I have enclosed the Job Report Number 11598 from the job referenced above. The report was recorded by Brian
Kocsis, OMG Field Sales Representative.
OMG is interested in your feedback on our services. Please visit www.omglistens.com to take a brief, 2-3
minute survey to help us understand how we did on this project, and more importantly, anything we can do
better next time. We value your time and input, and thank you in advance for your participation.
If you have any further questions, please feel free to call
Sincerely,
114n
Andy Cleveland
OMG Technical Support Lead
Brian Kocsis(OMG)- -
Attn:
bcadle@sutterroofmg.com;
Enc:
None
ja. Reviewed O Fumish as Corrected
O Revise and Resubmit
E3 Rejected O Submit Specified Item
---- Thin mvlmn Ln n I for general s conformance,whit the deai0n concept and me - --
--lnlarmatlorcpl0snN'tilot:ar>�on-Dccvmsma Corte ene�or ediradwb— - —
__ mado on the shop dmwinp dudrtp.this FWAW donot reliow tha_corrrvAQ
from comp0anco wlth the reaWrameme of the plena and specification.
Ftovimi of a cpedfio hem dm0 not Include ruvim of an assembly of nNN
the horn In a component The contractor Is responslblo for dimanslon to
be confirmod and correlated at the lob alto; Mommtlon that pertain solely
to No fabrlcatlon processes or to the means, methods, techniques,
so o8r�er'ade mend perf es oomdrq o 1 in a o��ot slimy mma meel.
ATLAS STRUCTURAL ENGINEERING. U-0
RS Data, — l — I
Report Number 11598
page 1 of 4
Pull Test Report
Job Name: Tropicana Roof Area 2
Job Location: FORT PIERCE, FL
Ambient Temperature: 81°F
Tester Manufacturer: DMD Force-2000
Test Witnessed By:
Ground Roughness: B
Test Performed By: Brian Kocsis
Test Cut Area Repaired By: See comments
Fasteners Tested: Carlisle HP-X
Roof Cover Type: M/A Single Ply
New Insulation Manufacturer: Carlisle
Insulation Type: ISO
Insulation Thickness: 1 1/2"
Deck Type
Steel
Thickness
Unknown
Report Number: 11598
Test Date: 12/30/2015
Building Height: 30'
Max Cap of Tester: 2000
Roof Area: 2,300 sq. ft.
Existing Roof System: Tear -Off
Thickness of Existing Roof: N/A
New System Manufacturer: Carlisle
Disclaimer: Manufacturer's installation requirements shall be
followed when using any of the tested fasteners or adhesives.
Neither the technician performing the pullout tests, nor his/her
company is responsible for the waterproofing integrity of the
repairs. This test report does not certify the structural integrity of
the -roof -deck. - - — -
Report Number 11598 page 2 of 4
1 / \
Test Results
Job Name: Tropicana Roof Area 2
Test Results lbs Fastener Tested Penetration Bit Diameter Comments
Location No.
1
636
Carlisle HP-X
1"
2
621
Carlisle HP-X
1"
3
542
Carlisle HP-X
1"
4
661
Carlisle HP-X
1"
5
598
Carlisle HP-X
1"
6
678
Carlisle HP-X
1"
7
651
Carlisle HP-X
1"
8
606
Carlisle HP-X
1"
9
628
Carlisle HP-X
1"
10
601
Carlisle HP-X
V
Pull Test Comments:
Ben Cadle is the superintendent on this job. Mike Hulley was on site to witness and repair.
0
Report Number 11598 page 3 of 4
Roof Diagram
Tropicana Roof Area 2
10
3
9
4
7
1
5
6
2
8
ON
Report Number 11598 page 4 of 4
SCANNED
BY
St. Lucie Countv
1/11/2016
Ben Cadle
Sutter Sarasota
8284 Vico Ct.
SARASOTA, FL 34240
UNITED STATES
Re: Tropicana Roof Area 2
Dear Mr. Cadle:
OMG.
ROOFING
PRODUCTS
153 BOWLES ROAD
AGAWAM, MA O1001
413-789.0252
800-633-3800
FAX: 413-789-1069
WWWOLYFASECOM
I have enclosed the Job Report Number 11598 from the job referenced above. The report was recorded by Brian
Kocsis, OMG Field Sales Representative.
OMG is interested in your feedback on our services. Please visit www.omglistens.com to take a brief, 2-3
minute survey to help us understand how we did on this project, and more importantly, anything we can do
better next time. We value your time and input, and thank you in advance for your participation.
If you have any further questions, please feel free to call.
Sincerely,
Andy Cleveland
OMG Technical Support Lead
CC:
Brian Kocsis-(OMG)
Attn:
bcadle@sutterroofing.com;
Eric:
None
O RWewed G Fumtsh as Co se
O Revise and Resubmit
O Rejected O Submit Specified Item
from compliance with the t�dI mrft al
1levIM of'a cpadfle ftarn not hicludo I
010 I10m Is a comporrem. The Contractor u
be can0-ned and correlated at the Job she,
to the fabrication processes or to the n
aequoncoc- end precuduroe of oonsbuctlon, o
of all othc:..=dcc and o_rfoanlnn n n Wer m
ATLAS STRUCTURAL ENC;NEERING, LLC
14r QS - - — c_: -I(o
Report Number 11598 page 1 of 4
Pull Test Report
Job Name: Tropicana Roof Area 2
Job Location: FORT PIERCE, FL
Ambient Temperature: 81 IF
Tester Manufacturer: DMD Force-2000
Test Witnessed By:
Ground Roughness: B
Test Performed By: Brian Kocsis
Test Cut Area Repaired By: See comments
Fasteners Tested: Carlisle HP-X
Roof Cover Type: TWA Single Ply
New Insulation Manufacturer: Carlisle
Insulation Type: ISO
Insulation Thickness: 1 1/2"
Deck Type
Steel
Thickness
Unknown
Report Number: 11598
Test Date: 12/30/2015
Building Height: 30'
Max Cap of Tester: 2000
Roof Area: 2,300 sq. ft.
Existing Roof System: Tear -Off
Thickness of Existing Roof: N/A
New System Manufacturer: Carlisle
Disclaimer: Manufacturer's installation requirements shall be
followed when using any of the tested fasteners or adhesives.
Neither the technician performing the pullout tests, nor his/her
company is responsible for the waterproofing integrity of the
repairs. This test report does not certify the structural integrity of
the roof deck.
Report Number 11598 page 2 of 4
Test Results
Job Name: Tropicana Roof Area 2
Test Results lbs Fastener Tested
Location No.
Penetration Bit Diameter Comments
1 636
Carlisle HP-X
1"
2 621
Carlisle HP-X
V
3 542
Carlisle HP-X
1"
4 661
Carlisle HP-X
1"
5 598
Carlisle HP-X
1"
6 678
Carlisle HP-X
1"
7 651
Carlisle HP-X
V,
8 606 Carlisle HP-X 1"
9 628 Carlisle HP-X 1"
10 601 Carlisle HP-X 1"
Pull Test Comments:
Ben Cadle is the superintendent on this job. Mike Hulley was on site to witness and repair.
Report Number 11598 page 3 of 4
Roof Diagram
Tropicana Roof Area 2
10
3
9
4
7
1
5
6
2
8
V N
Report Number 11598 page 4 of 4
ATLAS
Structural Engineering, LLC
August 1, 2016
Sutter Roofing Cc of SWFL
Mr. Jason Mills
4085 L.B. McLeod Road, Suite B
Orlando, FL 32811
Re: Tropicana Fort Pierce
Systems Building 3 — Steel Deck Pull Tests
Atlas Job No. 15002.05
Dear Jason:
12610 World Plaza Lane I Building 61, Suite 2
Fort Myers, Florida 33907
phone 239.274.6820 1 fox 239.274.68211 CA #28380
SCANNED
BY
St. Lucie Countv
As per your request, Atlas Structural Engineering, LLC has reviewed the fastener withdrawal test results
provided for the Tropicana Systems Building 3 located at 6500 Glades Cut Off Road in Fort Pierce, Florida.
The Systems Building 3 is an independent structure.
On -site withdrawal tests were performed at random locations to determine the average ultimate pullout value.
The withdrawal tests achieved an average ultimate pullout value of 622.2 Ibs per fastener. The fastener
patterns provided in the Engineering Letter titled 'Tropicana Fort Pierce - Systems Building 3" were
determined using an average ultimate pullout value of 400 Ibs per fastener, with a margin of safety for uplift
resistance equal to 2.0.
The fastening patterns provided in the Engineering Letter were determined using Florida Product Approval
(FPA) No. FL14083-R9, System SC-132, and do not exceed the force per fastener determined using the
above stated FPA and tested pullout value. See Engineering Letter for additional information.
After reviewing the fastener withdrawal test provided by OMG Roofing Products, Inc., it is our opinion the
fastening patterns provided in the Engineering Letter are structurally adequate to resist the wind uplift
pressures required when installed in accordance with the above stated FPA and Engineering Letter.
Please do not hesitate to contact our office if you have any questions.
Sincerely,
Atlas Structural Engineering, LLC - -
Robin W. Stephan, P.E. #66525
President
Tropicana Fort Pierce I Page 1 of 1
Systems Building 3 — Steel Deck Pull Tests
ATLAS
I
ructural Engineering, LLC
August 1, 2016 SCANNED
Sutter Roofing Cc of SWFL BY
Mr. Jason Mills St. Lude Count,
4085 L.B. McLeod Road, Suite B
Orlando, FL 32811
Re: Tropicana Fort Pierce
Systems Building 3 — Steel Deck Pull Tests
Atlas Job No. 15002.05
Dear Jason:
12610 World Plaza Lane I Building 61, Suite 2
Fort Myers, Florida 33907
phone 239.274.6820 i fox 239.274.68211 CA #28380
SEP 0 g 2016
PERMITTIyG
St. Lucie County, FL
As per your request, Atlas Structural Engineering, LLC has reviewed the fastener withdrawal test results
provided for the Tropicana Systems Building 3 located at 6500 Glades Cut Off Road in Fort Pierce, Florida.
The Systems Building 3 is an independent structure.
On -site withdrawal tests were performed at random locations to determine the average ultimate pullout value.
The withdrawal tests achieved an average ultimate pullout value of 622.2 Ibs per fastener. The fastener
patterns provided in the Engineering Letter titled 'Tropicana Fort Pierce - Systems Building 3" were
determined using an average ultimate pullout value of 400 Ibs per fastener, with a margin of safety for uplift
resistance equal to 2.0.
The fastening patterns provided in the Engineering Letter were determined using Florida Product Approval
(FPA) No. FL14083-R9, System SC-132, and do not exceed the force per fastener determined using the
above stated FPA and tested pullout value. See Engineering Letter for additional information.
After reviewing the fastener withdrawal test provided by OMG Roofing Products, Inc., it is our opinion the
fastening patterns provided in the Engineering Letter are structurally adequate to resist the wind uplift
pressures required when installed in accordance with the above stated FPA and Engineering Letter.
Please do not hesitate to contact our office if you have any questions.
Sincerely,
Atlas-Structural.Engineer.ing,-LLC
Robin W. Stephan, P:E. #66525
President
Tropicana Fort Pierce I Page 1 of f '
Systems Building 3 — Steel Deck Pull Tests
ATLAS
Structural Engineering, LLC
September 6, 2016
Sutter Roofing Cc of SWFL
Mr. Jason Mills
4085 L.B. McLeod Road, Suite B
Orlando, FL 32811
Re: Tropicana Fort Pierce
Systems Building 3 Inspection
12610 World Plaza Lane I Building 61, Suite 2
Fort Myers, Florida 33907
phone 239.274.68201 fax 239.274.6821 1 CA #28380
SCANNED
BY SEPg9.16
St. Lucie Countv 29
PEh;v11TTi VG
St. Lucie Count;, FL
Atlas Job No. 15002.05 / Permit No. 1510-0506
To Whom It May Concern:
As requested, a representative from Atlas Structural Engineering, LLC (Atlas) visited the Tropicana Systems
Building 3 located at 6500 Glades Cut Off Road in Fort Pierce, Florida, on Thursday August 4, 2016 to conduct
an assessment of the roof covering installed by Sutter Roofing Company of Florida (Sutter Roofing). The
purpose of the visit was to visually observe the fastening patterns used to mechanically attach insulation and
single -ply roofing membrane to an existing steel roof deck.
Insulation Attachment Findings
The single -ply membrane had been installed and access to the underside of the roof was not obtained during
the site visit. Therefore, the insulation fasteners and plates were not visible at the time of inspection. As
shown in photographs taken by Sutter Roofing during installation, 4'x8' insulation boards were preliminarily
fastened to the steel roof deck with (6) fasteners and plates per board. This complies with the preliminary
insulation attachment specified in the engineering letter. See photographs on page 3.
Single -Ply Attachment Findings
Access to the roof was not obtainable at time of inspection. As shown in photographs taken by Sutter Roofing
during installation, the single -ply membrane was fastened with screws and plates in the sidelaps of the sheets.
Sutter Roofing has stated that the single -ply membrane is Carlisle 60 mil Sure -Weld TPO, the sheets are 8'-0"
wide in Zone 1 and 4'-0" wide in Zone 2 (where sheets are parallel to the roof), —and fasteners are Carlisle
ue-rDUTran--auuiuonai_row=oc_rasteners_was_provioea mzine-cenrer_oT=messneer,.tnese=rasiening=patterns-��
_compiy_with_the _single-ply_attachment-patterns.specified_in_the_engineering_letter—See_photographs,on_page,3.
Summary and Limitations
Based on in progress photos, and the attached affidavit from the licensed contractor that performed the work
("As -Built Condition for Tropicana — Systems Building 3" by Sutter Roofing dated September 2, 2016) it is our
opinion that the fastening patterns installed are structurally adequate to resist the design wind pressures.
The scope of this investigation does not include analysis of the load carrying capacity of the existing structure,
and the fastener patterns provided in this report are based on the materials and fasteners stated above,
Tropicana Fort Pierce I Page 1 of 3
Systems Building 3Inspection
ATLAS STRUCTURAL ENGINEERING, LLC
12610 World Plaza Lane, Suite 2 1 Fort Myers, Florida 33907
phone 239.274.6820 1 fox 239.274.68211 CA #28380
provided by Sutter Roofing at the time of this investigation. See Engineering Letter "Tropicana Fort Pierce —
Systems Building 3" by Atlas Structural Engineering, LLC dated October 22, 2015 for additional information.
The observations, discrepancies and comments included in this report are made on the basis of what was
visible and accessible on the day of the inspection. Representative photos are attached for your convenience
but do not indicate a summary of all items observed or concerns noted; please refer to report above.
Please do not hesitate to contact our office if you have any questions.
Sincerely,
Atlas Structural Engineering, LLC
Cl -&-1
Robin W. Stephan, P.E. 466525
President
Tropicana Fort Pierce I Page 2 of 3
Systems Building 3 Inspection
Preliminary Insulation Attachment
ATLAS STRUCTURAL ENGINEERING, LLC
12610 World Plaza Lane, Suite 2 1 Fort Myers, Florida 33907
phone 239.274.6820 1 fox 239.274.68211 CA #28380
Twical Sidelap Fastener Spacing
Perimeter Half Sheet Installation Typical Sidela Fastener Spacing
Tropicana Fort Pierce I Page 3 of
Systems Building 3 Inspection
FLO
NG
AND SHEET MET
AL
CONTRACTORS
ASSO0ATION
09/02/16
Atlas Structural Engineering, LLC
Ms. Robin Stephan
12610 World Plaza Lane
Building 61, Suite 2
Fort Myers, FL 33907
SUTTER
ROOFING
Re: As -Built Condition for Tropics a —Systems Building 3
St. Lucie County Permit # 1S1Q-OSOfi
To Whom It May Concern:
SCANNED
BY
St Lucie Count%
NATIONAL
ROOFING
UECONTRACTORS
ASSOCIATION
RECF�, VIE D
SEP 0 9 2016
PERPOITTiNG
St. Lucie County, FL
The single -ply roof covering membrane and insulation on the Tropicana Systems Building 3 located at 6500 Glades Cut
off Road in Fort Pierce, Florida were installed under my direct supervision and in conformance with the permitted
construction drawings.
Carlisle Insulation Fasteners and 3" plates were used to preliminary fasten 1.5" thick POLYISO insulation to existing steel
roof deck. Each 4'x8' insulation board was fastened with six (6) fasteners. Smaller boards were fastened in each corner.
Carlisle SynTec #15 HP-X Fasteners and 2-3/8" Piranha Plates were used to mechanically fasten Carlisle SynTec 60 mil
Sure -Weld TPO to existing 22 gauge steel roof deck. The TPO was fastened at 6" o.c. within the side laps and side laps
were sealed with a 1.5" wide weld.
TPO sheets in the field of the roof were 8'-0" wide and two 4'-0" wide half sheets were used in the perimeters parallel to
the eave. A center row of fasteners was installed in the perimeters and corners where the sheets are perpendicular to
the eave. All fastener rows were installed perpendicular to the steel deck flutes.
Please do not hesitate to call with questions or for further assistance at (813) 868-0800.
4 I J � �, � '�•� rig f -Ia
Company of Florida _
IN WITNESS WHEREOF, 1 have hereunto set my hand and seal this 1 day of vl ° 2016_•
STATE OF FLORIDA
COUNTY OF LEE
Personally appeared v (\whais-aeFseaaAV-k ewg_tq mP
My Commission Expires: BROOKEMARTZ
Notary Public: a MY COMMISSION I FF 015734
EXPIRES: August 10; 2017
"a'oe nd4:'_ SondedThm SudgelNotatySmices
"SAFE. SOLID AND SECURE SINCE I902e1
8811 MAISLIN DRIVE • TAMPA, FLORIDA 33637 • (813) 868-0800
FAX: (813) 868-0500 • www.sufferroofing.com LIC: #CC CO20599
ATLAS
Structural Engineering, LLC
October 22, 2015
Sutter Roofing Co of SWFL
Mr. Jason Mills
4085 L.B. McLeod Road, Suite B
Orlando, FL 32811
Re: Tropicana Fort Pierce
Systems Building 3
Atlas Job No. 15002.05
Dear Jason:
12610 World Plaza Lane i Building 61, Suite 2
Fort Myers, Florida 33907
phone 239.274.6820 1 fax 239.274.6821 1 CA #28380
SCANNED
BY
St. Lucie County C
PY
E F
Factory Mutual Criteria and Design Wind Pressures
As requested, Factory Mutual (FM) recommendations for installing mechanically fastened base sheets, and
design wind pressures determined in accordance with FM Data Sheet 1-28, were used to determine the
fastener patterns provided in this report. The following criteria were used:
Basic Wind Speed: V = 123 mph
• Exposure: C
• Internal Pressure Coefficient: +/- 0.18 (Enclosed Building / Protected Openings)
According the FM 1-28 Table 4, the Roof Field Area (Zone 1) Uplift Design Pressure is equal to 41 psf. The
recommended roof ratings from Table 8 of FM 1-28 require an FM 1-90 rated system using the above criteria.
The corresponding design pressures are as follows:
• Roof Field Area = -45.0 psf
• Roof Perimeter Area = -75.0 psf
• Roof Corner Area = -112.5 psf
The pressures stated -above -meet or exceed the minimum recommended -FM. ratings provided -in FM _129—
—®—T:able 1_aW tthe=Compoaents_ai d laddipgmplib_pressures=deteunined_irLaccordance_witE_7_10--- -
_ -----Chapter 30, using the -following criteria:
• Ultimate Wind Speed: Vail = 158 mph
• Nominal Wind Speed: Vad = 123 mph
• Exposure: C
• Risk Category: Category II
• Internal Pressure Coefficient: +/- 0.18 (Enclosed Building / Protected Openings)
Pressures were determined for a building with a maximum roof height of 22'-0" and a minimum overall width of
28'-0". Perimeter and Corner Areas are defined as being within T-0" of the edges and corners of the flat roof.
Tropicana Fort Pierce I Page 1 of 3
Systems Building 3
ATLAS STRUCTURAL ENGINEERING, LLC
907
COPY12610 World Plaza Lane, Suite 2 1 Fort Myers, Florida 33907
RM phone 239.274.6820 1 fox 239.274.68211 CA #28380
Single -Ply Membrane Fastening
Carlisle SynTec #15 HP-X Fasteners and 2-3/8" Piranha Plates shall be used to attach Carlisle SynTec 60 mil
Sure -Weld TPO roof membrane through preliminarily fastened insulation to existing 22 gauge or thicker steel
roof deck. Insulation thickness shall be 1.5" minimum. Fasteners shall be corrosion resistant and each
fastener must penetrate through the top flange of the steel deck a minimum of 3/4". The attachment of the
single -ply roofing membrane shall be as follows:
Zone 1 Provide whole sheets (8' wide each) with 5.5" minimum side laps. Fasteners shall be
spaced at 6" o.c. maximum within the 5.5" wide side laps which are spaced at 90.5"
o.c. maximum.. Each lap shall be sealed with a minimum 1.5" wide outside heat weld.
Zone 2 (Parallel) TPO Sheets Parallel to Perimeter: Provide two half sheets (4' wide each) with 5.5"
minimum side laps. Fasteners shall be spaced at 6" o.c. maximum within the 5.5"
wide side laps which are spaced at 42.5" o.c. maximum. Each lap shall be sealed
with a minimum 1.5" wide outside heat weld.
Zone 2 (Perp) TPO Sheets Perpendicular to Perimeter: Within each whole sheet (8' wide each)
provide one row of fasteners spaced at 6" o.c. maximum in the center of the sheet.
Extend center row of fasteners a minimum of 6-0" in from the edges of the roof.
Center row of fasteners shall be stripped -in with a 6" wide cover strip. Each edge of
the cover strip shall be sealed with a minimum 1.5" wide heat weld.
Zone 3 Provide two half sheets (4' wide each) with 5.5" minimum side laps. Fasteners shall
be spaced at 6" o.c. maximum within the 5.5" wide side laps which are spaced at
42.5" o.c. maximum. Each lap shall be sealed with a minimum 1.5" wide outside heat
weld.
The insulation shall be preliminarily fastened to the steel roof deck with six (6) Carlisle Insulation Fasteners
and 3" plates per 4'x8' board (minimum) prior to placing the membrane. See below for example insulation
fastener pattern.
The fastener patterns provided above were determined using Florida Product Approval (FPA) No. FL14083-
R9, System SC-132, and do not exceed the force per fastener determined using the above stated FPA.
Fastener rows shall be installed perpendicular to steel deck flutes. See Carlisle Syntec literature and
construction details for additional installation requirements.
W-V
Sample Insulation Preliminary Attachment Pattern
(6) Fasteners per 4' x 8' board
Tropicana Fort Pierce I Page 2 of 3
Systems Building 3
ATLAS STRUCTURAL ENGINEERING, LLC
12610 World Plaza Lane, Suite 2 1 Fort Myers, Florida 33907
phone 239.274.6820 1 fox 239.274.6821 1 CA #28380
Limitations
The scope of this investigation does not include analysis of the load carrying capacity of these structures, and
the fastener patterns provided in this report are based on the materials and fasteners stated above, provided
by Sutter Roofing at the time of this investigation. Design wind pressures and edge distance were determined
using information regarding the location and overall dimensions of the structures provided by Sutter Roofing.
Follow all state, county and local codes and ordinances, and all manufacturer and roofing standard installation
requirements.
Please do not hesitate to contact our office if you have any questions.
Sincerely,
Atlas Structural 1=ngineering, LLC
/A%11 4, fo-ZZ-t5
Robin W. Stephan, P.E. #66525
President
�:1 i!• v � 4 r1V
Tropicana Fort Pierce I Page 3 of 3