Loading...
HomeMy WebLinkAboutMISC LETTERRESPONSE LETTER To: ST. LUCIE COUNTY -Plans Reviewer From: Douglas A. Ramirez, P.E.-Structural Engineer-ATKINS Date: November 9, 2015 Subject: Responses to Building Department Comments: FDOT I-95 REST AREA Process: PERMIT NUMBER 151 Structural Comment 1: FOUNDATION PLANS MUST BE ORIGINAL Response: SEE ATTACHED ORIGINALS Comment 2: o(; IY E® 3t LUCie County SHOW THE TIE DOWNS OF THE GENERATOR TO THE FOUNDATIONS Response: SEE DETAIL B/S-1 ON REVISED DRAWING Comment 3: ENGINEER TO DESIGN FOR VEHICULAR IMPACT PROTECTION AND — _ _MAtH1NERY-PROTECT -_ Response: SEE ATTACHED SITE PLANS FOR NORTHBOUND AND SOUTHBOUND LOCATIONS OF EQUIPMENT. UNITS ARE NOT LOCATED WHERE THEY ARE SUBJECT TO MECHANICAL DAMAGE. THERE IS NO VEHICULAR TRAFFIC IN THE AREAS WHERE THE UNITS ARE BEING PLACED AND AS SUCH NO BARRIERS ARE REQUIRED. ONLY PEDESTRIAN WALKWAYS ARE PRESENT AND THE NEAREST VEHICULAR ROADWAY IS A PARKING T AREA 60 FEET FROM THE EQUIPMENT. WE HAVE ADDED A NOTE TO THE SHEET INDICATING THIS. Comment 4: RE -SUBMIT 3 PLAN SETS W/ 2 PDF DISKS Response: SEE ATTACHED ORIGINALS No other comments were received by this office for structural. The above are our responses to the provided comments. Please, feel free to call me at your convenience if you should have any further questions or comments. Sincerely, Engineering