Loading...
HomeMy WebLinkAboutSUBMITTED PAPPERS 1' x GENERAL NOTES RAYD. REINHARD, P.E. ,1. The design and construction of the structure and/or structural components depicted on this plan are fully ., under the jurisdiction of the 1997 Standard Building Code. 2. All specified bolts (anchor bolts or other) shall be structural quality -ASTM 307 or better. • 3 ^ Prior to consWctlon, engineer shall review approved truss drawings with uplift loads for compatibility with these details and specifications. 4' Trusses depicted are schematic only. Refer to manufactures recommendations for proper design, drawings, lumber grade, bracing, installation, etc. - Truss plan is to be certified by a professional engineer with a note staling that the trusses are designed for the specified wind loading. Individually certified truss shop drawings are to be provided listing the uplift reactions for each truss. 5. All specified pre -fabricated fastening devices shall be installed in accordance with the manufacturers recommendations, use nailing for maximum load development 8. DESIGN LOADS Loads used for the design of structural components: Roof Loads Dead Loads 240 PSF Live Load 16 PSF Floor Loads Dead Load 15 PSF Live Load 40 PSF Conc. Structures Dead Load 150 PCF 1p Wind Load (L MPH (39PSF Basic, with applicable shape factors) Allow. Soil Pressure 2600 PSF (98%compaction density required) 7. CONCRETE - Cast in place concrete shall achieve a 28 day compressive strength as follows: Beams/Girders 3500 PSI -5"Slump Foundation 3000 PSI-3"to5"Slump Grout (cells) 2000 PSI - 8" to i"" Slump - Cast in place concrete shall be designed, mixed, placed and cured in accordance with ACI standards. 8. REINFORCEMENT - Concrete reinforcing bars shall be deformed new billet steel conforming to ASTM A-615, Grade 60. - All splices shall be lap splices. Splices shall be a minimum of 40 bar diameters, using larger bar diameters when splicing different size bars. - Reinforcement may be bent in shop or field provided that: Diameter of bend shall be greater than 6 bar diameters. Reinforcement partially embedded in concrete shall not be bent - Secure reinforcement from displacement during concrete placement utilizing chairs and bolsters. - Welded wire mesh shall conform to ASTM A-185. Provide chairs and bolsters to insure that the mesh is embedded 1" from top of slab. - Minimum concrete cover shall be: Footings 3" Beams, Slabs, & Walls 1 - W up to No. 5 Bar 2" No. 6 Bar and Greater Grouted Masonry Walls 2" - Standard 90° Hook is reinforcing bar terminating with a 9D° bend and an extension from bend at least 12 bar diameters. This shall be used at all vertical reinforcement terminations into tie beams and foundations. 9. GROUTED MASONRY CONSTRUCTION - All concrete masonry units shall comply with ASTM C-90 with type M or S mortar complying to ASTM A-270. - Min. net area compressive strength or CMU units shall be 1900 PSI. - All grout used in CMU cells shall have a maximum course aggregate of 3/8", shall be placed with a slump of 8" to 11", and shall have a min. compressive strength of 2000 PSI at 28 days, and shall be in accordance with ASTM C-476. - All exterior CMU walls shall be grouted and reinforced with 1 reinforcing bar with bar size and spacing as shown on typical section or plan. Provide W Gear distance between any inside cell wall and reinforcement bar. Ensure that cells that are to be grouted line up properly and have a min. dear area of 10 sq. in. and a min. 1 Gear distance of 3". Reinforcing bar lap splices shall be a minimum of 48 bar ^ diameters. - Provide clean -out openings at all filled cell locations at bottom course. Spaces to be grouted shall be free of mortar droppings, debris, loose aggregates, or other deleterious materials. SCANNED BY St Lucie County GENERAL NOTES RAYD. REINHARD, P.E. .1. The design and construction of the structure and/or structural components depicted on this plan are fully under the jurisdiction of the 1997 Standard Building Code. 2. All specified bolts (anchor bolts or other) shall be structural quality -ASTM 307 or better. 3. Prior to construction, engineer shall review approved truss drawings with uplift loads for compatibility with these details and specifications. 4. Trusses depicted are schematic only. Refer to manufactures recommendations for proper design, drawings, lumber grade, bracing, installation, etc - Truss plan is to be certified by a professional engineer with a note stating that the tosses are designed for the specified wind loading. Individually certified truss shop drawings are to be provided listing the uplift reactions for each truss. 5. All specified pre -fabricated fastening devices shall be installed in accordance with the manufacturers recommendations, use nailing for maximum load development. 6. DESIGN LOADS Loads used for the design of structural components: Roof Loads Dead Loads 2jo PSF Live Load 16 PSF Floor Loads Dead Load 15 PSF Live Load 40 PSF Conc. Structures Dead Load 150 PCF �.77pp Wind Load ItO MPH (W PSF Basic, with applicable shape factors) Allow. Soil Pressure 2500 PSF (98 % compaction density required) 7. CONCRETE - Cast in place concrete shall achieve a 28 day compressive strength as follows: Beams/Girders 3600 PSI-5"Slump Foundation 3000 PSI - 3" to 5" Slump Grout (cells) 2000 PSI - 8"toll" Slump - Cast in place concrete shall be designed, mixed, placed and cured in accordance with ACI standards. 8. REINFORCEMENT - Concrete reinforcing bars shall be deformed new billet steel conforming to ASTM A-615, Grade 60. - All splices shall be lap splices. Splices shall be a minimum of 40 bar diameters, using larger bar diameters when splicing different size bars. - Reinforcement may be bent in shop or field provided that Diameter of bend shall be greater than 6 bar diameters. Reinforcement partially embedded in concrete shall not be bent. - Secure reinforcement from displacement during concrete placement utilizing chairs and bolsters. - Welded wire mesh shall comorn to ASTM A-185. Provide chairs and bolsters to insure that the mesh is embedded 1" from top of slab. - Minimum concrete cover shall be: Footings 3" Beams, Slabs, & Walls 1 - W up to No. 5 Bar 2" No. 6 Bar and Greater Grouted Masonry Walls Z. - Standard 90" Hook is reinforcing bar terminating with a 90° bend and an extension from bend at least 12 bar diameters. This shall be used at all vertical reinforcement terminations into tie beams and foundations. 9. GROUTED MASONRY CONSTRUCTION - All concrete masonry units shall comply with ASTM C-90 with type M or S mortar complying to ASTM A-270. - Min. net area compressive strength or CMU units shall be 1900 PSI. - All grout used in CMU cells shall have a maximum course aggregate of 3/8", shall be placed with a slump of 8" to 11", and shall have a min. compressive strength of 2000 PSI at 28 days, and shall be in accordance with ASTM C-476. - All exterior CMU walls shall be grouted and reinforced with 1 reinforcing bar with bar size and spacing as shown on typical section or plan. Provide W' clear distance between any inside cell wall and reinforcement bar. Ensure that cells that are to be grouted line up property and have a min. Gear area of 10 sq. in. and a min. 1 dear distance of 3". Reinforcing bar lap splices shall be a minimum of 48 bar diameters. - Provide dean-0ut openings at all filled cell locations at bottom course. - Spaces to be grouted shall be free of mortar droppings, debris, loose aggregates, or other deleterious materials. I , Department of Community Affairs - FLORIDA ENERGY EFFICIENCY CO'DE ' FOR BUILDING CONSTRUCTION FORM 60OA-97 Residential Whole Building Performance Method I A CENTRAL 4 5 6 OFFICE* 1. New construction or addition 2. Single family detached or Multifamily attached 3. If Multifamily -No. of units covered by this submission 4. Is this a worst case? (yes / no) 5. Conditioned floor area (sq. ft.) 6. Predominant eave overhang (ft.) 7. Glass type and area: a. Clear glass b. Tint, film or solar screen .8. Floor type and insulation: a. Slab -on -grade (R-value + perimeter) b. Wood, raised (R-value + sq. ft.) c. Concrete, raised (R-value) 9. Net Wall type, area and insulation:. a. Exterior: 1. Concrete block (Insulation R-value) 2. Wood frame (Insulation R-value) 3. Steel frame (Insulation R-value) 4. Log (Insulation'R-value) 5. Other:. b. Adjacent: 1. Concrete block (Insulation R-value) 2. Wood frame (Insulation R-value) 3. Steel frame (Insulation R-value) 4. Log (Insulation R-value) 10. Ceiling type, area and insulation: a. 'Under attic (Insulation R-value) b. Single assembly (insulation R-value) c. Radiant barrier installed (yes / no) 11. Air distribution system: a: Ducts (Insulation + Location) b. Air Handier(Location) 12. Cooling system: (Types: central -split, central -single pkg., room unit, PTAC., gas, none) 13. Heating system: (Types: heat pump, elect strip, net. gas, L.P. gas; gas h.p., room or PTAC'„none) 14. Hot water system: (Types: elec.;,natural gas; solar, L.P. gas, none) 15. Hot Water Credits: a. Heat Recovery (HR) b. Dedicated Heat Pump(DHP) c. Solar 16. HVAC Credits (Use: CF-Ceiling Fan, CV -Cross vent, PT -Programmable thermostat, HF-Whole house fan; MZ•Multizone) 17. COMPLIANCE STATUS: (PASS if As -Built Pts. are less than Base Pts.) a. Total As -Built points b. Total Base points I hereby certify that the plans and specifications covered by the calculation are in I Ri compliance with the Florida Energy Code. ® in 3• NO.: t. /yew 2. v! F 3. 4.CS 5. 21 -7 V sq.. ft. 6. Z ft. Single Pane Double Pane 7a. sq. ft. sq. ft. 7b. 1 5�7 sq. ft. sq. ft. 8a. R= 1. ft. 8b. R= sq. ft. 8c. R= sq. ft. 9a-1 R= S. 7 262 sq. ft. 9a-2 R= sq. ft. 9a-3 R= sq. ft. 9a-4 R= sq. ft. 9b-1 R= _ sq. ft. 9b-2 R= sq. ft. 9b-3 R= sq. ft. 9b-4 R= sq. ft. 10a.R= c) 1307- sq. ft 10b. R= sq. ft 10c. 11 a. R= 6 r% tic fwndhmmnp ) 11b. Corr t.{ wed./uncwd.j 12a. Type: neg"I s.ne(a 12b. SEER/EER/CO- P 12c. Capacity: 13a. 'Type: e(ec. sk,'ej 13b. RSPF/COP/AFUE: 13c, Capacity: 14a. Type: C e C 14b. EF: .r!H 15a. 15b. 15c. 16. &r construction is con compliance in accord BUILDING OFFICIAL: CK the Florida Energy 'Code. Before this building will be inspected for VIL g 'f Revised 1998 CI IMMM rAl rIILATIONS CLIMATEZGNES 4 S' 6 MEN � �fSwrmwYImmomm �Ii]►7�7 • J m'I"f�� r't� fZa®mu= sw w®®�®®�■�I�J wzmjj ® rrkra COND WEIGHTEDGLASS BASE x FLOOR x MULTIPLIER = GLASS AREA SUBTOTAL .18 170 142.077 COMPONENT DESCRIPTION . AREA 'x UMMER BASESUMMER BASE POINT. MULT. = SPOINTS .EXTERIOR 1.9 ADJACENT' _ _. _7 3 EXTERIOR 22v c ADJACENT 0 COOLING I t5A=uuuu SYSTEM SYSTEM /2, HOT NUMBER BASE BASE OF x HOTWATER,._ HOTWATER' WATER BEDROOMS _ MULTIPLIER POITS SYSTEM _3-.- 2564 7G �L AS -BUILT GLASS -SUBTOTAL COMPONENT DESCRIPTION AREA SUMMER x POINT. MULT. = 0-2THRU 6A-6 AS -BUILT SUMMER _ POINTS. ev- . CBS :sr,r 2G2 , o - z AS -BUILT NUMBER - AS -BUILT' - AS -BUILT _ AS -BUILT HOTWATER OF x HWM x HWCM = HOTWATER SYSTEMDESC. ..BEDROOMS 6A-9) (6A-201 I POINTS. el ems, 3 1 V" 1 '7 u v - . SUMMER POINT MULTIPLIERS (SOM) ' 6A-1 SUMMER OVERHANG FACTORS(SOF) FOR SINGLE AND DOUBLE PANE GLASS. CLIMATEZONES 4 5 6 North 1:00 0.992 0.971 0.931 0.691 0.8 - 0. 11 0.776 0.748 0.695 0.651 0.611 m Southeast wo -Sou1R 1: 649 0776 07 0. 0.618 0. 0.53 0.503 .475 y Southwest T. 0.997 0,956 0.874_, 0.793. 0.709 0.645 0.588 0.547 0.47R 0.431 0.396 West 1.00 0:994 0.964. �0.902 0834 0.757 - 0.691 0.630 0.582 - 0.500 OA38 0.391. .Northwest 1.00 0.995 0.966 6:oil 0.857 0.798 0751 0.708 0.674 6 0.570 0.532 ,OHLen1h 0.0, 1.9 '1:5' I 2:0' 6A-2 WALLSUMMERPOINTMULTIPLIERS(SPMI FRAME WOOD- STEEL CO_NCRETEBLOCK ORMALVQ INTERIOR - INSULATION FACEBRICK LOG EXT. INSUL R-VALUE' WOODFR R-VALUE BLOCK 0-6.9. 2.9 0.2.9 1.0 61NCH 81NCH R-VALUE' EXT AW' EXT' ADJ A -VALUE _ EXT AW EXF 7-10.9 .6 3-6.9 ,6 _ R-VALUE EXT EXT '.6.6.9 6.4 2.2 8.9 2.9_ 0-2.9 25 .9 2.5 _11.18.9 .4 7.9.9 .4 0.2.9 1:7 1.0 7.10.9 2.3. .8 4A 1.3 3-4.9 1.4 .7 .7 19-25.9 .2 10&LP :2. - 3-6.9 1.1 - .8 11-12.9. 1.9 . .7 3.0 1.0 5-6.9 1'.0 .6 .3 26 &.0 .1 7 & U . ..8 .7 13-18.9 1.7-. .6 2.8 0.9 7-10.9 .4 :1 NOTE:SEESECTION2.00FAPPENDLXGFORMULTIPLIERS OF EWELOPE COMPONENTS NOT ON THIS FORM:. 19-25.9 1.0 .3 2.4 0.8 11-18.9 .4 .3' 0 26&U .6 :2 1.3 0.4 19-25.9 .2 .2 26 & U .1 .1 ITA-6 IWILINAIIUN&INIEHNALUAINS 5PM ' � � ..Yt9.Y'"7u'=tionAnterna[Gains I 44:31bined) 6A-7A AIR HANDLER MULTnIPLIER fSPM1 Located in attic 1.04. Located in ara 1.00 Locatedincondidonedarea I a:93 Located on exterior of builoidg RA.R enniimn SVATFmmiii TipiipnS(rgmi 6A=7 DUCT MULTIPLIERS IOMTsePnnuFme�.e�nomMim�a. SUPPLYDUCTSIN: DUCT R-Value RETURN DUCTSIn: UNCONDITIONEDSPACEATTIC WITH MIS CONDRIONED SPAC UnoenditionedSpace 4.2 '1.065 1.061 10 6.0 Y.048 1.045 1.044 .8.0. 1.037 _ t:035 Attic with Radiant Barrier.(RES) 4.2 1.046 L043 1.040 6.0' 1.034 1.032 1.030 8.0 1.02 -'1.025 1.224 Conditioned Space. 4:2 T.003 1.002 1.0 6.0 1.002 1.001 .0 -8.0 1 1.001 '1.001 SYSTEMTYPE Se Tab!e_s•3forCddeminiinums COOLINGSYSTEMMULTIPLIERS CSM Centre) Units RaVnq 1_ 7.5-7.9 1 8.0-8.4 8.5-8.8 1 8.9-9.4 i 9:5-9A to.0-10.4 10.5-10.9 11.0-11A 1 ,9 11;20 12.0-12.4 (SEER) CSM .45 .43 .40 - .38 - .36 %4 �:32 .31 -- .28 PTAC&Room Units.(EER) Raliri 12.5-12.9 13:0.13.4 13.5-13.9 14.0-14.4 14:5-14.9 15:0-15:4 15.5-15.9 16.0-16A 16!5-16.9. 1717. CSM .27 126. .25 .24 .24 .23 .22 .21. .27 .19 911.0 WnTWATFCILIITI MITI IFCCAJWIAI SYSTEMTYPE Seeie14e6.12torCooem'mimums HOTWATERMULTIPLIERS HWM - Electdc Resistance EF .80-.81 .82..83 .84-.85 .86-:87 :88,90 .91-.9 .94-.96 . 7& U HWM 2820 2752 2685 2624' 2564 2479 2326 Natural Gas EF _43..47 .48-:49' .50-51 .52-.53 .%.55 ,56-.57 .58-.59 .60-.61 .62-.63 .66 & U HWM 2162 1936 1859 1787 1721 1660 1602 1549 1499 1452 1408 LP Gas HWM 2645 2368 2274 2186 2106 -2031 1960 1895 1834 1776 1722 Ded. HP or Solar 'EF - 1.0.1.49 1.5-1.99 2.0.2A9 2.6-2.99 3.0-3.49 3.5-3.99 4.0-4.49 4.5-4.99 -5.0-U System with Tank HWM. '.2256 -- 1504 1128 902. '752 645 564 501 -451 .3- WINTER POINT MULTIPLIERS (WPM) 6A-10 WINTEROVERHANGFACTORS(WOF) « CLIMATEZONES 4 5 6 North 1.00 0.998 0.996 0.995 0.995 -0.994 0.993 0.992 0.990 0.988. 0.986 0.984 r m . Sou _7 L.._1,939 �a _ .. 1.2,291 W I Southwest .00 1.002 1.013 I.M - 1.071 1 118 1.168 1.225 1.278 1.490 1.573- II` West 1.00 0.M 1-.003 1.013_ 1.025 1.040 1.053 1:067 1'.077 1.095 1:107 1-.116' Northwest 1.00 0.999.. 0.998 . 97- 0.997 0.996 0.995 0.994 0.993 0.9 00 0.989 OH Lencith 1 0.0' 1 1.9 1 1:5' 1 2.V 3.Y 3.5' 4.5' c 6A-11 WALLWINTERPOINTMULTIPLIERSIWPMI FRAME WOOD STEEL CONCRETE BLOCK NORMAL _ FACESIRICK I LOG INTERIOR .INSULATION. EXT., INSUL R-VALUE. WOODFR R-VALUE, BLOCK 06.9 7.0 1 0-29 1 3.7 1 i6iNCH :81NCH R-VALUKEXr ADJ EXT ADJ R-VALUE EXT ADJ EXT' 7-IV9 2.1 3-6.9 2.6 R-VALUE EXT EXT 06.9 5.3' 9.4'. 1.7 0-2.9 6.0 1.1 61 11-18.9 1.7 �7-9.9 1.8 0-2.9 22 12 7.10.9 2.1 4.4 3.3 3-0:9 3.8 2.3 2.8 19-25.9 1.0 10&•UP11.12.9 1.8 3.3 26 56.9 2. .9` 2.0 26&L :6 7&U .9 '7 13-18.9- 1.6 3.0. 2:4 7-10.9 2.. •1.1 1.519.25.9 NOTE:SEESECTION2.00FAPPENDIXCFORMULTIPLIERS. OF ENVELOPE COMPONENTS NOT ON THIS FORM. 1.0 2.6 2.2 '11.18.9 1.5' .8 26&U .7 1A 12 19-25.9 .8� .7 26&,U _ .5 .5' 6A-12 DOOR.WINTER POINTMULTIPLIERS(WPM) DOOR TYPE 'EXTERIOR. ADJACENT WOOD, 7.6 5.9 INSULATED 5.T 4.0 6A-14 FLOOR WINTER POINTMULTIPLIERSIWPMI 6A-13 CEILING UNIT R TTI SINGLEASSEMBLY CONCRETE DECK ROOF CEILING TYPE R-VALUE WPM R-VALUE WPM 19-21.9 1.0 10-10.9 1.8 R-VALUE EXPOSED I DROPPED 22-25.9 .9 11-12.9' 1.6 10-13.9 1.02 0.83 26-29.9 .7 13-18.9 1.5 '14-20.9 0.59 0.49 - 3037.9 .6. 19-25.9 1.1 -21 &.0 0.26 023 -'38&U .4 26.29.9- - .6. ISO e It 30 & Up A SLAB -ON -GRADE EDGEINSULATION RAISED CONCRETE' RAISED WOOD ' ' POST OR PIER STEMWALLW/UNDER ADJACENT CONSTRUCTION FLCORINSULATION R-VALUE WPM R-VALUE WPM R-VALUE. WPM WPM WPM 0-2.9 2.5 0-2.9 _- 4.0 _ D-6.9 2.49 - 1.8 _ 5.3 3.4.9 -1.7 3-4.9 1.8 7-10.9 0.78 _ :7 _ 2.1 56.9 -2.4 "A 1.1 11-18.9 - 0:47 .5 ,8 7&U -2.7 7&U .8 19 & Up 0.14 - .3 6A-15 INFILTRATION &INTERNALGAINS P Willem, Gdm ,'RM� t�JO °• Infiftration4bternalGains -0.28 (Combined) RA.1AA, AIRHANnIPRmiu T1D11PGRMIDvn Located in a6ic 1.04 Located in oaraua 1.00 Located inoonditioned area 0.93 -Located onexteriorofbuilding "d1:94 BA.17 HPATINRRVQTPUMIII"DIICRC/HCO� 6A.16 DUCTMULTIPIIFRSrnMI SUPPLYDUCTSIN: DUCT R-Value RETURN DUCTSIn: _ UNCONDITIONED SPACE ATTIC WITH RBS CONDITIONED. SPACE Unconditioned Space 4.2 1.099 1.091 6.0 - 1.073 1.067 _1.063 8.0 1.056 1.052 1. AfbcwithRadiantBanier(RBS) 42 1,071 1.063 1.055 6.0 1053 1.047 1.040 O .042 - 1.037 1.333 Conditioned Space 42 1.008 1.005 6.0 1.006 1.004 - 1.0 !8.0 L005 1.003 - SYSTEMTYPE See Tabiees.6to6-8teroedeminimems HEATING SYSTEM MULTIPLIERS HSM Central Heat HSPF 6.40-6.79 6.80.6.89 1 6.90-7.39 7.40.7.89 7.90.8.39 8.40.8.89 1 8.9-9.39 1 9.4.9.99 Pump Units HSM - - .53 .50 1 .49.. .46 .43. .41 .38 .36 HSPF _ 9.90-10.39 10.40-10.89 1 10.90-11:39_ 11:40-11.89 11.90.12.39 1240 &u HSM .34 .33 .31 .30 .29 - .28 PTHP COP 2.50-2.69 2.70.2.89 2.903.09- 3.10.3.29 3.30-3.49 3.50-3.69 8.70-3.89 3.90-4.19. HSM. .40. .37 .34. :32 .30 .29 .27 - 26 Electric Strip 1,0.E f-- Gas &LP Gas 1.0(SeeTabkg&jitMuftiplier) s a: WINTER CALCULATIONS CLIMATEZONES 4 5 6 OEM Allmom7rMEFE, mufflam Mm® rwt•� r�s arl s w wryri Q�w �.��±���■wwrw�■wr■ �ww �sa.�se�.i���w?�w■�� �:Iww �se�>•��w�jww■� �w—�Iww�w■■�� ww r���www��w�ww www �w��w�w�w■ w�www�ws�l� ww ��ww�w■� ww ��ww�w•� COND' W_EIGHTEDGLASS BASE g ,jg x FLOOR z .MULTIPLIER GLASS AREA SUBTOTAL .18 O 1 4.79 / COMPONENTBASEWINTER AREA REA x BASE POINT.MULT, POINT'S EXTER OR Zv 2.0 yG. ADJACENT 1:8 a 3 s 'EXTERIOR 5:1 ADJACENT1 4.0 0 ?,ilk14 F 1 : 0 WWKFC-" BASEHEATING I TOTALBASE BASE SYSTEM SYSTEM x WINTER, = HE -- MULTIPLIER POINTS POINTS 1.07 1 &.75F,6 BASE BASE a COOLING + HEATING F POINTS - POINTS 71 Fram P.2 72pY,L; 'H = HORIZONTAL GLASS (SKYLIGHTS) AS -BUILT GLASS SUBTOTAL J v COMPONENT DESCRIPTION AREA x WINTER POINT.MULT. (6A-11THRU6A-15) WIBUILT = WINTER POINTS f, 6,14 .. - c1[ Zia S C-i •- uz- TOTAL AS --,BUILT ASBUILT ASBUILT AS -BUILT AS -BUILT AS -BUILT x DM x AHU z HSM z HCM = HEATING WIN.PTS. 6A-16 6A16A BA-1 6A-18 POINTS 16/7r,a Sce G r,- z6. BASE I COOLING —HEATING I HF om P?21R 'DINTS POINTS .POINTS POINTS er on P.1 (From P. 21 U u_ vo TOWN SHGC OR SC, SEE SECTION 21.APPENDIX C. TINT MULTIPLIERS MAYBE -4- ADDITIONAL TABLES SAAR HFATINGCREDITMULTIPLIERS(HCMI CLIMATEZONES 4 5' 6 SYSTEMTYPE _ HEATING CREDIT MULTIPLIERS HCM Programmable Thermostat HCM' .95 _ MultIzone- - HCM _ _ .95 Natural Gas AFUE_ .68-.72 1 .73-:77 1:78-:82 .83-.87 _ .88-.92.. .93&U HCM .56 1 .52 1 .49 .46 .44 .41 LP Gas HCM: _ .71 .68 .62 .5B .55. 1 ,52 7 6A-19 COOLING CREDITMULTIPLIERS(CCM) SYSTEM TYPE COOLING CREDIT LII ERS CCM C!edIt may be takegfor�only, one of these system types concurrently. Ceilia Fans :95' Cross Ventilation _ -Whole-HousaFan'. , _ ..�-� � _ :_..- -.95.- Multizone, .95 Programmable Thermostat _ .95 - - 662n HOTWATERCREDITMULTIPLIERS(HWCMI SYSTEM TYPE. NOTE:A HWM MUST BE USED IN CONJUNCTION WITH ALL HWCM. SEE TABLE:6A-9.EF MEANS ENERGY FACTOR.. With - Air Conditioner Heal Pump Heat Recovery Unit HWCM _ .84 _ .78 _ Add -on Dedicated Heat Pump EF _ 2.0-2A9. _ _ 2.5.2.99_ 3.03.49 3.5_ & U (without tank) _ HWCM .44 .35 .29 A 25 Add -on Solar Water Heater EF - 1..0-1.9 2.0-2.9 3.0-3.9 4.014.9 5.0 & U without tank) HWCM .84 .42 .28 .21 .17 A'HWM MUSTBE USED IN CONJUNCTION WITH ALL HWCM. SEE TABLE SA-9.EF MEANS ENERGY FACTOR 6A.91 INEII TRATInM REn11r nnN COMPLIANCE CHECKLIST COMPONENTS SECTION REOUIREMENTS FOR EACH PRACTICE - CHECK .Exterior Windows &Doors 606:1.ABC.1.1 Max: .3'cfm/sq.ft. window areaf_5 cfm/sq.ft. door area. 00 _ Exterior& Adjacent, Walls 606.1.ABC.12.1 Gaul k;.gasket, weatherstrip or seal between: windows/doors & frames, surrounding wall; foundation &wall sole or sill, plate; .joints between exterior wall panels at corners; utility penetrations; between wall panels &top/bottom plates; between walls & floor. EXCEPTION: Frame walls where a continuous infiltration barrier is installed that, extends from, and is sealed to, the foundation to the top plate. Floors 606.1.ABC.12.2 Penetrations/openings>1/8"sealed unlessbacked bytruss orjoint members. EXCEPTION: Frame floors where a continuousinfiltration _barrier isin-stalled thatis sealed to the perimeter, penetrations and seams. -Ceilings 606.1.ABC.1.2.3 Seal: Between walls '&.ceilings; penetrations, of ceiling. plane of top floor; aroundshafts, ch sea, soffits, chimneys, cabinets sealed to continuous air barrier;..gaps,in gyp board .&top plate;. attic access., EXCEPTION: Frameceilings where a continuous infiltration barrier is installed that is sealed .atthe perimeter, at penetrations and seams. Reeessed.Lrghting Fixtures 606.1.ABC:12.4 Type IC rated with no penetrations, sealed; or Type IC'ornon-IC rated, .installed inside a sealed box with 1/2' clearance & 3" from insulation; or Type IC rated with <2.0 cfm from conditioned space, tested. Multi -story, Houses 606.1 ABC:1.2.5' Air banner on perimeter of�floor cavity between floors. Additional Infiltration regts 606.1.ABC.1.3 Exhaust fans vented tooutdoors, dampers; combustion space heaters. comply with NFPA, have combustion air. 6A-22 OTHER PRESCRIPTIVE MEASURES be metorexceeded by all residences.) COMPONENTS SECTION - REQUIREMENTS - CHECK Water Heaters -- 612.1 Comply with efficiency requirements in Table6-12. Switch or clearly marked circuit breaker (electric) or cutoff as.. must be provided.'External or built-in heat trap .required. .Swimming Pools &,Spas 612:1 Spas &'heated pools must�have covers (except solar heated). Non-commercial poolsmust have a -pump timer. Gass a..&:pool heaters must have a minimum thermal efficiency of 78%. Shower Heads 612.1 Water flow must be restricted to no more than 2.5 gallons perminute at 80 PSIG. Air Distribution Systems 610.1 All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, insulated, and installed in accordance with the criteria of Section 610. Ducts in unconditioned attics: R-6 min. insulation. HVAG Controls 607.1 Se aratereadil accessible manual or automatic thermostat for each system. Insulation. 604.1, 602.f Ceilin s-Min: R-19. Common walls -Frame R-11 or GE S R-3.both 'sides. . Common ceilin & Floors R-11._ a � c CASALINO RESIDENCE HVAC LOAD ANALYSIS for CASALINO [Elite Software RNVAtResidential and Light Commercial HVAC Loads Prepared By. R. SMITH Smith Heating and A/C, Inc. 7707 North U.S.91 Suite 10 Vero Beach, Florida 32967 (407) 589-7666 03/04/99 RHVAC-Residential& Light Commercial.HVAC Loads Program F1171*1 Elite Software Development, Inc. Smith Heating & A/C CASALINO RESIDENCE Vero Beach, FL 329675667 03/04W Page 2 Project Summary Company: Smith Heating and A/C, Inc. Client: CASALINO Representative: R. SMITH 'Address: Address: 7707 North U.S. #1 Suite 10 City: City: Vero Beach, Florida 32967 Phone: Phone: (407) 589-7666 Fax: Fax: (407) 589-8212 Comment: Design Data Project Name: CASALINO RESIDENCE Reference City: Fort Pierce, Florida Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 Feet Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum. Dry -Bulb Difference Winter: 40 N/A N/A 72 N/A Summe,r; 95 78 -50% 75 53 Check Figures Total Building Supply CFM: 1124 CFM per square foot: 0.494 Square feet of room area: 2,277 Square feet per ton: 850,492 Building Loads Total heating required with outside air: 30,368 Btuh 30.368 MBH Total sensible gain: 24,738 Btuh 81 % Total latent gain: 5,635 Btuh 19 % Total copling required with outside. air: 30,373 Btuh 2.531 Tons (based -0nsensible t latent) 2.677 Tons (based on 77% sensible capacity) Notes Calculations are based on 7th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary Be sure to selector unit that meets both sensible and latent loads. r RHVAC - Residential,& LightCommercialHVAC.Loads .Program Llr1. *1 Elite Software Development,.lna Smith Heating & A/C i CASALINO RESIDENCE Vero Beach, FL 329675667 03RA199 Page 3 Total Building Summary Loads Component Area Sen. Lat. Sen. Total Description Quart Loss Gain Gain Gain 1C Window Clear Glass Metal Frame 226 8,352 0 6,812 6,812 8C Glass Door Single Clr Glass Metal Frame 48 1,774 0 1,152 1,152 10D Door Wood Solid Core 24 353 0 261 261 14B Wall 8" or 12" Block + R-5 2,034 9,373 0 4,776 4,776 16G Ceiling R-30 Insulation 1,797 1,897 0 2,611 2,611 22A Slab on Grade No.Edge Insulation 140 3,629 0 0 0 Subtotals for structure: 4,269 25,378 0 15,612 15,612 Active People: 14 0 3-1220 4,200 7,420 Inactive People: 0 0 0 0 0 Appliances: 0 0 0 1,200 1,200 Lighting: 0 0 0 Ductwork: 0 1,447 0 2,249 2,249 Infiltration: Winter CFM: 100.7, Summer CFM: 67.1 298 3,543 2,415 1,477 3,892 Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0 Sensible Gain Total: 24,738 Temperature Swing Multiplier: X1.00 Building Load Totals: 30,368 5,635 24,738 30,373 Check Figures Total Building Supply CFM: 1124 Square feet of room area: 2,277 Building Loads CFM per square foot: 0.494 Square.feet per ton: 850.492 Total heating required with outside air: 30,368 Btuh 30.368 MBH Total sensible gain: 24,738 -Btuh 81 % Total latent gain: 5,635 Btuh 19 % Total coolipg.required with outside air: 30,373 Btuh 2.531 Tons{based on sensible +-latent) 2.677 Tons (based on 77% sensible capacity) Notes Calculations are based on 7th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure toselect,a,unit thatmeetsboth sensible and latent -loads. RHVAC - Residential& Light. CommercialHVAC-Loads Program Elite Software -Development, -Inc. Smith Heating & A/C CASALINO RESIDENCE Vero Beach, FL 329675667 03/04/99 Page 4 System #1 Summary Loads Component Area Sen. Lat. Sen. Total Description _ Quan Loss Gain Gain Gain 1C Window Clear Glass Metal Frame 226 8,352 0 6,612 6,812 8C Glass Door SingleClrGlass -Metal Frame 48 1,774 0 1,152 1,152 10D Door Wood Solid Core 24 353 0 261 261 14B Wall.8" or 12" Block + R-5 2,034 9,373 0 4,77E 4,776 16G Ceiling R-30 Insulation 1,797 1,897 0 2,611 2,611 22A Slab on Grade No Edge Insulation 140 3,629 0 0 0 Subtotals for structure: 4,269 25,378 0 15,612 15,612 Active People: 14 0 3,220 4,200 7,420 Inactive People: 0 0 0 0 0 Appliances: 0 0 0 1,200 1,200 Lighting: 0 0 0 Ductwork: 0 1,447 0 2,249 2,249 Infiltration: Winter CFM: 100.7, Summer CFM: 67.1 298 3,543 2,415 1,477 3,892 Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0 Sensible Gain Total: 24,738 Temperature Swing Multiplier: X1.00 System Load Totals: 30,368 5,635 24,738 30,373 Check Figures Supply CFM: 1,124 CFM per square foot: 0.494 Square feet of room area: 2,277 Square feetperion: 850.492 System Loads Total heating required with outside air: 30,368 Btuh 30.368 MBH Total sepsible gain: 24,738 Stuh 81 % Total latent gain: 5,635 Btuh 19 % Total coolingrequired with outside air: -30,373 -Btuh 2.531 Tons (based on sensible + latent) 2.677 Tons (based on 77% sensible capacity) Notes Calculations are based on 7th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary Be sure to -select .a.unitthat meets both sensible and latent loads. RHVAC - Residential & Light CommercialHVAC.LoadsProgram �; '. *1 Elite Software Development, Inc. Smith Heating & A/C C CASALINO RESIDENCE Vero Beach, FL 32967-5667 03KAG9 Page 5 System #1 Zone #1 Summary Loads Component Area Sen. Lat. Sen. Total Description Quan Loss Gain Gain Gain I Window Clear Glass Metal Frame 102 3,770 0 3,669 3,669 14B Wall 8" or 12"-Block +.R-5 887 4,087 0 2,083 2,083 16G Ceiling R-30 Insulation 1,077 1,137 0 1,565 1,565 Subtotals for -structure: 2,066 8,994 0 7,317 7,317 Active People: 1 0 230 300 530 Inactive People: 0 0 0 0 0 Appliances: 0 0 0 0 0 Lighting: 0 0 0 Ductwork: 0 511 0 812 812 Infiltration: Winter CFM: 34.5, Summer CFM: 23.0 102 1,212 828 506 1,334 Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0 Sensible Gain Total: 8,935 Temperature Swing Multiplier. X1.00 Zone Load Totals: 10,717 1,058 8,935 2,993 Check Figures Supply CFM: 406 Square feet of room area: 1,077 Zone Loads Total heating required with outside air: 10,717 Btuh Total sensible gain: 8,935 Btuh Total latent gain: 1,058 Btuh Total cooling required with outside air: 9,993 Btuh CFM per square foot: 0.377 Square feet per ton: 1,252.038 10.717 MBH 89 % 11 % 0.833 Tons (based on sensible + latent) 0.860 Tons (basedon77%sensible.capacity) RHVAC - Residential & Light Commercial HVAC.Loads.Program * I Elite. Software Development, lac. Smith Heating & A/C b2i CASALINO RESIDENCE Vero Beach, FL 329675667 03104M Page 6 System #1 Zone #2 Summary Loads Component Area Sen. Lat. Sen. Total Description Quan Loss Gain Gain Gain 1C Window Clear Glass Metal Frame 124 4,582 0 3,143 3,143 8C Glass Door Single Clr Glass Metal Frame 48 1,774 0 1,152 1,152 10D Door Wood Solid Core 24 353 0 261 261 14B Wall 8" or 12" Block+ R-5 1,147 5,286 0 2,693 2,693 16G Ceiling R-30 Insulation 720 760 0 1,046 1,046 22A Slab on-Grade.No Edge Insulation 140 3,629 0 0 0 Subtotals for structure: 2,203 16,384 0 8,295 8,295 Active People: 13 0 2,990 3,900 6,890 Inactive People: 0 0 0 0 0 Appliances: Lighting: Ductwork: Infiltration: Winter CFM. 66.2, Summer CFM: 44.1 Ventilation: Winter CFM: 0.0. Summer CFM: 0.0 0 0 0 1,200 1,200 0 D 0 0 936 0 1,437 1,437 196 2,331 1,587 971 2,558 0 0 0 0 0 Sensible -Gain Total: 15803 Temperature Swing Multiplier: X1.00 Zone Load Totals: 19,651 4,577 15,803 20,380 Check Figures Supply CFM: 718 Square feet of room area: -1,200 Zone Loads CFM per square foot: 0.599 Square feetperton: 660.402 Total heating required with outside air: 19,651 Btuh 19.651 MBH Total sensible gain: 15,803 Btuh 78 % Total latent gain: 4,577 Btuh 22 % Total cooling -required with outside air: 20,380 -Btuh 1.698 Tons (based on sensible + latent) 1.817 Tons (based on 77% sensible capacity) RHVAC - Residential 8 Light Commercial HVAC Loads Program Smith Heating & A/C Vero Beach, FL 329675667 + =4Q9 -Elite.Software Development, Inc. CASALINO RESIDENCE Page 7 Detailed Room Loads 1. Bedroom 2 Room Length: 15.0 Feet System Number: 1 ' Room Width: 11.6 Feet Zone Number: 1 - Area: 174.0 Square Feet Supply Air: 137 CFM Ceiling Height: 8.0 Feet Required Vent. Air: 0 CFM Volume: 1,392.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 1 % of Supply: 0 % Runout Air: 137 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 6x6 Inches % of Supply: 0 % Runout Air Velocity: 731 Feet/Minute ActualWinterInfiltration Air. 8 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 6 CFM allocated Actual Loss: 0.208 .In.wg/1.00 Ft. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain W -WALL-14B 11.6 X 8 68 D_ 144 4.6 313 2.3 0 160 S -WALL-14B 15 X 8 120 0.144 4.6 553 2.3 0 282 W-GLAT4-1C 1-P 0-0 S-4 0%S 25 1.155 37.0 924 65.0 D 1,625 UP-CEIL-16G DARK 15 X 11.6 174 0.033 1.1 184 1.5 0 253 Subtotals -for structure: 387 1974 0 2320 Infiltration: Winter: 8.4, Summer: 5.6: 25 11.880 297 4.960 203 124 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 114 0.100 0 274 Active People: 230 ]at/per, 300 sen/per: 1 230 300 Inactive people: 150 lat/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 3018 Temperature Swing Multiplier: X1.00 Room Totals: 2,385 433 3,018 RHVAC - Residential & Light Commercial HVAC Loads Program • -Elite Software Development, Inc. Smith Heating 8 A/C b2i CASALINO RESIDENCE Vero Beach, FL 329675667 oa04W Page 8 Detailed Room Loads 2. Bridge Room Length: 12.0 Feet System Number: 1 Room Width: 8.0 Feet Zone Number: 1 Area: 96.0 Square Feet -Supply.Air: 7 CFM Ceiling Height: 8.0 Feet Required Vent. Air: 0 CFM Volume: 768.0 Cubic.Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 1 % of Supply: 0 % Runout Air: 7 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 4x4 Inches % of Supply: 0 % Runout Air Velocity: 67' Feet/Minute Actual Winterinfiltration Air: 0 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 0 CFM allocated Actual Loss: .0.004 .In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain UP-CEIL-16G DARK 12 X 8 96 0.033 1.1 101 1.5 0 139 Subtotals -for structure: 96 101 0 139 Infiltration: Winter: 0.0, Summer: 0.0: 0 0.000 0 0.000 0 0 Ventilation: -Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 5 0.100 0 14 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive,People: 150 ]at/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 153 Temperature Swing Multiplier: X1.00 Room Totals: 106 0 153 RHVAC - Residential & Light Commercial HVAC Loads Program F59 s Elite Software Development, Inc. Smith Heating 8-A/C n LASALINO-RESIDENCE Vero Beach, FL 329675667 03/04099 Pace 9 Room Loads 3. Upper Dining • Room Length: 12.0 Feet System -Number. 1 Room Width: 6.0 Feet Zone Number: 1 Area: 72.0 Square Feet Supply Air: 50 CFM Ceiling Height: 8.0 Feet Required Vent. Air: 0 CFM Volume: 576.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 1 % of Supply: 0 % Runout Air: 50 -CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 4x4 Inches % of Supply: 0 % Runout Air Velocity: 597 Feet/Minute Actual Winter.lnfiltration Air: 8 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 6 CFM allocated Actual Loss: 0.240 In.wg/100 Ft. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss 'HTM Gain Gain W -WAIL-1413 12 X 8 71 0.144 4.6 327 2.3 0 167 W-GLAS-1C 1-P 0-1 S-4 100%S 25 1.155 37.0 924 24.0 0 600 UP-CEIJ_-16G DARK 12 X 6 72 0.033 1.1 76 1.5 0 105 Subtotals for structure: 168 1327 0 872 Infiltration: Winter: 8.4, Summer: 5.6: 25 11.880 297 4.960 203 -124 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork; 0.050 81 0.100 0 100 Active People: 230 ]at/per, 300 sen/per: 0 0 0 Inactive People: 150 lat/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 1096 Temperature Swing Multiplier: X1.00 Room Totals: 1,705 203 1,096 RHVAC - Residential &light CommerciaLNVAC-Loads Program -*Fl Elite Soflware.Development, Ina Smith Heating & A/C Vero Beach, FL 32967-5667 baj oa,04199 CASALINO RESIDENCE Page 10 Detailed Room Loads 4. Bath • Room Length: 15.0 Feet System Number: 1 Room Width: 11.0 Feet Zone Number: 1 Area: 165.0 SquareFeetSupply Air. 39 CFM Ceiling Height: 8.0 Feet Required Vent. Air: 0 CFM Volume: 1,320.0 Cubic Feet Actual Winter Ventilation Air: 0 -CFM Number of Registers: 2 % of Supply: 0 % Runout Air: 19 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 4x4 Inches % of Supply: 0 % Runout Air Velocity: 185* Feet/Minute Actual Winter Infiltration Air: 3 -CFM-alkxated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 2 CFM allocated Actual Loss: 0.026 -ln.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain N -WALL-14B 6 X 8 40 0.144 4.6 184 2.3 0 94 W -WALL-146 11 X 8 88 -0.144 4.6 406 2.3 0 207 N-GLAS-1CI-PO-1 S4100%S 8 1.155 37.0 296 24.0 0 192 UP-CEIL-16G DARK 15 X 11 165 0.033 1.1 174 1.5 0 240 Subtotals for structure: 301 1060 0 733 Infiltration:- Winter: 2.7, Summer: 1.8: 8 11.875 95 5.000 85 40 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 58 0.100 0 77 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 150 [at/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 850 Temperature Swing Multiplier: X1.00 Room Totals: 1,213 65 850 RHVAC - Residential &-Light Commercial.HVAC Loads Program * I Elite. Software. Development, Inc. Smith Heating & A/C Q CASALINO RESIDENCE Vero Beach, FL 329675667 03KA/99 Page 11 DetailedRoomLoads 5. Upper -Great Room • Room Length: 24.0 Feet System Number: 1 ' Room Width: 15.0 Feet Zone Number: 1 Area: 360.0 Square Feet -Supply Air: 84 CFM Ceiling Height: 8.0 Feet Required Vent. Air: 0 CFM Volume: 2,880.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 2 % of Supply: 0 % Runout Air: 42 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 4x4 Inches % of Supply: 0 % Runout Air Velocity: 403* Feet/Minute Actual Winter Infiltration Air: 5 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 4 CFM allocated Actual Loss: 0.113 -In.wg/100-Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S -WALL-14B 15 X 8 120 0.144 4.6 553 2.3 0 282 E -WALK-14B 24 X 8 176 0.144 A.6 811 2.3 0 413 E-GLAS-1C 1-P 0-1 S-4 100%S 16 1.155 37.0 591 24.0 0 384 UP-CEIL 16G DARK 24 X 15 360 -0.033 1.1 380 1.5 -0 523 Subtotals for structure: 672 2335 0 1602 Infiltration: Winter: 5.4, Summer: 3.6: 16 11.875 -190 4.938 130 79 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 126 0.100 0 168 Active People: 230 Iattper, 300 sen/per: 0 0 0 Inactive People: 150 [at/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible -Gain Total: 1849 Temperature Swing Multiplier: X1.00 Room Totals: 2,651 130 1,849 RHVAC - Residential &Light Commercial HVAC Loads Pfogram :@j • FJite Software Development, Inc. Smith Heating & A/C CASALINO RESIDENCE Vero Beach, FL 329675667 03ftk1FJ9 Paae 12 Detailed Room Loads 6. Bedroom 3 Room Length: Room Width: Area: Ceiling Height: Volume: Number of Registers: 15.0 Feet 14.0 Feet 210.0 Square -Feet 8.0 Feet 1,680.0 Cubic Feet System Number: Zone Number: Supply Air: Required Vent. Air: Actual Winter Ventilation Air: % of Supply: Runout Air: 90 CFM Actual Summer Ventilation Air: Runout Duct Size: 6x6 Inches % of Supply: Runout Air -Velocity: 381` Feet/Minute Actual Winter Infiltration Air: Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: Actual Loss: 0.059 In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. 90-CFM 0 CFM 0 CFM 0 % 0 CFM 0 % 9 .CFM allocated 6 CFM allocated Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain N -WALL-146 15 X 8 108 0.144 4.6 498 2.3 0 253 E -WALL-14B 14 X 8 96 0.144 4.6 442 2.3 0 225 N-GLAS-IC 1-P 0-1 S-1 100%S 12 1.155 37.0 444 31.0 0 372 E-GLAS-1C 1-P-0-1 S-1 100%S 16 1.-155 -37.0 591 31.0 0 496 UP-CEIL-16G DARK 15 X 14 210 0.033 1.1 222 1.5 0 305 Subtotals for structure: 442 2197 0 1651 Infiltration: Winter: 9.5, Summer: 6.3: 28 11.893 333 4.964 227 139 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 127 0.100 0 179 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 150 lat/per, 250..sen/per: -0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 1969 Temperature Swing Multiplier: X1.00 Room Totals: 2,657 227 1,969 RHVAC - Residential &Light Commercial HVAC Loads Program { EliteSoftware Development, Inc. Smith Heating & A/C CASALINO RESIDENCE Vero Beach, FL 329675667 03934M Pape 13 Detailed Room Loads 7. Dining/kitchen Room Length: Room Width: Area: Ceiling Height: Volume: 24.0 Feet 15.0 Feet 360.0 Square Feet 9.6 Feet 3,456.0 Cubic Feet System .Number - Zone Number: Supply Air: Required Vent. Air: Actual Winter Ventilation Air., Number of Registers: 2 % of Supply: Runout Air: 149 CFM Actual Summer Ventilation Air: Runout Duct Size: 8x8 Inches % of Supply: Runout Air Velocity: 445* Feet/Minute Actual WinterInfiltrationAir: Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: Actual Loss: 0.055 1n.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. 2 297 CFM 0 CFM 0 CFM 0 % 0 CFM 0 % 21 .CFM allocated 14 CFM allocated Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S -WALL-1413 15 X 9.6 129 0.144 4.6 594 2.3 0 303 W -WALL-14B 24 X 9.6 182 0.144 4.6 839 2.3 0 427 S-GLAS-1C 1-P 0-2 S-4 7%S 15 1.155 37.0 554 35.1 0 527 W-G.DR-8C 1-P 0-2 S-4 100%S 48 1.155 37.0 1,774 24.0 0 1,152 UP-CEIL-16G DARK 24 X 15 360 0.033 1.1 380 1.5 0 523 FLOOR-22A 39 FT 39 0.810 25.9 1.011 0.0 0 0 Subtotals for structure: 773 5152 0 2932 Infiltration: Winter: 21.3, Summer. 14.2: 63 11.889 749 4.952 510 312 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 295 0.100 0 594 Active People: 230 lat/per, 300 sen/per: 5 1,150 1,500 Inactive People: 150 lat/per, 250 sen/per: 0 0 0 Appliances: 0 1,200 Sensible Gain Total: 6538 Temperature Swing Multiplier. X1.00 Room Totals: 6,196 1,660 6,538 RHVAC - ResidentialB.Light Commercial HVAC Loads Program . -* -Elite Software Development, lna Smith Heating & A/C Q CASALINO RESIDENCE yero Beach, FL 329675667 03/D4/99 Page 14 Detailed Room Loads 8. Great Room Room Length: 24.0 Feet System Number: 1 Room Width: 15.0 Feet Zone Number: 2 Area: 360.0 Square Feet Supply Air: 236 CFM Ceiling Height: 9.6 Feet Required Vent. Air: 0 CFM Volume: 3,456.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 2 % of Supply: 0 % Runout Air: 118 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 6x6 Inches % of Supply: 0 % Runout Air Velocity: 503 Feet/Minute Actual Winter Infiltration Air: 23 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 16 CFM allocated Actual boss: 0.101 In.wg/100 Ft. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gam S -WALL-1413 15 X 9.6 144 0.144 4.6 664 2.3 0 338 E -WALL-I4B 24 X 9.6 161 0.144 4.6 742 2.3 0 378 E -DOOR-10D3 X 8 24 0.460 14.7 353 10.9 0 261 E-GLAS-IC 1-P 0-3 S-4 100%S 45 1.155 37.0 1,663 24.0 0 1,080 UP-CEllr 16G DARK 24 X 15 360 0A33 1.1 380 1.5 0 523 FLOOR-22A 39 FT 39 0.810 25.9 1,011 0.0 0 0 Subtotals -for structure: 773 4813 0 2580 Infiltration: Winter: 23.3, Summer: 15.5: 69 11.899 821 4.957 559 342 Ventilation: -Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork: 0.050 282 0.100 0 472 Active People: 230 lat/per, 300 sen/per: 6 1,380 1,800 Inactive,People: 150 lat/per, 250.sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 5194 Temperature Swing Multiplier: X1.00 Room Totals: 5,916 1,939 5,194 RHVAC - Residential.& Light Commercial HVAC Loads Program Smith Heating & A/C Vero Beach, FL 329675667 _ a oaG4/99 Elite. Software Development, Inc. CASALINO RESIDENCE Page 15 Detailed Room Loads 9. Bath Room Length: 15.0 Feet System Number. 1 Room Width: 15.0 Feet Zone Number: 2 Area: 225.0 Square Feet -Supply Air: 66 CFM Ceiling Height: 9.6 Feet Required Vent. Air: 0 CFM Volume: 2,160.0 CubicFeet Actual Winter Ventilation Air: 0 CFM Number of Registers: 3 % of Supply: 0 % Runout Air: 22 CFM Actual Summer Ventilation Air. 0 CFM Runout Duct Size: 4x4 Inches % of Supply: 0 % Runout Air Velocity: 263* Feet/Minute Actual Winter Infiltration Air: 8 CFM allocated Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 5 CFM allocated Actual Loss: 0,050 In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain W -WALL-14B 15 X 9.6 120 0.144 4.6 553 2.3 0 282 N -WALE.-1413 15 X 9.6 144 -0.144 4.6 664 2.3 0 338 W-GLAS-1C 1-P 0-2 S-4 100%S 24 1.155 37.0 887 24.0 0 576 FLOOD-22A 30-FT 30 0.810 25.9 778 0.0 0 0 Subtotals for structure: 318 2882 0 1196 Infiltration: Winter: 8.1, Summer: 5A 24 11.875 285 4:958 '194 119 Ventilation: Winter: 0.0, Summer: 0.0: 0 0 0 Ductwork; 0.050 158 0.100 0 132 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 150 lat/per, 250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible -Gain Total: 1447 Temperature Swing Multiplier: X1.00 Room Totals: 3,325 194 1,447 RHVAC - Residential & Light Commercial HVAC Loads Program • Elite Software Development, Inc. Smith Heatipg& A/C =Q-CASALINO RESIDENCE Vero Beach, FL 329675667 =04199 Page 16 Detailed Room Loads 10. Master Bedroom Room Length: Room Width: Area: Ceiling Height: Volume: Number of Registers: Runout Air: Runout Duct Size: Runout Air Velocity: Design Loss: Actual Loss: 17.0 Feet 15.0 Feet 255.0 SquareFeet 9.6 Feet 2,448.0 Cubic Feet 2 60 CFM 4x4 Inches 572 Feet/Minute 0.100 In.wg/100 Ft. 0.221 In.wg/100 Ft. System Number: Zone Number: SupplyAir: Required Vent. Air: Actual Winter Ventilation Air: % of Supply: Actual Summer Ventilation Air: % of Supply: -Actual Winter Infiltration Air: Actual Summer Infiltration Air: 1 2 119 CFM 0 CFM 0-CFM 0 % 0 jCFM 0 % 14 -CFM-allocated 9 CFM allocated Item Area -U- Htg Sen. Clg Latent Sen. Description -Quantity Value HTM toss HTM Gain Gain E-WALI,-14615 X 9.6 104 0.144 4.6 479 2.3 0 244 N -WALL-14B 17 X 9.6 163 0.144 4.6 751 2.3 0 383 E-GLAS-1C 1-P 0-3 S-4 100%S 40 1.155 37.0 1,478 24.0 0 960 FLOOR-22A 32 FT 32 0.810 25.9 829 0.0 0 0 Subtotals -for structure: 339 3537 0 1387 Infiltration: Winter: 13.5, Summer: 9.0: 40 11.900 476 4.950 324 198 Ventilation: Winter: 0.-0, Summer: 0.0: 0 0 0 Ductwork: 0.050 201 0.100 0 239 Active People: 230 lat/per, 300 sen/per: 2 460 600 Inactive People: 150.Iat/per,-250 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 Sensible Gain Total: 2624 Temperature Swing -Multiplier: X1.00 Room Totals: 4,214 784 2,624 RHVAC - Residential a. Light. Commercial HVAC Loads. Program Smith Heating & A/C Vero Beach, FL 329675667 + oaC4M .Elite Software Development, Inc. CASALINO RESIDENCE Page 17 Room Load Summary Reports System#1 Room Load Summary • Htg Htg Rm Room Area Sens Nom No. Description SF Btuh CFM -Run Clg Duct Sens Size Btuh Clg Clg Zone Clg Air Lat Nom Adj Adj Sys -Btuh CFM -Fact CFM CFM ---Zone 1--- 1 Bedroom 2 174 2,385 31 6x6 3,018 433 137 1.25 171 -137 2 Bridge 96 106 1 4x4 153 0 7 1.00 7 7 3 Upper Dining 72 1,705 22 4x4 1,096 203 50 1.25 62 50 4 Bath 165 1,213 16 4x4 850 65 39 1.00 39 39 • 5 Upper Great 360 2,651 34. 4x4 1,849 130 84 1.00 84 84 Room 6 Bedroom 3 210 2,657 35 6x6 1,969 227 90 1.00 90 90 Zone 1 Subtotal 1077 10,717 139 8,935 1,058 4106 453 406 --Zone 2--- 7 Dining7kitchen 360 6,196 80 Bx8 6,538 1,660 297 1.25 371 297 8 Great Room 360 5,916 77 6x6 5,194 1,939 236 1.00 236 236 9 Bath 225 3,325 43 4x4 1,447 194 66 1.25 82 66 10 Master 255 4,214 55 4x4 2,624 784 119 1.00 119 119 Bedroom Zone 2 Subtotal 1200 19,651 .255 15,803 4,577 798 809 718 System 1 Totals 2277 30,368 394 24,738 5,635 1,124 1,262 1,124 Main Trunk Size: 14x14 in. System-#1 Cooling System Summary Cooling ,Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 2:531 81%/19% 24,738 5,635 30,373 Recommended: 2.677 77%/23% 24,738 7,389 32,127 System #1 Equipment Data Heating System Cooling System STATE OF FLORIDA DEPARTMENT OF HEALTH ONSITE 'SEWAGE DISPOSAL SYSTEM CONSTRUCTION PERMIT ' Authorityt Chapter 381, FS & Chapter 1OD-6, PAC PERMIT DATE PAID _ FEE PAID RECEIPT CONSTRUCTION PERMIT FOR: New System [ ] Existing System [. ] Holding Tank [' ] Temporary/Experimental [4"]. Repair [ j Abandonment ['. ] Other(Specify) - APPLICANT• - AGENT: PROPERTY STREET ADDRESS: LOT: -'' BLOCK';. :SUBDIVISION: 'PROPERTY ID)�'p - _ ['SECTION/TOWNSHIP/RANGE/PARCEL NUMBER] [OR TAX ID NUMBER] ---'- --=_-------==W===� =------------=---- :SYSTEM MUSTBE CONSTRUCTED IN ACCORDANCE WITH SPECIFICATIONS AND STANDARDS OF CHAPTER 1GD-6, FAC. REPAIR PERMITS AND HOLDING TANK PERMITS EXPIRE90 DAYS FROM THE DATE OF ISSUE, ALL. OTHER PERMITS. EXPIRE ONE YEAR FROM THE DATE OF ISSUE. DEPARTMENT OF HEALTH APPROVAL OF SYSTEM DOES NOT GUARANTEE SATISFACTORY PERFORMANCE' FOR ANY SPECIFIC PERIOD OF TIME. ANY CHANGE IN MATERIAL 'FACTS WHICH SERVED AS A BASIS FOR ISSUANCE OF THIS PERMIT REQUIRE. THE APPLICANT TO MODIFY THE PERMIT APPL'ICATION.. SUCH MODIFICATIONS MAY RESULT IN THIS PERMIT BEING MADE NULL AND VOID.. ------------------- SYSTEM DESIGN AND SPECIFICATIONS T ,( - ],[GALLONS/ GPDj' SEPTIC 'TANK/AEROBIC UNIT CAPACITY MULTI=CHAMBERED/IN 'SERIES:(. ) A ( • ] ['GALLONS / GPD), - -' CAPACITY MULTI..-CHAMBERED/IN SERIES;:( ) N ( ] GALLONS GREASE INTERCEPTOR CAPACITY (MAX'IMUM CAPACITY SINGLETANK: 1250 GALLONS] K (. ] GALLONS PER DOSE DOSING TANK CAPACITY DOSE -RATE.[ ] PER 24 HRS' NO. OF PUMPS: [ ] D (, ]: SQUARE FEET PRIMARY DRAINFIELD SYSTEM :R ( ] SQUARE FEET SYSTEM A TYPE, SYSTEM: [ '] STANDARD ( ]:FILLED „(, J MOUND [ ] 'I CONFIGURATION: [ ] TRENCH, -_-:( ] BED ['. ] - - - - LOCATION OF BENCHMARK: ELEVATION OF PROPOSED SYSTEM BOTTOM OF DRAINFIELD TO BE [ FILL REQUIRED: ( ] INCHES r '] [INCHES/FTI' [ABOVE/'BELOW] BENCHMARK/REFERENCE POINT ].(INCHES/FT] [ABOVE/BELOW] BENCHMARK/REFERENCE POINT EXCAVATION REQUIRED; [ ] INCHES, - - SPECIFICATIONS BY: ', ,' ,r TITLE: AT • APPROVED BY: r 'TITLE: CHD , DATE ISSUED.,,,, . EXPIRATION DATE: Page i of 2 _(r.4016, 10196 (Rep)aces HRS-H Form 4D10'(Page. 11 whwh'mey,6a-:used) (Aock.Numbora 044-001-4016-0) Building Department INSTRUCTIONS PERMIT NUMBER: Permit tracking number by County Health Department. APPLICATION FOR: Check type of permit, if "Other" specify type in blank:. APPLICANT: Property, owner's full ,name. TELEPHONE: Telephone number for applicant or agent. AGENT: - - `Property owner's legalry amhoiized representative. MAILING ADDRESS: P.O. box or street mailing address for applicant or agent. LOT, BLOCK,. SUBDIVISION. or PROPERTY ID#":. 27 character ID number for property.. (Health. Department may require property. appraiser ID# or section/township/range/parcel number.) SYSTEM DESIGN AND SPECIFICATIONS:. TANK: Minimum specifications from Chapter IOD-6, FAC. DRAINFIELD:. Minimum specifications from Chapter'IOD•6, FAC. OTHER: Other' specifications, such as operating permit requirements; low -volume flush toilets, variance provisos.: SPECIFICATIONS. BY: Nameofindividual providing specifications. If designed by a -registered engineer must be scaled, APPROVED BY: County Health Department personnel reviewing and approving. permit.. DATE ISSUED'. Date :permit is issued by County Health Department.. EXPIRATION. DATE: One year from date issued if the system has not been installed. Permits for system repairs become void 90 days from the dateissued. C KSM KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC. P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (561) 589-0712 MELBOURNE (407) 768-8488 SOIL COMPACTION REPORT FAX (561) 589-6469 ASTM D 1557 DATE TESTED June 18, 1999 PERMIT # 9904O2'82 CONTRACTOR Lou Casalino JOB LOCATION: 901 Casalino Road Ft. Pierce, Florida JOB # : 99630-2D ITEM TESTED : Compacted Stem -wall Fill For Slab-On-Grade ------------------------------------------------------------ TEST LOCATION DEPTH PEN DRY MAX. DRY PERCENT OF SAMPLE READ DENSITY PROCTOR VALUE COMPACTION -r - --------------------------------------------------------------------- 1 N.W. 0" - 12" 40 113.2 116.0 97.6 2 S.W. " 38 112.8 97.2 3 N.E. 35 111.0 95.7 4 S.E. 35 110.5 95.3 Soil-' Descript'ion c Gray Clayed Sand In Place Moisture: 10.5 Percent Optimum Moisture: 11.5 Percent Max. Dry Density: 116.0 P.C.F. 117.0 W E 116.0 I G 115.0 H T 114.0 P. C. F. @ Test Locations The D Density Readings Indicate R the Degree of Compaction Y �s 113.0 112.0 111.0 110.0 9 10 11 12 13 14 15 ioisture - % Of Dry Weight JOB Gi i14L.►l�fo ' ICQQ JOB-l'llrvo RAY D. REINHARD, P.E. Consulting Engineer 735 35th Avenue S.W. Home (407) 778-9329 Vero Beach, FL 32968 Office (407) 567-7461 rf F SHEET NO. OF CALCULATED BY` " DATE CHECKED BY DATE FMDUCI D.Y l A 8 C 0 5 F RAY D. REINHARD, P.E. Consulting Engineer 735 35th Avenue S.W. Home (407) 778-9329 Vero Beach, FL 32968 Office (407) 567-7461 JOB CASAu..10 RaWc.AA w'n"ists `soya o SHEET NO � OF I CAUCULATED" r�'D l� DATE b4I9 I/y' CHECKED PRODUCT 09 1 A 3 C 0 E F Gay Yo.7,F2, ST. LUCIE COUNTY DEPARTMENT OF COMMUNITY DEVELOPMENT 2300 VIRGINIA AVENUE FT. PIERCE, FL 34982-5652 561-462-1553 DESIGN CERTIFICATION FOR WIND LOAD COMPLIANCE This Certification is to be completed by the project design architect or engineer. This Certification must be submitted with all applications for building permit involving the construction of new residence (single or multi -fatuity), residential addition, any accessory structure requiring a building permit, and any nonresidential structure. This Certification shall not apply to interior renovations (provided that no structural walls, columns or other similar component is being effected) and certain other minor building permits. For further assistance, please contact the Building Inspection Office at 462-1553 or 462-2172. CERTIFICATION STATEMENT: CERTIFY THAT, TO THE BEST OF MY KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS HAVE BEEN DESIGNED TO COMPLY WITH THE APPLICABLE STRUCTURAL PORTION OF THE BUILDING CODES CURRENTLY ADOPTED AND ENFORCED BY ST. LUCIE COUNTY. I ALSO CERTIFY THAT STRUCTURAL ELEMENTS DEPICTED ON THESE PLANS PROVIDE ADEQUATE RESISTANCE TO THE WIND LOADS AND FORCES SPECIFIED BY CURRENT CODE PROVISIONS. DESIGN PARAMETERS AND ASSUMPTIONS USED- (Dlease check or complete the aoorourite boxl 1. STANDARD BUILDING CODE 1997 EDITION X 2. BUILDING DESIGN IS (CHECK ONE) ENCLOSED 3. BUILDING HEIGHT: 32. FT 4 ASCE 7-95 _ OTHER (SPECIFY) PARTIALLY ENCLOSED _ OPEN BUILDING WIND SPEED USED IN BUILDING DESIGN: I I O MPH S. WIND EXPOSURE CLASSIFICATION (REFER TO EXPOSURE TABLES IN BUILDING CODE IDENTIFIED IN LINE 01): SU`:(�1:C. Fjq' MIL•�'I��S. 6. AVERAGE WIND VELOCITY PRESSURE ON EXTERIOR FACES OF STRUCTURE: Z PSF _7 7. PEAK WIND VELOCITY PRESSURE ON EXTERIOR FACES OF STRUCTURE: 3 PSF 8. IMPORTANCE/USE FACTOR (OBTAIN FROM BUILDING CODE): 1. C) S. LOADS: FLOOR LIo PSF ROOF/DEAD: 20 PSF ROOF/LIVE: 16 PSF 10. WERE SHEAR WALLS. CONSIDERED FOR STRUCTURE (CHECK ONE) YES, NO explaination) _ If NO, why? (attach 11. IS A CONTINUOUS LOAD PATH PROVIDED (CHECKONE) YES K NO _ If NO, why? (attach explaination) 12. ARE COMPONENT AND CLADDING DETAILS PROVIDED (CHECK ONE) YES ---K�. NO _ If NO, why? (attach 4, explaination) 13. MINIMUM SOIL BEARING PRESSURE: ZScsJ PSF AS WITNESSED BY IS TRUE AND CO RI DESIGN FIRM: tEBY CERTIFY THAT THE INFORMATION INCLUDED WITH THIS CERTIFICATION BEST OF MY KNOWLEDGE AND BELIEF. [SEAL HERE] SLCCDV FORM NO: , CERTIFICATION NO: E. DATE: 47 oy I IS 'e `^�.`• GENERAL NOTES RAYD. REINHARD, P.E. 1. The design and construction of the structure and/or structural components depicted on this plan are fully • under the jurisdiction of the 1997 Standard Building Code. V 2. All specified bolts (anchor bolts or other) shall be structural quality - ASTM 307 or better. „ 3. Prior to construction, engineer shall review approved truss drawings with uplift loads for compatibility with 'v these details and specifications. 4. Trusses depicted are schematic only. Refer to manufactures recommendations for proper design, drawings, lumber grade, bracing, installation, etc -Truss plan is to be certified by a professional engineer with a note stating that the trusses are designed for the specified wind loading. Individually certified truss shop drawings are to be provided lisfing the uplift reactions for each truss. 5. All specified pre -fabricated fastening devices shall be installed in accordance with the manufacturers recommendations, use nailing for maximum load development 6. DESIGN LOADS Loads used for the design of structural components: Roof Loads Dead Loads 2C.) PSF Live Load 16 PSF Floor Loads Dead Load 15 PSF Live Load 40 PSF Conc. Structures Dead Load 150 PCF Wind Load LLO MPH (gPSF Basic, with applicable shape factors) Allow. Soil Pressure 2500 PSF (98%compaction density required) 7. CONCRETE - Cast in place concrete shall achieve a 28 day compressive strength as follows: Beams/Girders 3500 PSI - 5" Slump Foundation 3000 PSI - 3" to 5" Slump Grout (cells) 2000 PSI -8" to 11" Slump - Cast in place concrete shall be designed, mixed, placed and cured in accordance with ACI standards. 8. REINFORCEMENT - Concrete reinforcing bars shall be deformed new billet steel conforming to ASTM A-615, Grade 60. - All splices shall be lap splices. Splices shall be a minimum of 40 bar diameters, using larger bar diameters when splicing different size bars. - Reinforcement may be bent in shop or field provided that Diameter of bend shall be greater than 6 bar diameters. Reinforcement partially embedded in concrete shall not be bent - Secure reinforcement from displacement during concrete placement utilizing chairs and bolsters. - Welded wire mesh shall confonn to ASTM A-185. Provide chairs and bolsters to insure that the mesh is embedded 1" from top of slab. - Minimum concrete cover shall be: Footings 3" Beams, Slabs, & Walls 1 - %" up to No. 5 Bar 2" No. 6 Bar and Greater Grouted Masonry Walls 2" - Standard 90° Hook is reinforcing bar terminating with a 90° bend and an extension from bend at least 12 bar diameters. This shall be used at all vertical reinforcement terminations into fie beams and foundations. 9. GROUTED MASONRY CONSTRUCTION All concrete masonry units shall comply with ASTM C-90 with type M or S mortar complying to ASTM A-270. Min. net area compressive strength or CMU units shall be 1900 PSI. All grout used in CMU cells shall have a maximum course aggregate of 3/8", shall be placed with a slump of 8" to 11", and shall have a min. compressive strength of 2000 PSI at 28 days, and shall be in accordance with ASTM C476. All exterior CMU walls shall be grouted and reinforced with 1 reinforcing bar with bar size and spacing as shown on typical section or plan. Provide Y" clear distance between any inside cell wall and reinforcement bar. Ensure that cells that are to be grouted line up properly and have a min. clear area of 10 sq. in. and a min. 1 Gear distance of 3". Reinforcing bar lap splices shall be a minimum of 48 bar diameters. Provide cleanout openings at all filled cell locations at bottom course. Spaces to be grouted shall be free of mortar droppings, debris, loose aggregates, or other deleterious materials. Provide 9 Ga. ladder type horizontal joint reinforcing at 16" O.C. in all walls for structures located in a 110 M.P.H. or greater wind load zone. 10. GENERAL - Metal hardware All metal hardware exposed directly to the weather shall be hot dipped galvanized coated with a min. ' of 1.8 oz per sq. R of steel meeting the requirements of ASTM A-90 triple spot test All metal accessories for use in exterior wall construction but not directly exposed to weather shall be galvanized in accordance with ASTM A-153, class B-2. Sizes given for nails are common wire nails. 11. WOOD FRAMING - All load bearing studs (intedor/exterior) shall be a minimum of Group 2 - Grade 2 or better. Studs shall be spaced at a maximum of 16" O.C. with a double top plate and a single pressure treated bottom plate. Studs supporting girders shall be a minimum of a (3) stud column. - Walls higher than 8'-2' require (1) row of bridging at mid -span - 10' or taller walls require (2) rows at 1/3 and 2/3 span points. - All exterior wall and roof sheeting shall be a minimum of Group II plywood with the thickness and nailing requirements per typical section notes.. Pneumatic nailing devices shall be calibrated to avoid counter sinking nails into exterior wall and roof sheefing. Where fasteners are not specified - Fasteners shall be provided in accordance with the applicable tables in the current building code. Header beams are to be provided in accordance with the applicable tables in the current building code. Two studs and hold-down anchor are required at all exterior wall openings and endings. Hold-down to be specified per Floor plan anchor layout. Anchor bolts that will be drilled into concrete must be secured with SIMPSON EPDXY TIE ADHESIVE, expansion anchors will not be acceptable. 12. WINDOW & DOOR COMPONENTS - Window and door certifications are to be fumished by the contractor. All components are to be installed in accordance with the manufacturers fastening requirements as shown on the approved product certifications. Custom fabdcated butt joint (mitered) glazing is to be certified by an engineer registered in the state of Florida.. - Garage doors are to be installed on a minimum of a 2x6 wood buck with fasteners as shown on the garage door buck detail drawing. Where 3/4' P.T. buck strips are used for window installations, the bucks must be fastened with a 2' T. NAIL @ 8' O.C. (min.). Where 2x P.T. bucks are used for window or door installations, the bucks must be fastened with a 1/4' x 3' TAPCON @ 12' O.C. staggered (min.). 13. RECOMMENDATIONS The engineer assumes no responsibility for structural damage due to fallure of windows or doors or glass breakage. It Is recommended that a storm panel system or Impact resistant glazing system he installed to reduce the chance of major damage due to flying debris. The engineer assumes no responsibility for settling cracks which may develop In a monolithic concrete slab system. The use of a FIBERMESH type concrete additive will greatly reduce the risk of slab cracks due to settlement and temperature changes. The use of diagonal steel at Interior comers of concrete slabs is recommended but not required. ST. LUCIE COUNTY CHECKLIST SUMMARY L*99040282*PLAN.BL BUILDING DIVISION.CHHCKLIST STATUS DATE OR ID DESCRIPTION % COMMENTS NO 05/03/99 BLD16 3. Building Department Review Complete 5/04/99 COMMENT 1PROVIDE A FIRE SPRINKLER SYSTEM THROUGHT THE ENTIRE BUILDING. . .ALL BOLT SPECS / EMBEDMENT. .PROVIDE CONTINUOUS MECH. VENTILATION FOR GARAGE. 0 4.PROVIDE A LANDING ON BOTH SIDES OF ALL DOORS. .PROVIDE A STARRING SCHEDULE. NAILING SPECS. r ju,�a -&q QVI 1 S T. L U C I E C O U N T Y 2300 Virginia Avenue Ft. Pierce, Florida 34982 Growth Management Division PAYMENT R E C E I P T TRANSACTION NUMBER: 01129015 TRANSACTION DATE: 26 JUL 2000 PERMIT NUMBER: 99040282 PERMIT TYPE: BUILDING RESIDENTIAL PERMIT JOB DESC: * NEW SINGLE FAMILY RESIDENTIAL - MASTER 3/2 ACCESSORY TO AGRI-BUSINESS JOB ADDR: 901 CASALINO RD (14092) PARCEL NUMBER: 2203-321-0001-000/2 FCC DESC: *SINGLE FAMILY DETACHED AND ATTACHED APPLICANT: LOU CASALINO F E E S C O L L E C T E D FEE CODE DESCRIPTION AMOUNT ------------- ----------------------- --------------- REIN REINSPECTION FEE 25.00 AMOUNT PAID: $25.00 FEE WAIVED: CHECK NBR: PAID BY: MARC CASALINO MEMO : MLE J(S (10 f REQUEST FOR 30 DAY TEMPORARY- POWER RELEASE DATE: St. Lucie County Comm. Devel. Dept. i2, /O( Code Compliance Division �-I 2300 Virginia Avenue Fort Pierce, FL 34982-5652 PERMIT NUMBER: Ph. (561) 462- 2165 Fax (561) 462-1735 �C(o4oz.�z IBC �f�f1MFP-B PROPERTY ADDRESS: MAR 2 2 �t b 1 Cc�sG\:,.o R� _ _ `1�.er�� st. Lucie counry�i- FW0 rlol THE UNDERSIGNED HEREBY REQUEST RELEASE OF ELECTRICAL POWER TO THE ABOVE DESCRIBED PROPERTY, FOR A PERIOD NOT TO EXCEED THIRTY (30) DAYS, FOR THE PURPOSE OF TESTING SYSTEMS AND EQUIPMENT IN PREPARA- TION FOR FINAL INSPECTION. IN CONSIDERATION OF APPROVAL OF THIS REQUEST WE HEREBY ACKNOWLEDGE AND AGREE AS FOLLOWS: 1. This temporary power release is requested for the above stated purpose only, and there will be no occupancy of any type, other than that permitted by construction during this time period. 2. As witness by our signatures, we hereby agree to abide by all terms and conditions of this agreement, including Building Division Policy, which is incorporated herein by reference. 3. All conditions and requirements listed in the attached document entitled "Requirements for 30 Day Power for Testing" have been fulfilled and the premises is ready for compliance inspection. We hereby release and agree to hold harmless, St. Lucie County, and their employees from all liabilities and claims of any type or nature which may arise now or in the future out of this transaction, including any damages which may be ,incurred due to the disconnection of electrical power in the event of violation of this agreement. dv 1L ,onnrnl r.nnfracfnr• -llinnohnra- /() Z) DAVID NL JONES Professional Surveyor & Mapper 2M5 14T1-I AVENUE PO BOX 650674 VERO BEACH, FLORIDA PHONE (561)567-9875 FAX (561)567-9172 REPORT OF BOUNDARY SURVEY PROJECT NUMBER: 97-105 DATE OF SURVEY: 4-09-97 *MAP OF BOUNDARY SURVEY SEE MAP OF BOUNDARY SURVEY AS DESCRIBED BELOW. ('THIS MAP AND REPORT ARE. NOT VALID WITHOUT 'ITIE SIGNAI'IJRE AND ORIGINAL RAISED SEAL OF THE FLORIDA IICENSED SURVEYOR AND MAPPER NAMED BELOW WHICH SIGNATURE AND SEAL MAY 13E FOUND AT THE END OF THIS REPORT. THE MAP AND REPORT ARE NOT FULL AND COMPLEIT WITHOUT ONE ANO-ITIER) iLEGAL DESCRIPTION THE WEST ONE HALF OF THE SOUTHWEST ONE QUARTER AND TILE SOUTH ONE HALF OF 71-IE EAST ONE HALF OF THE SOU'1TIWES'T ONE QUARTER OF SECTION 3, TOWNSHIP 35 SOUTI-E, RANGE 38 EAST, ST. LUCIE COUNTY, FLORIDA. SUBJECT TO RIGHTS OF WAY, EASEMENTS AND OTHER RESTRICTIONS OF RECORD. *ACCURACY THE EXPECTED USE OF 'ITIE LAND IS ACREAGE. 'ITIE MINIMUM RELATIVE DISTANCE ACCURACY FOR THIS TYPE OF BOUNDARY SURVEY IS I FOOT IN 5,000 I''EE'T WHICH WAS EXCEEDED IN THE CASE; OF TIIIS SURVEY. •DATASOU.RCES THE DESCRIPTION WAS PROVIDED BY THE CLIENT. NO SEARCH OF THE PUBLIC RECORDS WAS MADE BY 1T-IIS OFFICE TO LOCATE 'ITIE EXISTENCE OF EASEMENT'S OR OTHER RESTRICTIONS NOT PROVIDED BY THE CLIENT OR HIS REPRESENTATIVE, *MEASUREMENT MFn-IODS ALL EQUIPMENT' USED IN PERFORMING'ITIE -LD WORK ASSOCIATED WITH THIS SURVEY WAS'IESTFD AND CALIBRATED. A1.L WORK WAS PERFORMED WITH AN EIIiC'IRONIC TOTAL STATION READING DIRECTLY TO A MINIMUM OF 6 SECONDS PER ANGLE Wail A DISTANCE ACCURACY OF I PART IN 50,000. ALL DATA WAS RIiCORDED page 1 of2 a 'e1 a USING A FIELD DATA COLLECTOR AND CONVENTIONAL FIELD N01TS. THE BOUNDARY WAS PERFORMED BY CREATING A CLOSED GEOMETRIC FIGURE AND ANY SIDE SHOTS WERE DONE USING A REDUNDANCY OF MEASUREMENTS. *LIMITATIONS SURVEYOR WAS NOT PROVIDED TITE INFORMATION FOR THIS PARCEL. RIGHT OF WAY WIDTHS WERE TAKEN FROM TAX MAPS AND OTHER SOURCES PROVIDED BY ST. LUCIE COUNTY. *BOUNDARY INCONSISTENCIES NONE. *APPARENT PHYSICAL USE VACANTLAND. *EASEMENTS NONE. *PREPARED A'T TIIE REQUEST OF LOU CASALINO *CERTIFIED TO LOU CASALINO St. Lucie County Health Unit Environmental Health Site Plan Approved For Construction Supersedes All Previous Site Plans For OSDS# Reviewer 'T. / *SURVEYOR AND MAPPER IN RESPONSIBLE CHARGE DAVID M. JONES, FLORIDA LICENSE NUMBER PLS 3909 add improvements & prop sadd et;a 6d /97 rev prop lake loc: 4A8 /9 add proposed lake:4/17M 97-105: 4/09/97 rep of bdry survey page 2 of