Windload Calculations
For
SCANNED
Land Management BY
St. Lucie Countv
FBC 2014, 5t' Edition & ASCE 7-10
Wind Speed 160 MPH @ 3 second gust
Exposure C
Internal Coeff:O
Prepared by:
FILE
UOPY
Daniel P. Retherford
1402 Hartman Road
Ft Pierce, FL 34947
September 10, 2015
Flags shall be removed for any storm higher than 75 MPH OR a named
x
Daniel P &
!
Single sheave truck, cast aluminui.
Model
ECXA25 IH
IMF
revolving, non -fouling, internal
halyard truck
0
1/8" x 7x19 Mil-C-5424
Stainless steel aircraft cable
Standard flag arrangement:
5' x 8'
?` `
I
I
Neoprene coated 2" diameter
o
steel counterweight
o
0
a�
b
,
Nylon beaded retainer ring
o
N
r
.c
M
Revolving non -fouling internal halyard
m
truck, cast aluminum body, 26
stainless steel ball bearings,
v
and 2-1/2" diameter plated
>
steel sheave.
O
Gearless, self locking direct
drive winch with six tumbler
cylinder lock
0.
0
0
N
`O
O
Aluminum flash collar
U
Q
U
a-
Winch Detail
3000 PSI conAa
¢
c
0
0
Hardwoges
a
r
All shafts with overall
(supplihers)
length of more than
38'-6" are shipped in
O
two sections.
Dry sand tighed
o
i
after aligni
o
_.
Each section matched
marked for field assembly.Exposed
Foundation sl6 a
portion of jam
hot dipgalsteel
3
sleeve must be well
Steel centerines
i
lubricated prior to
assembly.
6"
maximum shop
1/4" Steel bas1-1/2"
gap allowed for field
6"
12"
fitting (ram for tight joint)
1/4" Steel support plate
12"4-
welded to grounding spike
.0 30" IN
Pro ect:
Ground set tapered aluminum
flagpole: ALLOY:
6063T6
EDER FLAG
Date:
Location:
F�cposed height: 25'-0"
Overall height:
28'-0"
MANUFACTURING COMPANY
ReviS!on:
Architect:
Shi in 1 section
Bult diameter:
5"
1000 W. Rawson Avenue
Contractor
Top diameter: 3"
Wall thickness:
.156"
Oak Creek, VJI 53154
Customer:
Finish: 100 grit palish -
Job:
e
x+xx xx,a4
x x
illllll II111
EDER FLAG
MANUFACTURING
COMPANY, INC.
The largest company inAmertca
t(at serves as 6oth a flag
andflagpofe manufacturer
Phone: (414) 764-3522
Toll Free: (800) 558.6044
Fax: (414) 764-1039
www.ederflag.com
1000 W. Rawson Ave.
Oak Creek, W153154
Project Name:
-�
Date:
06/15/2015
Location:
�1 �� C tn,
Baartol Yoh Nbr:
Architect:
Contractor:
Revision Date:
Revision Nbr:
STANDARD FLAGPOLE STRESS CALCULATIONS
Material of Pole
aluminum - 6063-T6
Type of Pole
Standard
Top Diameter (in)
3
Butt Diameter (in)
5
Straight Section Wall Thickness (in)
0.156
Taper Section Wall Thickness (in)
0.156
Exposed Length (ft)
25
Tapered Length (ft)
11
Height of Pole Above Grade (ft)
0
Weight of Pole and Accessories (lbs)
69
Shear Force By Flag (lbs)
0
Shear Force By Pole (lbs)
417
Total Shear Force (lbs)
417
Moment By Flag (ft Ibs)
0
Moment By Pole (ft lbs)
5407
Total Moment (ft lbs)
5407
Cross Sectional Area ofBase (inA2)
2.374
Section Modulus (ie3)
2.788
Moment of Inertia, Base (ieQ
6.97
CA - Coefficient of Analification
0.9734
FY- Minimum Yield Stress(psi)
25000
FA - Compressive Stress (psi)
29.25
MFA - Allowable Compressive Stress(psi)
341
FB - Bending Stress (psi)
23272
MFB - Allowable Bending Stress (psi)
24000
FS - Shear Stress (psi)
351.32
MFS - Allowable Shear Stress (psi)
11330
Wind Speed (mph)
178
CSR - Combined Stress Ratio
11.0
(\ (
J
III111 II1'1
EDER FLAG
MANUFACTURING
COMPANY, INC.
General Notes For Ground Set Poles
The largest company in America
that serves as 6oth a flag
andf(agpole manufacturer
Wind Pressure on Flagpole
Segment Nurn
Height ft
Pressure(ps
1
0 to 14
79.5
2
14 to 16.4
79.5
3
16.4 to 20
81.8
4
20 to 25
85.5
Phone: (414) 764-3522
Toll Free: (800) 558.6044
Fax: (414) 764-1039
www.ederfag.com
1000 W. Rawson Ave.
Oak Creek, WI 53154
1. Regarding calculations for overturning of the concrete base, our formula for depth of the ground tube (10% of the exposed height) is
empirical and has been found to be satisfactory for average soil conditions. The only purpose of the concrete base -is to transmit
overturning forces to the surrounding soil.
2. Where unusual soil conditions prevail, it is assumed that the project designers will take whatever steps they consider necessary. It is
impractical for the pole manufacturer to assume this responsibility.
All flagpole design calculations are in accordance with GUIDE SPECIFICATIONS FOR DESIGN LOADS OF METAL FLAGPOLES,
ANSUNAAMM FP 1001-07 Fifth ed.
.A
xxxx xfxx
x x
II1111 II111
EDER FLAG
MANUFACTURING
COMPANY, INC.
Tke largest company inAmerica
that serves as 6oth a flag
andflagpole manufacturer
Phone: (414) 764-3522
Toll Free: (800) 558.6044
Fax: (414) 764-1039
www.ederflag.com
1000 W. Rawson Ave.
Oak Creek, WI 53154
Project Name:
P �I-Iqnridp
Date:
06/15/2015
Location:
-%qo
Baartol Job Nbr:
Architect:
Contractor:
Revision Date:
Revision Nbr:
STANDARD FLAGPOLE STRESS CALCULATIONS
Material of Pole
aluminum - 6063-T6
Type of Pole
Standard
Top Diameter (in)
3
Butt Diameter (in)
5
Straight Section Wall Thickness (in)
0.156
Taper Section Wall Thickness (in)
0.156
Exposed Length (ft)
25
Tapered Length ft)
11
Height of Pole Above Grade ft
0
Type of Flag(s)
Nylon / Cotton
Flag #1 Size (H x W ft)
4 X 6
Weight of Pole and Accessories (lbs)
69
Shear Force By Flag lbs)
72
Shear Force By Pole (lbs)
298
Total Shear Force (lbs)
371
Moment By Flag (ft lbs)
1662
Moment By Pole ft lbs)
3739
Total Moment (ft lbs)
5401
Cross Sectional Area of Base in^2)
2.374
Section Modulus ie3)
2.788
Moment of Inertia, Base (ie4)
6.97
CA - Coefficient of Amplification
0.9734
FY - Minimum Yield Stress(psi)
25000
FA - Compressive Stress (psi)
29.25
MIA - Allowable Compressive Stress (psi)
341
FB - Bending Stress (psi)
23247
MFB - Allowable Bending Stress (psi)
24000
FS - Shear Stress(psi)
312.18
MFS - Allowable Shear Stress (psi)
11330
EPW WE
LLM
EDER FLAG
MANUFACTURING
COMPANY, INC.
rilre largest company in America
that serves as both a flag
andfCagpofe manufacturer
Wind Speed (mph) 117
CSR - Combined Stress Ratio 11.0
Wind Pressure on Flagpole
Segment Num
Height ft)
Pressure sf)
1
0 to 14
34.4
2
14 to 16.4
34.4
3
16.4 to 20
35.3
4
20 to 25
36.9
General Notes For Ground Set Poles
Phone: (414) 764-3522
Toll Free: (800) 558-6044
Fax: (414) 764-1039
www.ederflag.com
1000 W. Rawson Ave.
Oak Creek, Wl53154
1. Regarding calculations for overturning of the concrete base, our formula for depth of the ground tube (10% of the exposed height) is
empirical and has been found to be satisfactory for average soil conditions. The only purpose of the concrete base is to transmit
overturning forces to the surrounding soil.
2. Where unusual soil conditions prevail, it is assumed that the project designers will take whatever steps they consider necessary. It is
impractical for the pole manufacturer to assume this responsibility.
All flagpole design calculations are in accordance with GUIDE SPECIFICATIONS FOR DESIGN LOADS OF METAL FLAGPOLES,
ANSUNAAMM FP 1001-07 Fifth ed.
All oll
• , t
;,> ryK•`pia-k-y.�+�'.�o�°�;�iar�.o ,�ry�;3�_�,+`kw„��,m�✓�
Nk . ,c
�'cc��,, �V7 �'j � ,� x••1+T
.a ?k pp',��f'dIInYLil�l�
k+�
•�,oa in,klp' d k .w v
f ; k
a U= r
EDER FLAG
MANUFACTURING
COMPANY, INC.
The largest company in America
that serves as both a f Iag
andflagpole manufacturer
Phone: (414)764.3522
Tall Free: (800) 558.6044
Fax: (414) 764-1039
www.ederfag.com
1000 W. Rawson Ave.
Oak Creek, WI 53154
Project Name:
Q H
Date:
06/15/2015
Location:
� ) a
Baartol Job Nbr:
Architect:
Contractor:
`
Revision Date:
Revision Nbr:
STANDARD FLAGPOLE STRESS CALCULATIONS
Material of Pole
aluminum - 6063-T6
Type of Pole
Standard
Top Diameter (in)
3
Butt Diameter (in)
5
Straight Section Wall Thickness (in)
0.156
Taper Section Wall Thickness (in)
0.156
Exposed Length (ft)
25
Tapered Length (ft)
11
Height of Pole Above Grade (ft)
0
Type of Fla (s)
Nylon / Cotton
Flag #1 Size x W ft
4 X 6
Weight of Pole and Accessories (Ibs)
69
Shear Force By Flag(lbs)
72
Shear Force By Pole (Ibs)
298
Total Shear Force lbs
371
Moment By Flag (ft lbs)
1662
Moment By Pole ft lbs
3739
Total Moment ft lbs)
5401
Cross Sectional Area of Base inA2
2.374
Section Modulus ie3)
2.788
Moment of Inertia, Base (inN)
6.97
CA - Coefficient of Amplification
0.9734
FY - Minimum Yield Stress (psi)
25000
FA - Compressive Stress (psi)
29.25
MFA - Allowable Compressive Stress(psi)
341
FB - Bending Stress (psi)
23247
MFB - Allowable Bending Stress(psi)
24000
FS - Shear Stress(psi)
312.18
MFS - Allowable Shear Stress(psi)
11330
r
EDER FLAG
MANUFACTURING
COMPANY, INC.
General Notes For Ground Set Poles
Vie largest company inArneiica
that serves as 6oth a fCag
andjEagpofe manufacturer
Wind Pressure on Flagpole
SegmentNum
Height fl
Pressure( s
1
0 to 14
34.4
2
14 to 16.4
34.4
3
16A to 20
35.3
4
20 to 25
36.9
Phone: (414) 764.3522
Toll Free: (800) 558' 6044
Fax: (414) 764-1039
www.ederHag.com
1000 W. Rawson Ave.
Oak Creek, WI 53154
1. Regarding calculations for overturning of the concrete base, our formula for depth of the ground tube (10% of the exposed height) is
empirical and has been found to be satisfactory for average soil conditions. The only purpose of the concrete base is to transmit
overturning forces to the surrounding soil.
2. Where unusual soil conditions prevail, it is assumed that the project designers will take whatever steps they consider necessary. It is
impractical for the pole manufacturer to assume this responsibility.
All flagpole design calculations are in accordance with GUIDE SPECIFICATIONS FOR DESIGN LOADS OF METAL FLAGPOLES,
ANSI/NAAMM FP 1001-07 Fifth ed.
ry
A
L
$�s
4� h rtfiµ* r tiv`
�ra t � • if? 7 t, i_
t. J1.N letrf� dZtf,�I1 nGLi ��il Y�'�� �i
T elf.. �_a•Ye. � ^I• �•J'
RECEIVED AUG 04,2015
Windload Calculations
for
Lang Management
FBC 2010 & ASCE 7-10
Wind Speed 160 MPH @ 3 Second Gust
Exposure C
Internal Coeff: 0
ST, i,iTm eeLwff
IWliAwed Not In 1
Prepared By:
Daniel P Retherford, P.E.
1402 Hartman Road
Fort Pierce, FL 34947
June 2015
Flags shall be removed for any storm higher than 75 mph OR a named storm.
.:�llfflii;in.
1`L I •,
�\0; W
� • S�O•�OV.W�1
Daniel P. R 3� A$
1402 Hartman R6001 1il!fl\\
Fort Pierce, FL 3494� '
(772)224-9826