APPLICATION INFORMATION
Permit Number: 1507-0077
PermitType: COMMERCIAL RENOVATION
REVIEW COMMENTS
scANNEU
BY
at. Lucie Count'
I
Owner(s):
Lakes Plaza LIc
Jurisdiction: ST LUCIE COUNTY
Lot#: P3-5 Block: 3
Stories: Automatic Sprinkler System? No
CONTRACTOR INFORMATION
Contractor Name:
Lloyd M Constant Fax Number:
Business Name:
Andros Roofing & Construction LIc
Email: Androsconstruction@Gmail.
Business Addr:
2706 Atlantic Ave Com
City / State / Zip:
Fort Pierce, FI 34947
REVIEWS AND COMMENTS
ReviewType
Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Audrey Humphrey 71612015
7/6/2015
Comment:
NEEDS A SUB AGREEMENT FOR ELECTRICAL.
7/6/2015
Comment:
NEEDS ASUB AGREEMENT FOR PLUMBING.
716/2015
Comment:
NEEDS A SUB SUMMARY.
7/6/2015
Comment:
NEEDS (2) ELECTRONIC VERSIONS OF PLANS (CID)
71612015
Comment:
NEEDS (3) SETS OF PLANS WITH THE 5TH ADDITION 2014 BUILDING CODES.
7114/2015
Comment:
MECHANICAL SUB AGRBE—MENT.
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Audrey Humphrey 71612015 71612015 71612015
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 812412015 8124/2015 8/24/2015
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Kevin Singley 8119/2015
8/19/2015
Comment:
ASSEMBLY AREAS, BREAK ROOM AMD RESTROOMS NEED TO COMPLY EWITH THE MINIMUM
VENTILATION RATES SET FOURTH BY 2014 FBCM, TABLE 403.3
8/1912015
Comment:
AHU#3 AND CU#3 ARE SHOWN ON PANEL SCHEDULES A, B, AND C / PLEASE MAKE CORRECTIONS
8/19/2015
Comment:
AHU AND CU #2 ARE NOT SHOWN ON PANEL SCHEDULES
1.
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
U
8/19/2015 Comment: INCLUDE CONDITIONED AIR REQUIRED FOR THE MECHANICAL ROOMS ON T& B
PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 811912015
8/19/2015 Comment: PLEASE REFER TO THE CORRECT CODE (2014)PLUMBING CODE
8/19/2015 Comment: THE PLANS YOU SUBMITTED ARE NOT SIGNED AND SEALED DOCUMENTS PLEASE RESUBMIT SIGN AND
SEALED PLANS 3 SETS
PLANS EXAMINER REVIEW INCOMPLETE Joe Ciclo 811912015
Comment: DESIGN PROFESSIONAL TO INCLUDE A CODE REFERENCE BOX ON PLANS AS TO CODES DESIGNED TO
THIS FACILITY WILL BE UNDER THE 2014 FLORIDA BUILDING CODE 5TH EDITION LIBRARY ] INCLUDE
8/19/2015 BUILDING, PLUMBING, MECHANICAL, ACCESSIBILITY, ELECTRICAL, ENERGY, LIFE SAFETY AND FIRE
CODES — CHANGES OF OCCUPANCY ARE GOVERNED BY FBC EXISTING BUILDING CODE, CHAPTER 10
NOT 9 ** ENGINEER TO MODIFY ALL NOTES ON PLANS REFERRING TO THE 2010 FBC TO 2014 FBC
8119/2015 Comment: THE PLANS ARE JUST COPIES AND NOT SEALED * ALL PLANS MUST BE ORIGINAL FORMAT, SIGNED,
SEALED AND DATED BY THE DESIGN PROFESSIONAL PER F.S. 471.025
8/19/2015 Comment: SUBMIT [ 3 ] COMMERCIAL ENERGY CALCULATIONS DESIGNED TO THE 2014 ENERGY CODES W/ MANUAL
N'S FOR THE EQUIPMENT DESIGNS
8119/2015 Comment: SUBMIT 2 PDF DISCS UPON RE-SUBMiTTAL
811912015
Comment:
DESIGN THE TIE DOWNS FOR THE EXTERIOR MECHANICAL EQUIPMENT PER FBCM 301.15
811912015
Comment:
DESIGN PROFESSIONAL TO INCLUDE AN INTERIOR FINISH TABLE ON PLANS FOR ALL INTERIOR FINISHES
PER FBC CHAPTER 8 [ SEE TABLE 803.9 ] 804.2 FOR FLOOR COVERINGS
8/19/2015
Comment:
SHOW THE FIXED SEATING AT 1 PERSON FOR 18- OF LENGTH [ SEE FBC 1004 RE -CALCULATE THE
OCCUPANTLOADS
8/1912015
Comment:
ENGINEER TO NOTE ON PLANS REGARDING THE ADDITIONAL LIVE AND DEAD LOADING IMPOSED ON THE
TRUSS B0170M CHORDS OF THE MECHANICAL EQUIPMENT
a/24/2015
Comment:
COMMENTS E-MAILED AS OF THIS DATE
ZONING REVIEW
COMPLETE Lydia Galbraith 711412015 711412015 7/1412015
Comment: