REVIEW COMMENTS
SCANNED
BY
St. Lucie County
1
Owner(s):
St Lucie Mep Ppi Emi Llc
Jurisdiction: ST LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Fax Number: 954-228-6664
Email: Dw@Delmarconstructioninc
.Corn
REVIEWS AND COMMENTS
Review Type
Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Dawn Milone 8131/2015
8/31/2015 Comment:
NOTICE OF COMMENCEMENT
8/31/2015 Comment:
PLUMBING SUB
8/31/2015 Comment:
HVAC SUB
- - -----8/31/2015 Comment:
_ ELECTRICALSUM
-- --- — 8/31/2015 Comment:_
SUB SUMMARY
8/31/2015 - Commen BONING COMPELAN6EAPPLIC-ARE)N-T4BESUBM[WED=BEFEREF4NAL--1NSPEC=TIO^
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Dawn Milone 813112015 813112015
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 9/2212015 9/2212015 9/2212016
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Kevin Singley 9/23/2015
9/23/2015 Comment:
SHOW REQUIRED VENTILATION ON PLANS PER 2014 FBCM CHAPTER 4 ,
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 9/16/2015
Comment:
THIS BUD WITH AN OCCUPANCY CLASSIFICATION OF A-3 REQUIRES SEPARATE SEX RESTROOMS.403.2
9/1612016
FLORIDA PLUMBING CODE 2014
57`�aaczc %w,x
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462.6443
REVIEW COMMENTS
2
Comment:
UNISEX RESTROOMS ARE NO LONGER ALLOWED THEY ARE NOW REFERED TO AS FAMILY OR ASSISTED
9/16/2015
USE TOILET ROOMS AND THIS OCCUPANT COUNT DOES NOT QUALIFY TO USE THEM. SECTION 403.2.1
FLORIDA PLUMBING CODE 2014.
9/1612015 Comment:
WOMENS REQUIRE TWO WATERCLOSETS ,ONE MUST BE ADA TABLE 403.1 FPC 2014
9/1612015 Comment:
MENS RESTROOM REQUIRES ONE WATERCLOSET ,WHICH MUST BE ADA TABLE 403.1 FPC 2014
9/16/2015 Comment:
ONE SERVICE SINK IS REQUIRED .TABLE 403.1 FPC 2014
9/16/2015 Comment:
SECTION 211. OF THE FLORIDA ACCESSABILITY CODE 2014 REQUIRES A HIGH LOW DRINKING FOUNTAINS
Comment:
THIS BUILDING REQUIRES HOT WATER TO THE SERVICE SINK AND THE LAVATORIES PER SECTION 607.1
9/1812015
OF THE FLORIDA PLUMBING CODE 2014
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 911612015
Comment:
TABLE 1004.1.1 IMPRESSED ON PLANS IS FROM THE 2010 BUILDING CODE * WE ARE CURRENTLY
ENFORCING THE 2014 5TH EDITION LIBRARY * DO NOT NEED TO SHOW THE COMPLETE TABLE ONLY
9/16/2015
WHAT OCCUPANCY CLASSIFICATIONS AND SUB -CLASSIFICATIONS PERTAIN TO THE WORSHIP FACILITY
USE 2014 FBC TABLE 1004.1.2 * SEE FBC 305.2.1 FOR ROOMS OR SPACES PROVIDING DAY CARE
Comment:
HOW WAS OCCUPANT LOAD CALCULATED TO ACHEIVE 150 PEOPLE * SHOW A BREAKDOWN ON PLANS
SHOWING BUSINESS AREAS, ASSEMBLY AREAS, STANDING AREAS, PLATFORM AREAS, RESTROOM
9/16/2015
AREAS AND CORRIDOR AREAS * SHOW THE REQUIRED OCCUPANT LOADS FOR SAME AREAS FROM
TABLE 1004.1.2
Comment:
SUBMIT TRIPLICATE FIRE SPRINKLER PLANS WITH CRITERIA SHOWING THE PROPOSED MODIFICATIONS
9/1612015
TO THE EXISTING FIRE SPRINKLER SYSTEM
Comment:
DESIGN CRITERIA BOX ON PLANS TO INCLUDE: THIS IS A CHANGE OF OCCUPANCY PER THE 2014
EXISTING BUILDING CODE CHAPTER 10 : ALL PROVISIONS FROM CHAPTER APPLY AS STATED WITHIN
CHAPTER AND MUST BE NOTED ON PLANS * NOTE THE 2014 F.F.P.C. IN DESIGN BOX, NOTE THE 2014
9/16/2015
ENERGY CONSERVATION CODE IN DESIGN BOX, 2011 NFPA 70 CODE TO BE NOTED ON PLANS AND
ELECTRICAL TO BE DESIGNED TO THESE PROVISIONS, 2012 NFPA 101 DESIGNS LIFE SAFETY PROVISIONS,
SHOW THE DSIGN CRITERIA ON PLANS TO THE 2014 ACCESSIBILITY CODE W/ADAAG
Comment:
DESIGN LIFE SAFETY PLANS IN TRIPLICATE IN ACCORDANCE WITH 2O12 NFPA 101 PROVISIONS * NO
911612015
DAIGONAL LINES OF TRAVEL
Comment:
SEE FBC 1005.7.1 DOORS ** CANNOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE HALF * SEE
9/16/2015
RESTROOM DOORS AND UTILITY ROOM DOOR ON PLANS TYO BE MODIFIED
Comment:
INCLUDE AN INTERIOR FINISH TABLE ON PLANS PER FBC EXISTING BUILDING 1012.3 AND FBC CHAPTER 8
9/16/2015
FOR THE ASSEMBLY OCCUPANCY * INCLUDE FLAME SPREAD INDEX AND SDI
Comment:
SUBMIT TRIPLICATE, APPROVED, CURRENT COMMERCIAL ENERGY CALCS [ SEEC101.4.4 CHANGE IN
OCCUPANCY, 2014 FLORIDA BUILDING ENERGY ] AND TRIPLICATE MANUAL N COMMERCIAL CALCS * YOU
911712015
HAVE SUBMITTED RESIDENTIAL ENERGY FOR A HOME IN MARTIN COUNTY AND SHORT FORM HEATING
AND COOLING CALC / LOADS ARE TO BE VERIFIED * RESUBMIT ALL IN TRIPLICATE * SEE INTERIOR
—---- -------------
--LIGHTING ALLOWANCES C405.5.2-------- -- ---- ---- ---- - - -- - --------
9/1712015 Comment INCLUDE A GYPSUM BOARD AND ACCESSORY CHART ON PLANS [ SEE FBC TABLE 2506.21 SPECIFY ALL
MA7ERtAL-TESTING-STANDARDS-0N:PLAN —
Commenf SEEFBC-SECTIOWT21U-FORT' IL MEN779fSFt VV7TL�ET`AiE N-PEANE
9/17/2015 - FOR THE FLOORS; WALLS, PARTITIONS
9/17/2015 Comment: SHOW THE MALTESE CROSS LOCATION ON A BUILDING ELEVATION PER F.A.C. 69A-60.0081
ZONING REVIEW COMPLETE Lydia Galbraith 9/15/2016 9/15/2015 9/1512015
Comment:
Planning S Development Services
Building 8 Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)462.6443
PROPERTY INFORMATION
Address: 6668 S US 1
City / State / Zip: Port St Lucie, FI 34952
Parcel #: 3415-501-0065-000/4
Zoning:
APPLICATION
Permit Number:
Permit Type:
1601
1508-0464
Cdi]t�luD�e3GL�:Lq t[iv�yNLl
CONTRACTOR INFORMATION
Contractor Name:
Delroy V Wilson
Business Name:
Delmar Construction Group
Business Addr:
6299 W Sunrise Blvd #206
City / State / Zip:
Sunrise, FI 33313
REVIEW COMMENTS
SCANNED
BY
St. Lucie County
1
Owner(s):
St Lucie Map Ppi Emi Llc
Jurisdiction: ST LUCIE COUNTY
Lot#:
Stories:
C
O
ni
c� \• � q
1 � 1
c 3 IIRIrB
C=
0
cn M
Block:
Automatic Sprinkler System? No
Fax Number: 954-228-6664
Email: Dw@Delmarconstructicninc
.Com
REVIEWS AND COMMENTS
Review Tvpe
Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Dawn Milone 8/3112015
8/3112015 Comment:
NOTICE OF COMMENCEMENT
8/31/2016 Comment:
PLUMBING SUB
8/31/2015 Comment:
HVAC SUB
-- -- 8/31/2015.. Comment:
ELECTRICAL SUM
8131/2015 Comment:
SUB SUMMARY
--S/31//20f5 Comirient.=Z49NINGC-AMPLdANCEAP-PLICAllON=TO-BE-SUBMIi
Fn REEOREEINALINSPEC110ti-- -
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Dawn Milone 8/31/2015 8/31/2015
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 9/22/2015 912212015 9/2212015
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Kevin Singley 9/2312015
9/23/2015 Comment:
SHOW REQUIRED VENTILATION ON PLAN 2014 FBCM CHAPTER 4
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 9/16/2015
Comment:
THIS BLD WITH AN OCCUPANCY CLASSIFICATION OF A-3 REQUIRES SEPARATE SEX RESTROOMS.403.2
9/1612015
FLORIDA PLUMBING CODE 2014
V,
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Pbone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
Comment:
UNISEX RESTROOMS ARE NO LONGER ALLOWED THEY ARE NOW REFERED TO AS FAMILY OR ASSISTED
9/16/2015
USE TOILET ROOMS AND THIS OCCUPANT COUNT DOES NOT QUALIFY TO USE THEM. SECTION 403.2.1
FLORIDA PLUMBING CODE 2014.
9116/2015
Comment:
WOMENS REQUIRE TWO WATERCLOSETS ,ONE MUST BE ADA TABLE 403.1 FPC 2014
911612015
Comment:
MENS RESTROOM REQUIRES ONE WATERCLOSET ,WHICH MUST BE ADA TABLE 403.1 FPC 2014
9116/2015
Comment:
ONE SERVICE SINK IS REQUIRED .TABLE 403.1 FPC 2014
9116/2015
Comment:
SECTION 211 OF THE FLORIDA ACCESSABILITY CODE 2014 REQUIRES A HIGH LOW DRINKING FOUNTAINS
Comment:
THIS BUILDING REQUIRES HOT WATER TO THE SERVICE SINK AND THE LAVATORIES PER SECTION 607.1
9/18/2015
OF THE FLORIDA PLUMBING CODE 2014
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 9/1612015
Comment:
TABLE 1004.1.1 IMPRESSED ON PLANS IS FROM THE 2010 BUILDING CODE' WE ARE CURRENTLY
9116/2015
ENFORCING THE 2014 5TH EDITION LIBRARY * DO NOT NEED TO SHOW THE COMPLETE TABLE ONLY
WHAT OCCUPANCY CLASSIFICATIONS AND SUB -CLASSIFICATIONS PERTAIN TO THE WORSHIP FACILITY'
USE 2014 FBC TABLE 1004.1.2 * SEE FBC 305.2.1 FOR ROOMS OR SPACES PROVIDING DAY CARE
Comment:
HOW WAS OCCUPANT LOAD CALCULATED TO ACHEIVE 150 PEOPLE' SHOW A BREAKDOWN ON PLANS
9/1612015
SHOWING BUSINESS AREAS, ASSEMBLY AREAS, STANDING AREAS, PLATFORM AREAS, RESTROOM
AREAS AND CORRIDOR AREAS * SHOW THE REQUIRED OCCUPANT LOADS FOR SAME AREAS FROM
TABLE 1004.1.2
9/16/2016 Comment:
SUBMIT TRIPLICATE FIRE SPRINKLER PLANS WITH CRITERIA SHOWING THE PROPOSED MODIFICATIONS
TO THE EXISTING FIRE SPRINKLER SYSTEM
Comment:
DESIGN CRITERIA BOX ON PLANS TO INCLUDE: THIS IS A CHANGE OF OCCUPANCY PER THE 2014
EXISTING BUILDING CODE CHAPTER 10 : ALL PROVISIONS FROM CHAPTER APPLY AS STATED WITHIN
9/1612015
CHAPTER AND MUST BE NOTED ON PLANS' NOTE THE 2014 F.F.P.C. IN DESIGN BOX, NOTE THE 2014
ENERGY CONSERVATION CODE IN DESIGN BOX, 2011 NFPA 70 CODE TO BE NOTED ON PLANS AND
ELECTRICAL TO BE DESIGNED TO THESE PROVISIONS, 2012 NFPA 101 DESIGNS LIFE SAFETY PROVISIONS,
SHOW THE DSIGN CRITERIA ON PLANS TO THE 2014 ACCESSIBILITY CODE W/ ADAAG
9/1612015 Comment:
DESIGN LIFE SAFETY PLANS IN TRIPLICATE IN ACCORDANCE WITH 2O12 NFPA 101 PROVISIONS' NO
DAIGONAL LINES OF TRAVEL
9/16/2015 Comment:
SEE FBC 1005.7.1 DOORS "CANNOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE HALF' SEE
RESTROOM DOORS AND UTILITY ROOM DOOR ON PLANS TYO BE MODIFIED
Comment:
INCLUDE AN INTERIOR FINISH TABLE ON PLANS PER FBC EXISTING BUILDING 1012.3 AND FBC CHAPTER 8
9/1612015
FOR THE ASSEMBLY OCCUPANCY' INCLUDE FLAME SPREAD INDEX AND SDI
Comment:
SUBMIT TRIPLICATE, APPROVED, CURRENT COMMERCIAL ENERGY CALCS [ SEE C101.4.4 CHANGE IN
OCCUPANCY, 2014 FLORIDA BUILDING ENERGY] AND TRIPLICATE MANUAL N COMMERCIAL CALCS * YOU
9/17/2015
HAVE SUBMITTED RESIDENTIAL ENERGY FOR A HOME IN MARTIN COUNTY AND SHORT FORM HEATING
AND COOLING CALC I LOADS ARE TO BE VERIFIED * RESUBMIT ALL IN TRIPLICATE * SEE INTERIOR
------LIGHTING
ALLOWANCES .C405.5.2___ _______
Cment:
om-
INCLUDE A GYPSUM BOARD AND ACCESSORY CHART ON PLANS[ SEE FBC TABLE 2506.2 ] SPECIFY ALL
— - 9/.17/2015.
MATERIAL-TESTINGSTANDARDS.ON.P-LANS- -- - - - - -
- Comme$ nr----9E157fBCSECTTOM210FOR-TOi ET'AND-BATHROOMREQUIREMENTS+SHOW#tit-DETAILS-ON=PizANS-- - -
9/17/2015
FORTHEFLOORS,WALLS,PARTITIONS
9/17/2015 Comment:
SHOW THE MALTESE CROSS LOCATION ON A BUILDING ELEVATION PER F.A.C. 69A-60.0081
9/2312015 Comment: COMMENTS MAILED AND E-MAILED AS OF THIS DATE
9/23/2015 Comment: UPON RE -SUBMITTAL PLEASE SUBMIT [ 3 ] SETS OF S.S.D. ORIGINAL PLANS W/ [ 21 PDF DISCS FOR RE -
REVIEW
ZONING REVIEW COMPLETE Lydia Galbraith 9/1512016 9/1512015 9/1512015
Comment:
Planning & Development Services
Building 8 Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
Address: 6668 S US 1
City / State I Zip: Port St Lucie, FI 34952
Parcel #: 3415-501-0065-000/4
SCANNED
REVIEW COMMENTS BY
St. Lucie CountV
Owner(s):
St Lucie Map Ppi Emi Llc
Jurisdiction: ST LUCIE COUNTY
1
Zoning: CG Lot#: Block:
APPLICATION INFORMATION
Permit Number: 1508-0464 Stories: Automatic Sprinkler System? No
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
Contractor Name: Delray V Wilson Fax Number: 954-228-6664
Business Name: Delmar Construction Group i
Business Addr: 6299 W Sunrise Blvd #206 Email: Dw@Delmarconstructioninc.
Com
City I State I Zip: Sunrise, FI 33313
REVIEWS AND COMMENTS
Review Type
Status Reviewed By Date Started Date Completed
Date Released
DOCUMENTS MISSING
PENDING Dawn Milano 813112015
8/31/2015 Comment:
NOTICE OF COMMENCEMENT
8/31/2016 Comment:
PLUMBING SUB
8/31/2015 Comment:
HVAC SUB
8/31/2015 Comment:
ELECTRICAL SUM
8/31/2015 -Comment:
SUB SUMMARY - — - - - -- - -
- --- -- - -
-8731/2015 - Comment:_ZONING_COMPLIANGE:AFPLICATIQN.TO
BE SU_BMLTTEDBEFORE-FINAL.INSPECTION_
--
FIRE DEPARTMENT REVIEW
PENDING -- Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Dawn Milano 8/31/2015
8/3112015
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 9122/2015 912212015
9/2212015
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Kevin Singley 9/2312015
9/23/2015 Comment:
SHOW REQUIRED VENTILATION ON PLANS PER 2014 FBCM CHAPTER 4
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 9/1612015
9/16/2015 Comment:
THIS BUD WITH AN OCCUPANCY CLASSIFICATION OF A-3 REQUIRES SEPARATE SEX RESTROOMS.403.2
FLORIDA PLUMBING CODE 2014
JG. �LrG16 UOac�+u2
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone•.(772)462.2172 Fax:(772)462.6443
REVIEW COMMENTS
Comment:
UNISEX RESTROOMS ARE NO LONGER ALLOWED THEY ARE NOW REFERED TO AS FAMILY OR ASSISTED
9/1612015
USE TOILET ROOMS AND THIS OCCUPANT COUNT DOES NOT QUALIFY TO USE THEM. SECTION 403.2.1
FLORIDA PLUMBING CODE 2014.
9/16/2015
Comment:
WOMENS REQUIRE TWO WATERCLOSETS ,ONE MUST BE ADA TABLE 403.1 FPC 2014
9/16/2015
Comment:
MENS RESTROOM REQUIRES ONE WATERCLOSET ,WHICH MUST BE ADA TABLE 403.1 FPC 2014
9/16/2015
Comment:
ONE SERVICE SINK IS REQUIRED .TABLE 403.1 FPC 2014
9/1612015
Comment:
SECTION 211 OF THE FLORIDA ACCESSABILITY CODE 2014 REQUIRES A HIGH LOW DRINKING FOUNTAINS
9/18/2015
Comment:
THIS BUILDING REQUIRES HOT WATER TO THE SERVICE SINK AND THE LAVATORIES PER SECTION 607.1
OF THE FLORIDA PLUMBING CODE 2014
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 911612015
Comment: TABLE 1004.1.1 IMPRESSED ON PLANS IS FROM THE 2010 BUILDING CODE' WE ARE CURRENTLY
9/1612015 ENFORCING THE 2014 5TH EDITION LIBRARY' DO NOT NEED TO SHOW THE COMPLETE TABLE ONLY
WHAT OCCUPANCY CLASSIFICATIONS AND SUB -CLASSIFICATIONS PERTAIN TO THE WORSHIP FACILITY'
USE 2014 FBC TABLE 1004.1.2 • SEE FBC 305.2.1 FOR ROOMS OR SPACES PROVIDING DAY CARE
Comment: HOW WAS OCCUPANT LOAD CALCULATED TO ACHEIVE 150 PEOPLE' SHOW A BREAKDOWN ON PLANS
9/16/2015 SHOWING BUSINESS AREAS, ASSEMBLY AREAS, STANDING AREAS, PLATFORM AREAS, RESTROOM
AREAS AND CORRIDOR AREAS • SHOW THE REQUIRED OCCUPANT LOADS FOR SAME AREAS FROM
TABLE 1004.1.2
9/16/2015 Comment: SUBMIT TRIPLICATE FIRE SPRINKLER PLANS WITH CRITERIA SHOWING THE PROPOSED MODIFICATIONS
TO THE EXISTING FIRE SPRINKLER SYSTEM
Comment: DESIGN CRITERIA BOX ON PLANS TO INCLUDE: THIS IS A CHANGE OF OCCUPANCY PER THE 2014
EXISTING BUILDING CODE CHAPTER 10: ALL PROVISIONS FROM CHAPTER APPLY AS STATED WITHIN
9/1612015 CHAPTER AND MUST BE NOTED ON PLANS' NOTE THE 2014 F.F.P.C. IN DESIGN BOX, NOTE THE 2014
ENERGY CONSERVATION CODE IN DESIGN BOX, 2011 NFPA 70 CODE TO BE NOTED ON PLANS AND
ELECTRICAL TO BE DESIGNED TO THESE PROVISIONS, 2012 NFPA 101 DESIGNS LIFE SAFETY
PROVISIONS, SHOW THE DSIGN CRITERIA ON PLANS TO THE 2014 ACCESSIBILITY CODE W/ ADAAG
9/16/2015 Comment: DESIGN LIFE SAFETY PLANS IN TRIPLICATE IN ACCORDANCE WITH 2O12 NFPA 101 PROVISIONSNO
DAIGONAL LINES OF TRAVEL
9/1612015 Comment: SEE FBC 1005.7.1 DOORS" CANNOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE HALF • SEE
RESTROOM DOORS AND UTILITY ROOM DOOR ON PLANS TYO BE MODIFIED
911612015 Comment: INCLUDE AN INTERIOR FINISH TABLE ON PLANS PER FBC EXISTING BUILDING 1012.3 AND FBC CHAPTER
8 FOR THE ASSEMBLY OCCUPANCY' INCLUDE FLAME SPREAD INDEX AND SDI
Comment: SUBMIT TRIPLICATE, APPROVED, CURRENT COMMERCIAL ENERGY CALCS [ SEE C101.4.4CHANGE IN
OCCUPANCY, 2014 FLORIDA BUILDING ENERGY ] AND TRIPLICATE MANUAL N COMMERCIAL CALCS • YOU
9/17/2015 HAVE SUBMITTED RESIDENTIAL ENERGY FOR A HOME IN MARTIN COUNTY AND SHORT FORM HEATING
AND COOLING CALC / LOADS ARE TO BE VERIFIED' RE -SUBMIT ALL IN TRIPLICATE' SEE INTERIOR
LIGHTING ALLOWANCES C405.5.2
---9117/2015- ---Comment:. __INCLUDE A GYPSUM BOARD AND ACCESSORY CHART ON PLANS [ SEE FBC TABLE 2506.2 ] SPECIFY ALL
MATERIALTESTING STANDARDS ON PLANS -
SHOW ALL DETAILS ON PLANS
9/17/2015 Comment: SHOW THE MALTESE CROSS LOCATION ON A
9/23/2015 Comment: COMMENTS MAILED AND E-MAILED AS OF THIS DATE
9/2312015 Comment: UPON RE -SUBMITTAL PLEASE SUBMIT [ 3 ] SETS OF S.S.D. ORIGINAL PLANS W/ [ 2 ] PDF DISCS FOR RE -
REVIEW
ZONING REVIEW COMPLETE Lydia Galbraith 9/1512015 9/1512015 9115/2015
Comment: