CCP FU4 " CCP IF-1I IF-1 CCP 3 -------1`-J3 ------- 4 P51 a C1 - a TS1 SOLI S g z C 4 a ti C y � a 1 HP •° IF-1 BY OTHERS FU2 WATER PUMP ,r y m� v A m r CCP a 11 ------- 8 CG 3 r o o 2-- ---✓�-- '�'�-- ------ 6 z x A A-9 of 12 14 I i H $ y $� sy ga � $;A s 4s;'p E" CHI O16 a: $ HAa FfF _ f v a dap bn Ali[ E If t� I a �6 E66g $ ggt IRA $ 5?g �E £ !a §a 1 aaaF E I A Fag it 8 Fe MIN ® ® ® ® 0 f T C _T G N N F F F 1� RESIN MIXER Resin Tank 1 All inside resin piping in your plant must be ran in 2 inch grade A schedule 40 carbon steel pipe and all fittings and valves must be ether carbon steel or stainless steel. No brass or galvanized piping or fittings shall be used. Also all piping must be insulated with at least 2 inch of fiberglass pipe insulation. All outside piping must be heat traced, insulated with aluminum jacketing. We use the following: 1. Owens Corning ASJ Fiberglass Pipe Insulation 2. RPR Products Insul—Mate .024 Aluminum Jacketing 2 INCH FILL LINE 4 aw ti 3 INCH n[ "nw�R +^�� �2 INCH 8 INCH O O 8 INCH 2 INCH VENT VENT VENT VENT HEAT AGITATOR MANWAY MANWAY r� AGITATOR \ EXCHANGER DRIVE TANK R3 INCH cO @ �° / LINEN O Resin Tank 2 Resin Tank 1 All heat exchanger piping will be 1 Inch grade A schedule 40 galvanized piping, Insulated With at least 2 Inch of fiberglass pipe insulation with aluminum Jacketing. We use the following: 1. Owens Corning ASJ Fiberglass Pipe Insulation 2. RPR Products Insul—Mote .024 Aluminum Jacketing