Loading...
HomeMy WebLinkAboutMISC LETTERS} RESPONSE LETTER SCANNED To: ST. LUCIE COUNTY -Plans Reviewer ;t � BY County From: Douglas A. Ramirez, P.E.-Structural Engineer-ATRIN� Date: November 9, 2015 Subject: Responses to Building Department Comments: FDOT 1-95 REST AREA Process: PERMIT NUMBER 1510-0327 Structural Comment 1: FOUNDATION PLANS MUST BE ORIGINAL Response: SEE ATTACHED ORIGINALS Comment 2: NOV 1 2 BEC'D SHOW THE TIE DOWNS OF THE GENERATOR TO THE FOUNDATIONS Response: SEE DETAIL B/S-1 ON REVISED DRAWING Comment 3: ENGINEER TO DESIGN FOR VEHICULAR IMPACT PROTECTION AND —_ - - HINERY-PROTE - - - - Response: SEE ATTACHED SITE PLANS FOR NORTHBOUND AND SOUTHBOUND LOCATIONS OF EQUIPMENT. UNITS ARE NOT LOCATED WHERE THEY ARE SUBJECT TO MECHANICAL DAMAGE. THERE IS NO VEHICULAR TRAFFIC IN THE AREAS WHERE THE UNITS ARE BEING PLACED AND AS SUCH NO BARRIERS ARE REQUIRED. ONLY PEDESTRIAN WALKWAYS ARE PRESENT AND THE NEAREST VEHICULAR ROADWAY IS A PARKING J I AREA 60 FEET FROM THE EQUIPMENT. WE HAVE ADDED A NOTE TO THE SHEET INDICATING THIS. Comment 4: RE -SUBMIT 3 PLAN SETS W/ 2 PDF DISKS Response: SEE ATTACHED ORIGINALS No other comments were received by this office for structural. The above are our responses to the provided comments. Please, feel free to call me at your convenience if you should have any further questions or comments. Sincerely, Douglag A. R,$mi M.S., E. Senior Structural ngineer, rchitecture Engineering ATKINS Joe Cicio From: Joe Cicio Sent: Thursday, October 29, 2015 8:18 AM To: 'customerservice@Novoaelectric.com' SCANNED Cc: Joe Cicio BY Subject: Review Comments for Permit Number 1510-0327 St. Lucie County Attachments: Report_FL_Review_Comments_Noncompliantjrf.pdf Dear St. Lucie County Permit Applicant, Please see the attached plan review comments which have been generated for your permit. As soon as we receive the modified plans and any additional required documentation back from the design professional, contractor or owner we will perform the additional reviews as necessary in order to complete the plan review process. Once the plans have been signed, by all applicable plan reviewers, we will move the permit forward either to the Fire Department or back to permitting for permit issuance. Thank You, Raaelml W, ei & Plans Examiner II Standard Building Inspector Building Plans Examiner One and Two Family Dwelling Inspector One and Two Family Plans Examiner St I_v4iz, Cou+vty Pt t*vfti" raft& Dev�a,f Se -vi coy Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records available to the public and media upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and / or copying. Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error, Please notify the sender by reply email -and delete all materials from all computers..