FLORIDA BUILDING CODE, ENERGY CONSERVATION
CHAPTER C4—COMMERCIAL ENERGY EFFICIENCY
Form C402-2014 ALTERATIONS, RENOVATED BUILDING and BUILDING SYSTEMS
Climate Zone:
2
A 0
Project Name: JONES LUMBER
Occupancy type:
Address: 7410 COMMERCIAL CIRCLE
Alteration Renovated Building 0 Building System
City, Zip Code: FT PIERCE FLORIDA 34951
Building Permit No.:
Builder: MRJ PROPERTIES
Permitting OKce: FT PIERCE
Owner. MRJ PROPERTIES
BUILDING ENVELOPE INFORMATION (Where changed)
Requirement
Efficiency
Envelope Component
Description
Location
Unit
Required
Installed
Rooftype
EXISTING
Table C402.1.2 or
Table C402.2
U-factor or
>
_ R-value
NA
Roof reflectancW ittance
(low slope roofs)
EXISTING
Table C402.2.1.1
>_ SolarreBectance,
> Thermal emittance
NA
Wall type, above grade • •
EXISTING CBS ADD R-6
Table C402.1.2 or Table C402.2
<U-factor or
_ R-value
5.7 -
6.0
Wall, below grade: %
EXISTING
NA
Floor type �! :
EXISTING
NA
EXISTING
< U-factor
NA
Vertical fenestratiops '
<SHGC
NA
Table C402.3
NONE
5 U-factor
NA
Skylights
<SHGC
NA
BUILDING SYSTEMS INFORMATION [far HVAC, service hot water or pool heating, lighting systems, and replacement fenestration (C701 A.7)]
System
Type (describe system)
Requirement
Efficiency
Location
Unit
Required
Installed
Air-conditioning system
4TON SPLIT
Tables G403.2.3 (1-3, 6-8, 10-11)
SEER orEER, 1EER
13
14
Heatingsystem
ELECTRIC
Tables C403.2.3(2-6)
HSPF or COP AFUE, E, or E,
1
1
Ventilationlair handling system
<51-11P NOT APPLICABLE
Tables C403.2.10.1(1-2)
Fan power(cfm).-'
NA
NA
Ducts
Location: UNCONDITIONED
Table C403.2.7.1
R-value
6
6
Piping
Fluid design operating temp:
Table C403.2.8
Inches
EXISTS
Hot water
Table C404.2
EF,E COP
NONE
Lighting
�{ WA(*s'(fappy d list)
Table C405.5.2 (I or 2)
Lighting power density
1.6
1.67
Fenestrations: Enter informatiQll' _ �� f7.1 FORMATION box above.
Other. \\
! \CEIV S`"k,t///
i
COMPLIANCE IS BYAIQSUAS RAFJIESNA
(Submit alternate form o0p documents as needed) I —_
1 hereby certify that the pM d peoiticatio covemtl by the;caiculadon are in compliance with the
Review of plans and specifications covered by this
Florida Building Code, E� ry a 9% j I —
PREPARED BY: �� ^ (�Y;fS j
calculation indicates compliance with the Florida Building
Code, Energy Conservation. Before construction is
F•`
DATE: �=`
1 hereby ce2"N that this bui*the,F o 'tl GbActing Code, Energy Conservation:
V" �f1)v
completed, this building will be inspected for compliance
in accordance with Section 553.908, F.S.
OWNERIAGENT. "•.,; ..�.\V
BUILDING OFFICIAL:
""
DATE:
FLORIDA BUILDING CODE— ENERGY CONSERVATION, 5th EDITION (2014) C-C.1
b 1 ' / ' 1 ' Copyright to, or licensed by, IOC (ALL RIGHTS RESERVED); accessed by Loucks Engineering, Inc. on Jun 3, 2015 10:05.41 AM pursuant
to License Agreement. No further reproductions authorized.
Air System Sizing Summary for JONES LUMBER
Project Name: 15259 JONES LUMBER 09/01/2015
Prepared by: Dave Loucks 12:20PM
Air System Information
Air System Name .................................... JONES LUMBER
Equipment Class .......... _ ...................................... SPIT AHU
Air System Type ............ .......... ..................... ------ ....... SZCAV
Sizing Calculation Information
*w Zone and Space Sizing Method:
Zone CFM ................. ...___ Sum of space airflow rates
Space CFM .. ..................... Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load --- .................................. __._::..................._.....
3.8
Total coil load ___._____ _- ____..._..._______._
_ _45.3
Sensible coil load...............................................................
34.3
Coil CFM at Jun 1500--- __:...._:.,:
,:_ 1513
Max block CFM---------------------------------------- _------------------------
1513
Sum of peak zone CFM..................................................
1513
Sensible heat ratio ------------------- .------------- ------ .--- ---
----- _. 0.758
ft2fron_------------------- ,-.....................................
_........ 334.0
BTU/(hr-W)...---- --------------------- ,_._ ..___, . _..._...__.____
35.9
Water flow @ 10.0'F rise ................................................
NIA
Number of zones
Floor Area ...........:
Location ...........-_
Calculation Months
Sizing Data.._._......
Tons
Load occurs at ..............
MBH
OADB/WB..................
MBH
Entering DB/WB------ _
CFM
Leaving DB / WB.........
CFM
Coil ADP ..______..___
CFM
Bypass Factor ...............
Resulting RH ._.__.__....
Design supply temp....
Zone T-stat Check.......
Max zone temperature
Central Heating Coil Sizing Data
Max coil load __---- --- -------- : ----- --- _._._--- _--- ___ .--- ... 18.9 MBH
Coil CFM at Des Htg........................................................ 1513 CFM
Max coil CFM------ ------ _.------ ------- ...... __---- ..----- .----- __------- _ 1513 CFM
Water flow @ 20.0'F drop N/A
Supply Fan Sizing Data
Actual max CFM................................................................ 1513 CFM
Standard CFM ________ - _ __ ___ ___,_,___:..: __----- 1512 CFM
Actual max CFM/ft2............................. _............................. 1.20 CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM 226 CFM
CFM/$'---------------------- _------- ------- _------- ------ _.___ _______ 0.18 CFM/ft2
-- ..............................I
....._.----- ,_.____ ___....1260.0 112
West Palm Beach, Florida
to Dec
.Jun 1500
90.0178.0 'F
78.3166.1 'F
57.3 156.2 'F
.......... 55.0 'F
_..._.. 0.100
...... 50 %
-58.0 'F
1 of 1 OK
0.0 'F
Load occurs at_ _---------- ...---- ___ --- .------- ---------------- ..._..... Des Htg
BTU/(hr-ft2)............................................... _.... ______________ 15.0
Ent. DB/Lvg DB......................................................... 65.9/ 77.5 'F
Fan motor BHP ---------- ....._,------ :_.---------- .--- .., ____ ---0.00 BHP
Fanmotor kW ...... ................................ _................................... 0.00 kW
Fan stalio-,_ _ __......_ —__.-__._________::.........._........ 0.00 in wg
CFM/person ---- ._........____._____._____.___.::......:.:....... 22.62 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
Zone Sizing Summary for JONES LUMBER
Project Name: 15259 JONES LUMBER 09/01/2015
Prepared by: Dave Loucks 1220PM
Air System Information
Air System Name _____- ....................... JONES LUMBER
Equipment Class...,SPLTAHU
Air System Type -- ---- ....................... SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ........... ---------------- -- Sum of space aft -flow rates
Space CFM ------------ __ Individual peak space loads
Zone Sizing Data
Number of zones ------ -......... .._.................. -.. -1
Floor Area __. ....... .--- ___--- ........... _-.__--- ------ 1260.0 ft'
Location ---------------------------- --------- West Palm Beach, Florida
Calculation Months
Sizing Data ........ ...._
to Dec
Maximum
Design
Minimum
Time
Maximum
-Zone
-
cooling
Air
f Air
of
Heating
Floor
Sensible
Flow
.Flow
Peak
Load
Area
Zone
Zone Name
(MBH)
(CFM)
(CFM)
.Load
(MBH)
_ (ft')
_ . CFMITP,
Zone 1
27.8
1513
1513
Sep 1500
11.7
1260.0
1.20
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling
Time
Air
Heating
Floor
Zone Name./
Sensible
of
Flow
Load
.Area
- Space
_ Space Name
Mult.
(MBH)
Load
(CFM)
(MBH)
(fP)
CFM/ft?
Zone 1
SHOWROOM
1
27.81
Sep 1500
1513
11.7
1260.0
1.20
Hourly Analysis Program v4.50 Page 1 of 1
Air System Design Load Summary for JONES LUMBER
Project Name: 15259 JONES LUMBER 09/01/2015
Prepared by: Dave Loucks 12:20PM
DESIGN COOLING
DESIGN HEATING
COOLING DATAAT Jun 1500
COOLINGOADB/WB 90.0°F/78.0°F
HEATING DATA AT DES HTG
HEATING OA DBI WB 43.0 OF/36.1 OF
ZONE LOADS
.Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
188 ft2
7612
-
188 ft2
-
-
Wall Transmission
1864 ft2
2338
-
1864 ft2
4747
-
Roof Transmission
1260 ft2
2970
-
1260 ft2
1680
Window Transmission
188 ft2
2465
-
188 ft2
5279
Skylight Transmission
Oft'
0
-
Oft'
0
-
Door Loads
0 ft2
0
-
0 ft2
0
-
Floor Transmission
1260 ft2
0
-
1260 ft2l
0
-
Partitions
0 ft2
0
-
0 ft2
0
-
Ceiling
0 ft2
0
-
0 ft2
0
-
Overhead Lighting
2520 W
8597
-
0
0
-
Task Lighting
0 W
0
-
0
-0
-
Electric Equipment
0 W
0
-
0
0
-
People
10
2450
2050
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
0%/0%j
0
0
0%1
0
0
>> Total Zone Loads
-
26432
2050
- 11706
- -0
Zone Conditioning
-
25274
2050
-
12336
0
Plenum Wall Load
0%
0
-
0
0
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Return Fan Load
1513 CFM
0
-
1513 CFM
0
-
Ventilation Load
226 CFM
3351
8908
226 CFM
6571
0
Supply Fan Load
1513 CFM
0
-
1513 CFM
0
-
Space Fan Coil Fans
-1
0
-
-
1 0
Duct Heat Gain / Loss
0%
0
-
0%
0
-
>> Total System Loads
- 28625
10958
18906
0
Central Cooling Coil
-
34308
10958
-
0
0
Central Heating Coil
-
-5683
-
-
18906
-
>> Total Conditioning
-
28625
10958
_ _ -
18906
0
Key:
Positive values are clg loads
Negative values are htg loads
.Positive values are htg loads
Negative values areclg loads
Program v4.50 Page 1 of 1