HomeMy WebLinkAboutPLAN REVIEW FORMSAINT LUCIE COUNTY FIRE DISTRICT GDHNNED
14
gu, 9
PLAN REVIEW FORM gy
5160 N.W. Milner Drive Into
Wf
�
Port Saint Lucie, FL 34983 .St•
"r
Telephone: 772-621-3322
9FUI5(P�
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept.
ISLC
FMO Permit#
IB-15-232
Project Name
Melanie's Tanglemasters Inc
BLDG Permit#
1507-0464
Address
6668 South US Hwy 1
City PSL
Contractor
Don Williems
Address
701 Hartman Road
City Ft Pierce
State
FL Zip 34947
Telephone
(772)519-0167
Architect/Engineer Paul Welch - Telephone (772)785-9888
OccupancyType Business Construction Type VB Square Feet 1200
Occupant Load 12 per plans Number of Stories Access Box Access Key Switch F
AFS Permit I FA Permit FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD Is required. The file format shall be.pdf only.
2. All revisions, Including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final Inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located Indoors within air conditioned space.
S. Plans and construction are subject to corrections In the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC systemis that exceed 2,000 ctm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2010 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
2. Provide portable fire extinguishers from a licensed contractor.
Page of 11
Reviewed by Tony Jerger Date 08/05/2015