Loading...
HomeMy WebLinkAboutPROJECT INFORMATION1 COOLING TECHNOLOGIES Proposal to: Precision Air Project: Sands Condo SCANNED BY St. Lucie County Opportunity / Quote No. (Ver): Rick Kalczuk_140715_131255768 / Rick Kalczuk_140919_081912990 (1) Rep Quote No.: Marley NC8400 Tower Engineer: Jascko Corp 13200 SW 128th Street, Suite B-1 Miami, FL 33186 (305) 278-8523 / fax: (305) 259-6716 March 26. 2015 TOWER MODEL PERFORMANCE CONDITIONS MOTOR DATA TOWER DIMENSIONS WEIGHTS Quantity of (1) Marley NC Per 1-cell tower. NEMA 15 HP 1 speed / Each cell: (without options) Per cell: Class Diamond Series 805 gpm 1 wind Length 8' - 4 3K' Shipping: 6,1271b model NC8402PAN 95.0'F Hot Water 3phase /60 Hz Width 14'-2" Operating: 11,558 lb factory assembled 1-Cell 86.0 of Cold Water 230/460v Height 19 - 3" crossflow cooling tower 79.0 of Entering WB 1.15sf / TEFC I-c per 1-cell tower. 1800 RPM per 1-cell tower. vnth options) ( Shipping: 6,127 lb Premium Efficiency Length 9'- 1 518" OperaSng: 11,558 lb Inverter duty nameplated Width 14'-2" Height 13'-45/8" Quantities shown below are per tower. Base Tower Construction/Equipment: Stainless Steel casing. Stainless Steel structure. Stainless Steel collection basin. Stainless Steel discs"d tit+ I• All stainless steel is -- .16, 0 4t f)gggl;, - Low Sound fan with aluminum blades. Marley designed Geareducer®with 5-yearZvarranty, r 15 mil PVC film fill with ihtegral louvers a?d drft'eliminators designed and Drift rate guaranteed: to. be no greater thap .l)05% of the design ' owiate.1 CTI certification per STD-201. HDG steel fan guard. Collection Basin Connections and Accessories: All flanges are to Class 125 ANSI B16.1 standard. All threads are to American Standard Pipe Taper Thread. (1) 6 in (152 mm) diameter bevel and groove cased face outlet(s) with trash screen(s). 4 in (102 mm) diameter combination drain and overflow in each cell (1) 1 in (25.4 mm) water make-up float valve Distribution Basin Inlet and Accessories: --- -(2) 6 in (152 mm) diameter top inlet connections per cell: -- --- -- -- -- - - (2) 6 in (152 mm) horizontal flow control valves per cell. -—�ower_is-designedin_accordance-with-GSHA_safetystandards- — This quotation does not include. features whichareavailableto allow safe access on the fan -deck while the fan is still operating. If this -is-a desired feature for your intended operation, please contact your sales representative. External tube line with dipstick Convenient access to the collection basin and plenum area is provided via a large access door located on each endwall Easy fitting perimeter guardrail, kneerail & toeboard (1) Cased face ladder Ladder(s) extended 60 in below base of tower Control Systems: none Page 1 of 6 Standpipe Grain 6 Overflow P Float Valve Inlet Face C Plan View or Basin I I 6" Side Suction Outlet I I I I NOTES 1. Flanged connections conform to class 125 of the ANSI 816.1 specification. The halt hales straddle the centerlines. 2 Alt piping supports are by others. On NOT support outlet piping from the tower. 3. The collection basin piping accessories shown on this drawing are furnished by SPX CT. G. The standpipe overflow is to be field installed by others. 5. The design operating loads shown in the table an the Grillage Details drawing are based upon the volume of water in the collection basin at shutdown, The shutdown water level has been sized to accommodate the maximum allowable flow rates. The actual operating load is variable, and is dependent upon the design flow rate per cell. Design loads are all based upon the recommended operating water level. Operating levels in excess of that recommended con result in loads exceeding values stated, Consult a SPX CT representative for greater detail on this or any other subject, 6. The tower assembly tolerance applicable to all dimensions is • or - US 13 mml. Consult suppliers of supporting structure for construction tolerances. 7.The units of measure are in IP ISII units unless otherwise noted. Em r,zvR NC8402PANlSGF - Piping Plan Sands Condo I M��Ja e t6v. Br C1lCNEU C rxw- I United States AEv, 0.11E CNAFN By WINE a CKIX I AWflaVEO I ORDER Ni Rai Ifi Ma— W 5' Ritk Kalauk.140919.081912990 V1 03/16115 QTC SYS 0 1=1 RK555330P �i Access Door a V N a = C P �u in I 6' -2 V2" Face C Interior View ca m _a ua ca i VI > O V — Z NOTES 1. The fan motor must be locked out and inoperable before entering the tower. This warning has been placed on the access door. 2. Flonged connections conform to class 125 of the ANSI B16.1 specification. The boll holes straddle the centerlines. 3. Horizontal Control IHCI valves can withstand a maximum static shutoff pressure of 25 psi (172 kPot 4. Nil flat face flange gaskets are supplied by SPX CT. S. To insure maximum thermal performance the calling laver must be installed level and plumb. Both of the air inlet faces must have adequate air supply. If obstructions exist, consult your SPX CT representative. 6. Hoisting clips are provided for ease of unloading and positioning. For overhead lilts or where additional safety precautions are prudent, add slings beneath the tower. See Hoisting Details drawing. 7. The vertical weight of the piping illustrated within the tower perimeter may be supported by the tower structure. An other piping shall be supported independent of the lower (see section A -A for specific delailsl. The piping, their supports, the design of bath piping and supports, and the lateral restraint of piping loads shalt be supplied by others. 8. Construction of the ladder and guardrail: The guardrail is fabricated from galvanized structural tubing. Top rail, middle rail and posts are 1 112" (38 mml square tube 118' 13 cam) thick. Toeboards are 12 gouge heavy mill galvanized steel. The ladder is aluminum 3" 176 .1 x 1 118' (29 cam) 1-beam side rails and 1 114" 132 mn) serrated rungs. 9, the ladder and guardrail are field installed by others. The tower is shop modified to accept the option. The clips and hardware are provided by SPX CT for the field installation. The installation detail drawings are included in the literature package shipped with the lower. 10. O.SH.A. standards recommend the use of a Safety Cage when the length of a single ladder exceeds 20'-0" (6096 mml. 11. O.S.H.A. standards recommend the use of an Access Door Platform if the door is 1 (1219 cam) or higher above grade. 12. The lower assembly tolerance applicable to all dimensions is . or - I18' 13 mml. Consult suppliers of supporting structure for construction tolerances. 13. The units of measure are in IP ISO units unless otherwise noted. can NC8402PANlSGF - Schematic Cased Elevation and Notes m. er aca6O Sands Condo ,q United States � ••'" CQ AS C6 OAEM N TOLE BLOCK SPK 000.N0 TE ORES. K. ...�. � �u"" ^m°n° alLn 1 x ROT aranw a LINIMS1fO-ALL TOTS RISE RyfO ldd]ER Cady r T LMS Rick Kalauk-140919-081912990 V1 03/16115 CItC SYS 0 1=1 I RK555330M