HomeMy WebLinkAboutGENERATOR PAPPERSGENERAC® I INDUSTRIAL
POWER
SG035
Standby Power Rating
35 kW 44 WA 60 Hz
Prime Power Rating*
32 kW 39 kVA 60 Hz
Industrial Spark -ignited Generator Set
SCANNED EPA Certified Stationary Emergency
BY
St. Lucie County
'EPA Certified Prime ratings are not available in the U.S. or its Territories
Codes and Standards
Generac products are designed to the following standards:
c®us UL2200, UL508, UL142, UL498
tH NFPA70, 99,110, 37
racwar
nec NEC700, 701, 702, 708
IS09001, 8528, 3046, 7637, Pluses #2b, 4
jl l NEMA ICs10, MG1, 250, ICS6, AB1
ANSI C62.41
Amortean World sfandad, hutlfaro
} , IBC 2009, CBC 2010. IBC 2012, ASCE 7-05,
w osl /pd ASCE 7-10, IMES AC-156 (2012)
Image used for iflwtrabon puryases arty
Powering Ahead
For over.50 years, Generac has led the industry with
innovative design and superior manufacturing.
Generac ensures superior quality by designing and
manufacturing most of its generator components,
including alternators, enclosures and base tanks,
control systems and communications software.
of options,
ing us to
cally every.
Generac searched globally to ensure the most reliable
engines power our generators. We choose only engines
that have already been proven in heavy-duty industrial
application under adverse conditions.
Generac is committed to ensuring our customers'
service support continues after their generator
purchase.
GENERAC' I INDUSTRIAL
--��- POWER
SGO35
60 and FeOke"s:
ENGINE SYSTEM
General
• Oil Drain Extension
• Air Cleaner
• Fan Guard
• Stainless Steel flexible exhaust connection
• Critical Exhaust Silencer (enclosed only)
• Factory Filled oil
• Radiator duct adapter (open set only)
Fuel System
• Primary and Secondary Fuel Shutoff
• Flexible Fuel Line - NPT Connection
Cooling System
• Closed Coolant Recovery System
• UV/Ozone resistant hoses
• Factory -installed Radiator
• Radiator drain extension
• 50/50 Ethylene glycol antifreeze
Engine Electrical System
• Battery charging alternator
• Battery Cables
• Battery Tray
• Solenoid activated starter motor
• Rubber -boated engine electrical connections
CONTROL SYSTEM
ALTERNATOR SYSTEM
• UL2200 GENprotect'"
• Class H insulation material
• 2/3 Pitch
• Skewed Stator
• Brushless Excitation
• Sealed Bearings
• Amortisseur winding
• Full load capacity alternator
GENERATOR SET
• Internal Genset.Vibration Isolation
• Separation of circuits - high/lowvoltage
• Separation of circuits - multiple breakers
• Wrapped Exhaust Piping
• Standard Factory Testing
• 2 Year Limited Warranty (Standby rated Units)
• 1 Year Warranty (Prime rated units)
• Silencer mounted in the discharge hood
(enclosed only)
ENCLOSURE (if selected)
• Rust -proof fasteners with nylon washers to
protect finish
• High performance sound -absorbing material
• Gasketed doors
• Stamped air-intake louvers
• Air discharge hoods for radiator -upward
pointing
• Stainless steel lift off door hinges
• Stainless steel lockable handles
• Rhino Coat'" -Textured polyester powder coat
• Real/Reactive/Apparent Power
• Single point ground
• All Phase AC Voltage
• 15 channel data logging
• All Phase Currents
• 0.2 msec high speed data logging
_
• oil Pressure
• Alarm information automatically comes up
• Coolant Temperature
on the display
• Coolant Level
Alarms
• Engine Speed
• Oil Pressure (Pre -programmable Low
• BatleryVoltage _
Pressure Shutdown)
Control Panel
• Frequency
• Coolant Temperature (Pre-programmed High
• Digital H Control Panel - Dual 420 Display
• Date/rime Fault History (Event Log)
Temp Shutdown)
• Programmable Crank Limiter
• Isochronous Governor Control
• Coolant Level (Pre-programmed Low Level
• 7-Day Programmable Exerciser
• Waterproof/sealed Connectors
Shutdown)
• Special Applications Programmable PLC
• Audible Alarms and Shutdowns
• Low Fuel Pressure Alarm
• RS-232/485
• Not in Auto (Flashing Light)
• Engine Speed (Pre-programmed Over speed
• All -Phase Sensing DVR
• Auto/Off/Manual Switch
Shutdown)
• E-Stop (Red Mushroom -Type)
• Battery Voltage Warning
• Full System Status
• NFPA110 Level I and II (Programmable)
• Alarms & warnings time and date stamped
• Utility Monitoring
• Customizable Alarms, Warnings, and Events
• Alarms & warnings for transient and steady
• Low Fuel Pressure Indication
• Modbus protocol
stale conditions
• 2-Wire Start Compatible
• Predictive Maintenance algorithm
• Snap shots of key operation parameters
• Power Output (kW)
• Sealed Boards
during alarms & warnings
• Power Factor
• Password parameter adjustment protection
• Alarms and warnings spelled out (no alarm
• kW Hours, Total & Last Run
codes)
GENERAC' I INDUSTRIAL
o
-�..m� POWER
SG035
�C?i9g le Qpt =
ENGINE SYSTEM
General
O Engine Block Heater
O Oil Heater
O Air Filter Restriction Indicator
O Stone Guard (Open Set Only)
O Critical Exhaust Silencer (Open Set Only /
Standard on Ultra Low Emissions Option)
Engine Electrical System
O 10A UL battery charger
O 2.5A UL battery charger
O Battery Warmer
ALTERNATOR SYSTEM
O Alternator Upsizing
O Anti -Condensation Heater
O Tropical coating
O Permanent Magnet Excitation
CONTROL SYSTEM
GENERATOR SET
O
Gen -Link Communications Software
(English Only)
O
Extended Factory Testing (3 Phase Only)
O
IBC Seismic Certification
O
8 Position Load Center
O
2 Year Extended Warranty
O
5 Year Warranty
O
5 Year Extended Warranty
CIRCUIT BREAKER OPTIONS
O Main Line Circuit Breaker
O 2nd Main Line Circuit Breaker
O Shunt Trip and Auxiliary Contact
O Electronic Trip Breakers
ENCLOSURE
O Standard Enclosure
O Level Sound Attenuation
O Level 2 Sound Attenuation
O Steel Enclosure
O Aluminum Enclosure
O 150 MPH Wind Kit
O 12 VDC Enclosure Lighting Kit
O 120 VAC Enclosure Lighting Kit
O AC/DC Enclosure Lighting Kit
O Door Alarm Switch
O 21-Light Remote Annunciator O Remote E-Slop (Break Glass -Type, Surface O Remote Communication - Modem
O Remote Relay Panel (8 or 16) Mount) O Remote Communication - Ethernet
O Oil Temperature Sender with Indication O Remote E-Stop (Red Mushroom Type, O 1 OA Run Relay
Alarm Surface Mount) O Ground fault indication and protection
O Remote E-Stop (Red Mushroom Type, functions
Flush Mount)
ENGINE SYSTEM GENERATOR SET CONTROL SYSTEM
O Coolant heater ball valves
O Fluid containment pans
O Special Testing
O Battery Box
ALTERNATOR SYSTEM ENCLOSURE
O 3rd Breaker Systems
O Motorized Dampers
O Enclosure Ambient Heaters
O Spare inputs (x4) / outputs (x4) - H Panel
Only
O Battery Disconnect Switch
Rating Definitions .-�
Standby —Applicable for a varying emergency load for the duration of a utility power outage with no overload capability.
Prime —Applicable for supplying power to a varying load in lieu of utility for an unlimited amount of running time. A 10%overload capacity is available for 1 out of
every 12 hours. The Prime Power option is only available on International applications.
Power ratings in accordance with ISO 8528-1, Second Edition dated 2005-06-01, definitions for Prime Power (PRP) and Emergency Standby Power (ESP).
GENERAC' I INDUSTRIAL
POWER
SG035 application and engineering data
ENGINE SPECIFICATIONS
General
Make
Gylinder� '-
Type
Displacehent -1 Cu n)
Bore - mm (in)
( Stroke -ruin (In)'
Compression Ratio
Intake Air Methodm_
Number of Main Bearings
Connecting Ro_d_s_
Cylinder Head
Cylinder Liners
Ignition
Rstoms,
Crankshaft
LiflerType
Intake Valve Material
Exhaust Valve Material
Hardened Valve Seats
Generac
8i
V
5.4 (32953)
90.17 (3.55)
105.92. (4.17)
9:1
Naturally Aspirated ;
4
Forged
Aluminum
No
Single Fire
Aluminum Alloy
Nodular Iron
Hydraulic
Steel Alloy
- HardenedSteel
Yes
Engine Governing
Governor Electronic
Fnquency)ieguladon(SteadyState) +1-0.25%
ALTERNATOR SPECIFICATIONS
Standard Model
UPoles
Field Type
Insulafion:Class Rotor
Insulation Class - Stator
Total Harmonic Distortion .,
Telephone Interference Factor (TIF)
Standard! Excitation
Bearings
Coupling;:..
Prototype Short Circuit Test
390
4',
Revolving
H,
H
<5%
<50
Bfushless
Sealed Ball
Flexibile Disc
Yes
Lubrication System
Oil Pump Type Gear
Oil Filter Type Fult-(lowspin-oncarrwge
Crankcase Capacity- L (qts) 5.7 (6)
Cooling System
Cooling System Type
Pressurized Closed Recovery
Water PumpFloyi-gpm(I'prn) '`
38044)
Fan Type
Pusher
fanSpewrpm)
;2143,4
Fan Diameter mm (in)
508 (20)
,Coolant Heater Wattage
Coolant Heater Standard Voltage
120V
Fuel System
Fuel Type
Carburetor
Secondary Fuel Regulator
Fuel Shut Off Solenoid
Operating Fuel Pressure
Enaine Electrical System
Battery Size
Ground Polarity
Natural Gas, Propane Vapor
Dovm Draft
Standard
Shandard� _
.:..7° - It" H20
12 VDC
Negative
Voltage Regulator Type Full Digital
Number of Sensed Phases All,
Regulation Accuracy (Steady State) +/-0.25%
GENERAC I INDUSTRIAL
memlIiiiiiiiiiiiii POWER
SG035 operating data
POWER RATINGS
Single -Phase 120/240 VAC @1.Opl
M(ee-Phase120/208VAC'@0:8pt -
Three -Phase 120/240 VAC @O.8pf
¢¢ hree PPhase 2771480 VAC @a Bpi:
Three -Phase 346/600 VAC @0.8pt
STARTING CAPABILNTES (sKVA)
Natural Gas Propane Vapor
35 kW
Amps:
146
35 kW
Amps:
146
35:MW
Amps:
`1Z1 _
35 kW
Amps:
'12t
35 kW
Amps:
1"
35 kW
Amps:
105
35 "kW
_,_ Amps..
53..
._ 35kW ";
Amps:
53
35 kW
Amps:
42
35 kW
Amps:
42
sl vs. Voltage Dip
480 VAC
208/240 VAC
Alternator kW
' 10%
15,%
20%
25% `':
30%
- 35%1
10%
15% '
20%
,r25%'
30%
35%
Standard
35
24
: 35
48
60 :.
72
84
18
27
36
45
54
63 '1
Upsiie1
40
27
41.
54
68 :L.
81
95„
20
3t
41
:; 51 `
61
,, 71
Upsize2
50
34
.- 52 -:
69
`86
103
120
26
39
52
;. 65 6
77
90 ;
UPsize3
60
42
63:
83
704 `:..
125
146'
32
47
62
t10
FUEL CONSUMPTION RATES'
Natural Gas -ION (m3/hr)
Percent Load Standby
25%
239 (6.8)
50%
409(11%) -'
75%
553 (15.7)
UK
- 68.2(t93) :.
`Fuel supply installation must accommodate fuel consumption rates at 100% load.
COOLING
Propane Vapor -X3/hr (m3/hr)
Percent Load Standby
25%
69.8(2.0)
"50%
1191(3.d)
75%
161.E
1100%
219.8
Standby
Air Flow (inlet air combustion and radiator)
fP/min (m3/min)
2460 (69.7)
Coolant Flow per Minute.
gpm Rpm)
38(144)
Coolant System Capacity
gal (L)
3(11.36)
Heaf Rejection to Gdoladt '
` BTU/hr
444,000 '
Max Operating Air Temp on Radiator
OF (OC)
122 (50)
Max Operating Ambient Temperature(betmederate)
OF(OC)
110(6.3)
Maximum Radiator Backpressure
in H 0
0.5
COMBUSTION AIR REQUIREMENTS
Standby
Flow at Rated Power char (m3/min).r 87(2.5)
ENGINE EXHAUST
Standby
Rated Engine Speed
rpm
1800
HorsepoweratRatedkW"
hp
.. 54
Piston Speed
f /mm (in/min)
1251 (381)
BMEP _
Psi:
72
- Niel to'EMMCns Data Sheet' for mt taw bHP for EPA and SCAdMO permitanp purposes
Standby
Exhaust Flow (Rated Output)
rim (m3/min)
260 (7.4)
Maximum Recommended Back Pressure
InHg
- _ 1.5
Exhaust Temp (Rated Output)
T (OC)
900 (482)
Fxhausi Outfbt Sim (Open Set)
in
25^'1,D, Flex (NO muffler)::
Deacon - Operational characters ics consider maxnnum ambient candi8ans. Derate factors may apply under atypical site conditions. Please consult a Generac Power Systems Industrial Dealer for
additional details. All performance ratings in accordance with IS03046, BS5514, IS08528 and DIN5271 standards.
GENERAC' I INDUSTRIAL
_�r•�I! POWER
SG035 dimensions and weights
1—L-I
OPEN SET (Includes Exhaust Flex)
L x W x H in (mm) 76 (1930) x 37.4 (949.9) x 47 (1193.8)
Weight Ibs (kg) 1575 (714)
STANDARD ENCLOSURE
L x W x H in (mm)
94.8 (2408.9) x 38 (965.1) x 49.5 (1258.1)
Weight Ibs (kg)
Steel: 2100 (952)
Aluminum: 1754 (795)
LEVEL 1 ACOUSTIC ENCLOSURE
Lx W x H in (mm)
112.5(2857.1) x 38(965.1) x 49.5(1258.1)
Weight Ibs (kg)
Steel: 2140 (970)
Aluminum: 1767 (8011
LEVEL 2 ACOUSTIC ENCLOSURE
L x W x H in (mm)
94.8 (2407) x 38 (965.1) x 62 (1573.9)
Weight Ibs (kg)
Steel: 2328 (1056)
Aluminum: 1831 (830)
YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER I
Snecileatten ChaaNedstics may change wimoN notice. Neaseconsuft a Generate Nwzr Systems Intlustrul Dealer for detailed installation t awings.
Generac Power Systems, Inc. • S45 W29290 HWY.. 59, Waukesha, WI 53189 • generac.com
@2013 senate Power Systems, Ine. All rights reserved. AD snecifsa5ons are subject to charge wNwN matloe. Part No. OK4265-0( Primed in U.SA 12/10/13