St. Lucie County
DATE: 1/05/16 JOB ORDER #: 16-109
CLIENT: CP Rankin, Inc.
ADDRESS: 4359 County Line Road Chalfont, PA 18914
PROJECT: Advanced Auto Parts # 9232 22 Ga. Steel Insulated Roof Deck
ADDRESS: 7075 Indrio Road Fort Pierce, FL
FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Height= 16' Exposure: C
Length = 104' Category: II
Width = 65' Slope: < 7°
Parapet Wall: 18" to 24" Commercial
Design Calculations:
Basic/Ultimate Wind Speed: V ii=170 mph
Nominal Wind Speed: Vasd=V dt*y0.6
(asd = allowable strength design)
K� = 0.86, Kzt = 1.0, Kd = 0.85
Velocity Pressure: q = 0.00256*KzK,&V2
Velocity Pressure ("it): q=0.00256(0.86)(1.0)(0.85)(170)2] = 54.08 psf
Velocity Pressure (asd): q=0.00256(0.86)(1.0)(0.85)(170*v0.6)2] = 32.45 psf
Width of Pressure Coefficient: 0.1(65) = 6.5'
0.4(16') = 6.4' ) use: 6'6"
Effective Wind Area: <10ft2
For parapet height three feet (3D or larger, zone three (3) shall be treated as zone two (2).
External Pressure Coefficient:
1)
GCP1
= -1.0
2)
GCP2
= -1.8
3)
GCP3
= -2.8
Internal Pressure Coefficient:
1) GCPi =
MM
JAN 16 2016
ri
'v' Q v
Quality �1b\ Any/.3swranee
— G
Page 2, 1/05/16, Job Or,. 'I 16-109
CP Rankin, Inc.
Advanced Auto Parts # 9232 - 22 Ga. Steel Insulated Roof Deck
7075 Indrio Road; Fort Pierce, FL:
Design Pressures Based on Vasd:
1)
Field
P1 =
32.45*[(-1.0)—(0.18)]=-38.3psf
2)
Perimeter
P2 =
32.45*[(-1.8) — (0.18)] = -64.2 psf
3)
Comers
P3 =
32.45*[(-2.8) — (0.18)] _ -96.7 psf
Attachment Requirements Per RAS-117:
FLO A
Based on the requirements of Notice of Acceptance # 13-1212.04 pg 52 of 89, System
Type C(28), with a maximum design pressure-45psf, the following are our recommended
patterns for fastening minimum 0.5" thick ISO 95+ GL, RESISTA, ISOGARD HD
insulation layer to the minimum 22 ga. steel deck with supports spaced maximum 6 ft.
o.c. (with a MCRF of 3601bf with approved Firestone Heavy -Duty # 15 fasteners and
U1traPly TPO InvisiWeld Plates:
Fasteners Per Board(Minimum)
Insulation Board
Field
Perimeter
Corners
4' x 4'
4
6
9
4'x8'
8
12
18
Notes: Comers and perimeter area dimension shall not be less than a = 66"
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2014 Edition.
Wind load calculations based on ASCE 7-10, FBC 2014 and information
provided by client. Client is responsible for verifying existing conditions as it
pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications
Sincerely,
Mark A. Mesiano, P:E.
Florida Engineering & Testing, Inc.
Florida Reg. No. 48202
Certificate of Authorization No. 6923
ENGINEERING & TESTING, INC.
�(:Hw Phone: (866) 781-6889 Wax: (866) 784-8550
eww floridaengineeringandtesting.com
j 1i l r L� 250 S.W.13'h Avenue
Ste co 'n1ir1ty Pompano Beach, FL33069
DATE: 1/05/16 JOB ORDER #: 16-109
CLIENT: CP Rankin, Inc.
ADDRESS: 4359 County Line Road Chalfont, PA 18914
PROJECT: Advanced Auto Parts # 9232 22 Ga. Steel Insulated Roof Deck
ADDRESS: 7075 Indrio Road Fort Pierce, FL
FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Height = 16' Exposure: C Basic/Ultimate Wind Speed: Vmt=170 mph
Length = 104' Category: H Nominal Wind Speed: Vasd=Vuu*v0.6
Width = 65' Slope: < 7° (asd = allowable strength design)
Parapet Wall: 18" to 24" Commercial Kz = 0.86, Kzt =1.0, Kd = 0.85
Design Calculations:
Velocity Pressure: q = 0.00256*KzKtKdV2
Velocity Pressure (,at): q=0.00256(0.86)(1.0)(0.85)(170)2] = 54.08 psf
Velocity Pressure (asd): q=0.00256(0.86)(1.0)(0.85)(170*v0.6)2] = 32.45 psf
Width of Pressure Coefficient: 0.1(65') = 6.5'
0.4(16') = 6.4' ) use: 6'6"
Effective Wind Area: <lOft
For parapet height three feet (T) or larger, zone three (3) shall be treated as zone two (2).
External Pressure Coefficient:
1) GCP1 = -1.0
2) GCP2 = -1.8
3) GCP3 = -2.8
•Internal Pressure Coefficient:
4) j GCP, 0.18 --
1 %ti
mile
Quality 4\'AOf ✓lacurance
Page 2, 1/05/16, Job Or,, _ 116-109
CP Rankin, Inc.
Advanced Auto Parts # 9232 - 22 Ga. Steel Insulated Roof Deck
7075 Indrio Road; Fort Pierce, FL:
Design Pressures Based on Vs:d:
1)
Field
P1
32.45*[(-1.0)—(0.18)]=-38.3psf
2)
Perimeter
P2 =
32.45*[(-1.8) — (0.18)] = -64.2 psf
3)
Comers
P3 =
32.45*[(-2.8) — (0.18)] = -96.7 psf
Attachment Requirements Per RAS-117:
FILORIPA
Based on the requirements of Notice of Acceptance # 13-1212.04 pg 52 of 89, System
Type C(28), with a maximum design pressure-45psf, the following are our recommended
patterns for fastening minimum 0.5" thick ISO 95+ GL, RESISTA, ISOGARD HD
insulation layer to the minimum 22 ga. steel deck with supports spaced maximum 6 ft.
o.c. (with a MCRF of 3601bf) with approved Firestone Heavy -Duty # 15 fasteners and
UltraPly TPO InvisiWeld Plates:
Fasteners Per Board nimum
Insulation Board
Field
I Perimeter
Corners
4' x 4'
4
L6
9
4' x 8'
8
1 12
18
Notes: Corners and perimeter area dimension shall not be less than a = 66"
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2014 Edition.
Wind load calculations based on ASCE 7-10, FBC 2014 and information
provided by client. Client is responsible for verifying existing conditions as it
pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications
Sincerely,
Mark A. Mesiaho, P.E. '
Florida Engineering & Testing, Inc.
Florida Reg. No. 48202
Certificate of Authorization No. 6923