HomeMy WebLinkAboutPROJECT INFORMATIONRi ht-Suite® Universal 2015 Short Form Job:
wrightsoft g Data: Jul 10, 2016
UNIT ONE ny:
For. First Born Ministry
US #1, Port St Lucie, FI
BY
St. Lucie County
Htg Clg
Htg CIg
Outside db
(OF)
42 87
Inside db
(OF)
70 75
Outside RH
M)
- 65
Inside RH
M)
- 50
Outside wb
(OF)
- 77
Inside wb
(OF)
- 63
Daily range
(OF)
- 15
Design TD
(OF)
28 12
Moisture diff.
(gr/lb)
- 61
Heating Equipment
Cooling Equipment
Make
Make
Ruud
Model
Model
UAPM-060JEZ
Type
Elec strip
Type
Split AC
Efficiency
100 EFF
COP / EER / SEER
14.0
Heating Input
11.3 kW
Sensible Cooling
39.9
MBtuh
Heating Output
38.5 MBtuh
Latent Cooling
17.1
MBtuh
Humidifier
14.6 gpd
Total Cooling
57.0
MBtuh
Leaving Air Temp
120.0 OF
Leaving Air Temp
- 55.0
OF
Actual Heating Fan
700 cfm
Actual Cooling Fan
1900
cfm
Equipment Location
UNIT ONE
System Type
PEAKCV
Fan Motor Heat Type
PACKAGE
Fan & Motor Combined Efficiency
0
%
Static Pressure Across Fan
0
in H2O
NAME
re
I Aig
Heat
I
ible
I
LatetgCcfm
I
I Hcfm
I
I Time
Loss
Gain
Gainnt
UTILITY
48
1440
987
229
36
54
Jul 1900 LOT
BATH 2
56
1492
1137
690
30
58
Jul 1900 LOT
H
84
509
66
211
0
0
Jul 1900 LOT
VESTIBULE
483
24958
24035
7099
642
1223
Jul 1900 LDT
SANCTUARY
436
11048
12448
10760
91
565
Jul 1900 LOT
- a/c
32—
---35—
0—
0—
0
—0-1JOI-1900
LDT—
_ UNIT,ONE
.39481
386 3
70D
h11900
�-Jol`1900'LDT-
201SOct-01 18:27:54
wrightsoft' RlghtSuik® lhiversal 201515.0.19 RSu06570 Page 1
J:1TransfertManual RFIRST BORN MINISTRY.rup Cale =CLTD Front Door faces: N
wrightsofr
Rig ht-Suite® Universal 2015 Short.Form Jo : Jul 10, 2015
UNIT TWO By:
Project Information
For., First Born Ministry
US #1, Port St Lucie, FI
Htg Clg
Htg Clg
Outside db
(OF)
42 87
Inside db
(OF)
70 75
Outside RH
(o/a)
- 65
Inside RH
(a/e)
50
Outsidewb
(OF)
- 77
Insidewb
(OF)
- 63
Daily range
(OF)
- 15
Design TO
(OF)
28 12
Moisture diff.
(grAb)
- 61
Heating Equipment
Cooling Equipment
Make
Make
Heil
Model
Model
HC4A336AKA•
Type
Elec strip
Type
Split AC
Efficiency
100 EFF
COP / EER / SEER
13.5
Heating Input
6.2 kW
Sensible Cooling
23.8
MBtuh
Heating Output
21.2 MBtuh
Latent Cooling
10.2
MBtuh
Humidifier
10.8 gpd
Total Cooling
34.0
MBtuh
Leaving Air Temp
87.0 OF
Leaving Air Temp
55.0
OF
Actual Heating Fan
1133 cfm
Actual Cooling Fan
1133
cfm
Equipment Location
UNIT TWO
System Type
PEAKCV
Fan Motor Heat Type
PACKAGE
Fan & Motor Combined Efficiency
0
%
Static Pressure Across Fan
0
in H2O
NAME
I Area
ft'
I Heat
Loss
I Sensible
Gain
I Latent
Gain
I Htg I
cfm
Clg I
cfm
Time
SANCTUARY 2
442
10264
12099
10357
288
637
Jul 1900 LDT
OFFICE 2
132
1627
1462
651
114
85
Jul 1900 LDT
OFFICE 1
120
2209
1813
628
186
109
Jul 1900 LDT
PASTOR'S OFFICE
195
3118,
2693
962
249
162
Jul 1900 LDT
H/C BATH
72
3962
2041
3410
297
140
Jul 1900 LDT
UNIT TWO
961
21180
1 20108
1 16007
1 1133
1133
Jul 1900 LDT
2015-0IX-01 18:27:54
Wi1-rFr911r"Joitt RighiSui� universal RSU06570 Page 2
JATransfeAManual AFIRST BORN MINISTRY.rup Cale =CLTD Front Door faces: N
RightSuite® Universal 2015 Load Summary Job:
wrightsoft° UNIT ONE Date: Jul 10, 2015
Y
For: First Born Ministry
US #1, Port St Lucie, FI
.Zone:�UNITQNE° ' GOQLIN!',.LQAD`
r T RI=t
1.
DESIGN CONDITIONS at Jul 1900 LOT
Peak load
at Jul 1900 LDT
Inside: 75 OF Outside: 87 OF
TD:
12 OF
RH: 65 % MoistDiff: 61.5 grllb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
12676
-
3.
TRANSMISSION GAINS Sensible
7425
-
Walls: 1956
-
-
Glass: 2785
-
-
Doors: 87
-
-
Partitions: 0
-
-
Floors: 0
-
-
Ceilings: 2597
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
14212
5004
Occupants: 10623
5004
-
-
Lights: 3589
-
Motors: 0
-
-
-
Appliances: 0
0
-
-
5.
INFILTRATION: Outside air cfm:
32
416
1333
6.
SUBTOTAL: Spaceload Sensible
Latent
34729
6338
Envelope 34729
6338
-
-
Less external 0
-
-
-
Redistribution 0
0
-
7.
SUPPLY DUCT
0
-
8.
SUBTOTAL: Space load + supply duct
34729
-
Actual cfm: 1900 at supply TD:
20
-
-
9.
VENTILATION: Make-up air cfm:
303
3944
12651
10.
RETURN AIR LOAD: Lighting + plenum (net)
0
-
11.
RETURN DUCT
0
-
12.
TOTAL LOADS ON EQUIPMENT
38673
18989
13. DESIGN CONDITIONS
Mult:
Inside: 70 OF Outside:
42 OF TD:
14. TRANSMISSION LOSSES
Walls:
3157
Glass:
6238
Doors:
194
— Partitions:
0
Floors:
1596
Leilinps:= = -_ -
=-1265=—
1.0
28 OF
12450
16.
SUBTOTAL: Space load
- 24705
Envelope 24705
-
Less external 0
-
Less transfer 0
-
Redistribution 0
-
17.
SUPPLY DUCT:
0
18.
VENTILATION: Make-up air cfm:
303 9319
19.
HUMIDIFICATION
5457
Piping
0
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
39481
wri hffioft zolson-011B:z7:sa
g PoghFSuite®Utivema1201515.0.19fSWB570
Page 1
J:1T2nsferlManuaI JIFIRST BORN MINISTRY.rup Cale =CLTD Front Door faces: N
Right -Suite® Universal 2015 Load Summary Job:
wrightsoft° uN►r TWO Date: Jul 10, 2015
By:
Project Information
For: First Born Ministry
US #1, Port St Lucie, FI
LZoos"�UNILYVO_ _` - ' _ �mE0011NG_LOAD" _ .i
1.
DESIGN CONDITIONS at Jul 1900 LDT
Peak load at Jul 1700 LOT
Inside: 75 OF Outside: 87 OF
TD:
12 OF
RH: 65 % MoistDiff: 61.5 gr/lb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
0
-
3.
TRANSMISSION GAINS Sensible
5514
-
Walls: 3323
Glass: 0
-
-
Doors: 0
-
-
Partitions: 0
-
-
Floors: 0
-
-
Ceilings: 2192
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
10785
3794
Occupants: 7667
3794
-
-
Lights: 3119
-
Motors: 0
-
Appliances: 0
0
-
-
5.
INFILTRATION: Outside air cfm:
65
850
2727
6.
SUBTOTAL: Space load Sensible
Latent
17150
6521
Envelope 17150
6521
-
-
Less external 0
-
-
-
Redistribution 0
0
-
7.
SUPPLY DUCT
0
-
8.
SUBTOTAL: Space load + supply duct
17150
Actual cfm: 1133 at supply TD:
20
9.
VENTILATION: Make-up air cfm:
227
2957
9487
10.
RETURN AIR LOAD: Lighting + plenum (net)
0
-
11.
RETURN DUCT
0
-
12.
TOTAL LOADS ON EQUIPMENT
20108
16007
a HALtN131,140A
13. DESIGN CONDITIONS
Inside: 70 OF Outside:
14. TRANSMISSION LOSSES
Walls:
Glass:
Doors:
Floors:
Mult: 1.0
42 OF TD: 28 OF
6731
4068 -
0
0
Envelope
10114
Less external
0
Less transfer
0
Redistribution
0
17.
SUPPLY DUCT:
18.
VENTILATION:
Make-up air cfm:
19.
HUMIDIFICATION
Piping
20.
RETURN DUCT
21.
TOTAL HEATING LOAD ON EQUIPMENT
227
10114
0
6988
4078
0
0
21180
Wai htsofi 2015-Oct-0118:27:54
g RigM.S.ILO 11i M-1 201515.0.19 ML06570 Page 2
JATransfeAManual MIRST BORN MINISTRYaup Cale=CLTD Front Dcorfaces: N
Sheet
fresh verb
x 24
116
1 33
6' —
22'
�24x2
-
18
I crm
212 dm
I
12"
v`y
SANCTUARY
ARFz
188 dm
11
r14`
a
212 dm
I,
766 dm.
I
I
e' 212erm
I
OUTSIDEFRESHAIR UNIT ONE-6'vent 303 CFM, UNIT TWOS* vent
227 CFM. MIXED USE OF OFFICE AND PLACE OF RELIGIOUS
WORKSHOP. OUT DOOR AIR RATE AT 5 CFMIPERSON AND.06
CFM/FT2. Outside freshair will be brought into return pleumns with damp(
with birdscreens.
245 cfm. z
IZ20x24 '
24 x
n
I
245clm
OFFICE
2 k
14 CfM
I
BULJ�24x3d1^
t-;
I
245zfm.'-_
Job #:
Scale: 1 : 110
Performed for:
First eom Ministry
Page 1
RighlSuite® Universal 2015
us 01
Port St Lucie, FI
15.0.19 RSU06570
2015-Ott-01 18:29:04
...Manual J\FIRST BORN MINISTRY